Power Transmission

A question to start

Vietnam's 500 kV500\ \text{kV} North–South transmission line, opened in 1994, carries electricity about 1500 km1500\ \text{km}. Such voltages need huge towers and long insulators. Why not send the power at a safe 230 V230\ \text{V} and save all that trouble?

The idea

A power line has resistance RR (it is many kilometres of metal). The current II in it heats the line, and that power is simply lost:

Ploss=I2RP_{loss} = I^2 R

For a given power PP sent at voltage UU, the current is I=PUI = \frac{P}{U} (taking the current and voltage in step, as for a resistive load), so

Ploss=P2RU2P_{loss} = \frac{P^2 R}{U^2}
Quantity Symbol Unit
power sent PP W\text{W}
transmission voltage (rms) UU V\text{V}
resistance of the line (both wires) RR Ω\Omega
power lost as heat in the line PlossP_{loss} W\text{W}

The loss falls with the square of the voltage: 1010 times the voltage, 1100\frac{1}{100} of the loss. A thicker line would also help, but copper and aluminium are heavy and expensive; raising the voltage is far cheaper. The voltage drop along the line, ΔU=IR\Delta U = IR, shrinks too.

So the grid works like this: the generator makes about 1010–25 kV25\ \text{kV}; a step-up transformer raises it to 110110, 220220 or 500 kV500\ \text{kV} for the long lines; step-down transformers in substations lower it in stages to about 22 kV22\ \text{kV} for local lines and finally to 230 V230\ \text{V} for homes. This is the main reason the world uses AC: transformers only work with AC.

G 20 kVstep-up500 kV linestep-down230 V high voltage, small current: small I^2 R losses

Two overlapping circles are the circuit symbol for a transformer.

Worked examples

Example 1. A station sends 1.0 MW1.0\ \text{MW} through a line of total resistance 10 Ω10\ \Omega. Find the current and the power lost when it sends at (a) 10 kV10\ \text{kV} and (b) 100 kV100\ \text{kV}.

  • Given: P=1.0×106 WP = 1.0 \times 10^6\ \text{W}, R=10 ΩR = 10\ \Omega; U=1.0×104 VU = 1.0 \times 10^4\ \text{V} or 1.0×105 V1.0 \times 10^5\ \text{V}.
  • Find: II, PlossP_{loss} in each case.
  • Formula: I=PUI = \frac{P}{U}, Ploss=I2RP_{loss} = I^2R.
  • Solve: (a) I=1.0×106 W1.0×104 V=100 AI = \frac{1.0 \times 10^6\ \text{W}}{1.0 \times 10^4\ \text{V}} = 100\ \text{A}, Ploss=(100 A)2×10 Ω=1.0×105 WP_{loss} = (100\ \text{A})^2 \times 10\ \Omega = 1.0 \times 10^5\ \text{W}. (b) I=10 AI = 10\ \text{A}, Ploss=(10 A)2×10 Ω=1.0×103 WP_{loss} = (10\ \text{A})^2 \times 10\ \Omega = 1.0 \times 10^3\ \text{W}.
  • Answer: (a) 100 A100\ \text{A}, 100 kW100\ \text{kW} lost (10%10\%); (b) 10 A10\ \text{A}, 1.0 kW1.0\ \text{kW} lost (0.1%0.1\%).
  • Check: ten times the voltage gives a hundredth of the loss, as Ploss∝1U2P_{loss} \propto \frac{1}{U^2} predicts.

Example 2. In case (a), how much voltage is lost along the line, and what voltage arrives?

  • Given: I=100 AI = 100\ \text{A}, R=10 ΩR = 10\ \Omega, U=10 kVU = 10\ \text{kV}.
  • Find: ΔU\Delta U, UendU_{end}.
  • Formula: ΔU=IR\Delta U = IR.
  • Solve: ΔU=100 A×10 Ω=1000 V\Delta U = 100\ \text{A} \times 10\ \Omega = 1000\ \text{V}; Uend=10 000−1000=9000 VU_{end} = 10\,000 - 1000 = 9000\ \text{V}.
  • Answer: 1000 V1000\ \text{V} is lost; 9.0 kV9.0\ \text{kV} arrives. At 100 kV100\ \text{kV} only 100 V100\ \text{V} would be lost.
  • Check: ΔU⋅I=1000×100=100 kW\Delta U \cdot I = 1000 \times 100 = 100\ \text{kW}, the same loss as in Example 1.

Try it: thin wire, warm wire (paper experiment)

The same effect is in every extension cord. Using Ploss=I2RP_{loss} = I^2R: an extension cord has R=0.2 ΩR = 0.2\ \Omega in total. Work out the power heating the cord for a 100 W100\ \text{W} lamp and for a 2000 W2000\ \text{W} heater on 230 V230\ \text{V}. (Answers: I=0.43 AI = 0.43\ \text{A}, 0.04 W0.04\ \text{W}; I=8.7 AI = 8.7\ \text{A}, 15 W15\ \text{W}.) Fifteen watts in a coiled-up cable can't escape, which is why the instructions on a cable reel say to unroll it fully before using a heater.

Common mistakes

  • Using the transmission voltage in P=U2RP = \frac{U^2}{R} for the line loss. The full UU is not across the line; use I2RI^2R with I=PUI = \frac{P}{U}.
  • Thinking high voltage means high current. For the same power, it means low current.
  • Forgetting that both wires (there and back) count in RR.

Practice

  1. The transmission voltage is doubled, with the same power and line. What happens to the loss?
Answer

Ploss∝1U2P_{loss} \propto \frac{1}{U^2}: it falls to a quarter.

  1. 5.0 MW5.0\ \text{MW} is sent at 220 kV220\ \text{kV} through a line of 20 Ω20\ \Omega. What fraction is lost?
Answer

I=5.0×1062.2×105=22.7 AI = \frac{5.0 \times 10^6}{2.2 \times 10^5} = 22.7\ \text{A}; Ploss=22.72×20=1.03×104 WP_{loss} = 22.7^2 \times 20 = 1.03 \times 10^4\ \text{W}, about 0.2%0.2\% of 5.0 MW5.0\ \text{MW}.

Test yourself

With the same power and line, raising the transmission voltage 10 times makes the line loss...

  1. 10 times larger
  2. 10 times smaller
  3. 100 times smaller
  4. unchanged

1 MW1\ \text{MW} at 10 kV10\ \text{kV} through 10 Ω10\ \Omega of line loses...

  1. 1 kW1\ \text{kW}
  2. 10 kW10\ \text{kW}
  3. 100 kW100\ \text{kW}
  4. 1 MW1\ \text{MW}

Why is electricity transmitted as AC rather than DC in most grids?

  1. AC travels faster
  2. AC voltage is easy to step up and down with transformers
  3. AC has no losses
  4. DC can't light lamps