A workshop compressor takes 2 kW2\ \text{kW} of real power from a 230 V230\ \text{V}, 50 Hz50\ \text{Hz} supply, but its current is 12.4 A12.4\ \text{A}, not the 8.7 A8.7\ \text{A} that 2000/2302000/230 suggests. The wiring, the fuse and the supply transformer must all carry the larger current, the cables lose I2RI^2R on it, and many electricity tariffs for business customers charge for it. A capacitor of about 83 μF83\ \mu\text{F} connected across the motor brings the current down to 9.2 A9.2\ \text{A} without changing the power the motor receives. This lesson builds the tool that makes such calculations one line long: complex power. The physics of PP and QQ is in Instantaneous and Average Power.

Safety note. Everything at 230 V230\ \text{V} in this lesson is calculation and simulation only. Mains wiring and power-factor capacitors on mains are work for qualified electricians; mains-rated capacitors also store a lethal charge after disconnection unless a discharge resistor is fitted. The hands-on part uses a function generator at signal level.

Complex power

For an element with RMS phasors V\mathbf{V} across it and I\mathbf{I} into it (passive sign convention), define

S=V I∗=VI∠(θv−θi)=VIcos⁡ϕ+jVIsin⁡ϕ=P+jQS = \mathbf{V}\,\mathbf{I}^{*} = V I \angle(\theta_v - \theta_i) = VI\cos\phi + jVI\sin\phi = P + jQ

The conjugate is what makes the angle come out as ϕ=θv−θi\phi = \theta_v - \theta_i, the load angle. One complex number now carries everything:

quantity formula unit
complex power S=VI∗=P+jQS = \mathbf{V}\mathbf{I}^{*} = P + jQ VA
apparent power ∣S∣=VI=P2+Q2\lvert S \rvert = VI = \sqrt{P^2 + Q^2} VA
real (active) power P=Re⁡S=I2RP = \operatorname{Re} S = I^2 R W
reactive power Q=Im⁡S=I2XQ = \operatorname{Im} S = I^2 X var
power factor pf=P/∣S∣=cos⁡ϕ\text{pf} = P/\lvert S \rvert = \cos\phi, "lagging" if Q>0Q > 0, "leading" if Q<0Q < 0 none

With V=ZI\mathbf{V} = Z\mathbf{I}, S=Z ∣I∣2=∣V∣2/Z∗S = Z\,\lvert \mathbf{I} \rvert^2 = \lvert \mathbf{V} \rvert^2 / Z^{*}: the complex power has the angle of the impedance.

Conservation. In any circuit, the complex powers of all elements sum to zero (Tellegen's theorem): the PP delivered by the sources equals the PP absorbed by the resistances, and the same holds separately for QQ. So the total SS of several loads on one supply is simply the sum of their SS values, whether they are in series or in parallel. (Apparent powers ∣S∣\lvert S \rvert do not add.)

The power triangle and correction

Drawn as a vector, SS is the hypotenuse of a right triangle with legs PP and QQ. Most industrial loads (motors, transformers, fluorescent ballasts) are inductive, Q>0Q > 0. A capacitor in parallel has QC=−ωCV2<0Q_C = -\omega C V^2 < 0 and no PP. Adding it leaves the load's voltage, current and PP untouched but shortens the QQ leg of the supply's triangle, and so the supply current:

QC=P(tan⁡ϕold−tan⁡ϕnew),C=QCωV2Q_C = P\left(\tan\phi_\text{old} - \tan\phi_\text{new}\right), \qquad C = \frac{Q_C}{\omega V^2}
P = 2000 W Q1 = 2040 var S1 = 2857 VA Qc = -1383 var (capacitor) S2 = 2105 VA, Q2 = 657 var 45.6 deg 18.2 deg 230 V, 50 Hz load: calculation only

Correcting all the way to pf=1\text{pf} = 1 is rarely worth it: the last few hundredths cost a lot of capacitance, the load varies, and overcorrection makes the plant leading. Targets of 0.9 to 0.98 are typical. Whether and how a utility charges for reactive power depends on the country and the tariff; as of 2026 many tariffs for commercial and industrial customers set a minimum power factor (values such as 0.9 or 0.95 are common) or bill reactive energy in kvarh, while household tariffs usually do not. Check your own supplier's current tariff rather than relying on a general figure.

Worked example: the compressor (calculation only)

Given: a single-phase load of P=2.00 kWP = 2.00\ \text{kW} at pf=0.70\text{pf} = 0.70 lagging, on V=230 VV = 230\ \text{V} RMS, 50 Hz50\ \text{Hz}.

Find: SS, QQ and the current; the parallel capacitor that raises the pf to 0.950.95; the new current.

Solve:

∣S1∣=Ppf=20000.70=2857 VA,ϕ1=arccos⁡0.70=45.57∘Q1=Ptan⁡ϕ1=2000⋅1.0202=2040 var,I1=2857230=12.42 Aϕ2=arccos⁡0.95=18.19∘,Q2=2000⋅0.3287=657 varQC=2040−657=1383 varC=13832π⋅50⋅2302=83.2 μFI2=Ppf2V=20000.95⋅230=9.15 A\begin{aligned} \lvert S_1 \rvert &= \frac{P}{\text{pf}} = \frac{2000}{0.70} = 2857\ \text{VA}, \quad \phi_1 = \arccos 0.70 = 45.57^\circ \\ Q_1 &= P\tan\phi_1 = 2000 \cdot 1.0202 = 2040\ \text{var}, \quad I_1 = \frac{2857}{230} = 12.42\ \text{A} \\ \phi_2 &= \arccos 0.95 = 18.19^\circ, \quad Q_2 = 2000 \cdot 0.3287 = 657\ \text{var} \\ Q_C &= 2040 - 657 = 1383\ \text{var} \\ C &= \frac{1383}{2\pi \cdot 50 \cdot 230^2} = 83.2\ \mu\text{F} \\ I_2 &= \frac{P}{\text{pf}_2 V} = \frac{2000}{0.95 \cdot 230} = 9.15\ \text{A} \end{aligned}

Check: ∣S2∣=20002+6572=2105 VA=9.15⋅230\lvert S_2 \rvert = \sqrt{2000^2 + 657^2} = 2105\ \text{VA} = 9.15 \cdot 230. The current falls by 26 %, so the I2RI^2R loss in the supply cable falls by 1−(9.15/12.42)2=46 %1 - (9.15/12.42)^2 = 46\,\%. The motor's own current is unchanged at 12.42 A; only the current from the supply drops.

In Python

The first part computes S=VI∗S = \mathbf{V}\mathbf{I}^{*} for an impedance chosen to represent the compressor (Z=V2/S∗Z = V^2/S^{*}); the second sizes the capacitor for several targets.

python · try it yourself
import numpy as np

# 1. complex power from phasors: S = V I*
V = 230.0                                # rms, reference phase
Z = 12.96 + 13.22j                       # inductive load: 2 kW at pf 0.70
I = V / Z
S = V * np.conj(I)
print(f"I = {abs(I):.2f} A at {np.degrees(np.angle(I)):.1f} deg")
print(f"S = {S.real:.0f} W {S.imag:+.0f}j var, |S| = {abs(S):.0f} VA, pf = {S.real / abs(S):.3f}")

# 2. capacitor for power-factor correction (parallel, 50 Hz)
def correction(P, pf_old, pf_new, V=230.0, f=50.0):
    Qc = P * (np.tan(np.arccos(pf_old)) - np.tan(np.arccos(pf_new)))
    return Qc, Qc / (2 * np.pi * f * V ** 2)

P = S.real
print(" target pf   Qc (var)    C (uF)   line current (A)")
for pf_new in (0.90, 0.95, 0.99, 1.00):
    Qc, C = correction(P, 0.70, pf_new)
    print(f"{pf_new:9.2f} {Qc:10.0f} {C * 1e6:9.1f} {P / (pf_new * V):12.2f}")
I = 12.42 A at -45.6 deg
S = 2000 W +2040j var, |S| = 2857 VA, pf = 0.700
 target pf   Qc (var)    C (uF)   line current (A)
     0.90       1072      64.5         9.66
     0.95       1383      83.2         9.15
     0.99       1756     105.6         8.79
     1.00       2041     122.8         8.70

Going from 0.95 to 1.00 needs 48 % more capacitance for a further 5 % cut in current: diminishing returns.

Guided lab: power-factor correction at signal level

Hand calculation. A scaled model: a function generator at 1.00 kHz1.00\ \text{kHz}, 5.0 V5.0\ \text{V} peak drives an "inductive load" of R=100 ΩR = 100\ \Omega in series with L=22 mHL = 22\ \text{mH} (XL=138.2 ΩX_L = 138.2\ \Omega, pf=0.586\text{pf} = 0.586 lagging). Without correction the generator supplies 29.3 mA29.3\ \text{mA} peak. For pf=1\text{pf} = 1 the parallel capacitor must cancel the load's susceptance: C=L/(R2+ω2L2)=0.756 μFC = L/(R^2 + \omega^2 L^2) = 0.756\ \mu\text{F}. The nearest standard value, 0.68 μF0.68\ \mu\text{F}, gives pf=0.991\text{pf} = 0.991 and a source current of 17.3 mA17.3\ \text{mA} peak, while P=42.9 mWP = 42.9\ \text{mW} stays the same.

Simulation. The netlist lab models it with peak phasors (source magnitude 5). Slide C1C_1 from its smallest value up through 0.756 μF0.756\ \mu\text{F} and watch ∣I(V1)∣\lvert \mathbf{I}(V_1) \rvert pass through a minimum while I(L1)\mathbf{I}(L_1), the load's own current, does not move.

0241001k10kf (Hz)|V| (V)0 A100 mA200 mA|I| (A)|V(in)||I(V1)||I(L1)||I(C1)|phasors at f = 1.000 kHz (magnitude @ phase)V(in)5.00 V @ 0.0 degV(m)4.05 V @ 35.9 degI(V1)17.3 mA @ 172.1 degI(R1)29.3 mA @ -54.1 degI(L1)29.3 mA @ -54.1 degI(C1)21.4 mA @ 90.0 deg

At the default 0.68 μF0.68\ \mu\text{F} the lab reads ∣I(V1)∣=17.34 mA\lvert \mathbf{I}(V_1) \rvert = 17.34\ \text{mA} at 172.1∘172.1^\circ (SPICE's sign convention, so the current delivered by the source is at −7.9∘-7.9^\circ, almost in phase with the voltage), while I(L1)\mathbf{I}(L_1) stays at 29.31 mA29.31\ \text{mA} at −54.1∘-54.1^\circ; set C1=0.01 μFC_1 = 0.01\ \mu\text{F} (nearly no correction) and it reads 29.05 mA29.05\ \text{mA}, close to the uncorrected 29.3 mA29.3\ \text{mA}.

What you would measure. Insert a 10 Ω10\ \Omega sense resistor in the generator's ground return and watch its voltage on the scope (it adds 10 Ω10\ \Omega to the source path, which lowers the readings by about 3 %). Without the capacitor expect about 0.29 V0.29\ \text{V} peak across the sense resistor, phase-shifted about 54∘54^\circ behind the generator; with 0.68 μF0.68\ \mu\text{F} about 0.17 V0.17\ \text{V} peak and nearly in phase. Capacitor (±10 %\pm 10\,\%) and inductor (±10 %\pm 10\,\%, plus winding resistance) tolerances move the minimum, so sweep a few values; the trend, not the third digit, is the result.

Hazards and safe setup. Function generator at ≤10 V\le 10\ \text{V} peak only. Do not scale this experiment up to mains: the same circuit at 230 V needs mains-rated parts, enclosures and qualified work.

Pitfalls

  • Forgetting the conjugate. VI\mathbf{V}\mathbf{I} (no conjugate) has the angle θv+θi\theta_v + \theta_i, which means nothing.
  • Adding apparent powers. Add SS as complex numbers; ∣S1∣+∣S2∣\lvert S_1 \rvert + \lvert S_2 \rvert overestimates unless the angles are equal.
  • Peak phasors in S=VI∗S = \mathbf{V}\mathbf{I}^{*}. With peak values, S=12VmIm∗S = \tfrac{1}{2}\mathbf{V}_m\mathbf{I}_m^{*}.
  • Putting the correction capacitor in series. Series correction changes the load voltage; power-factor capacitors go in parallel.
  • Overcorrection. Too much capacitance gives a leading power factor and, with light loads, raised voltages.

Practice

  1. A 230 V230\ \text{V} load draws S=1.5+j0.8 kVAS = 1.5 + j0.8\ \text{kVA}. Find the current and the power factor. (Calculation only.)
  2. Two loads share a supply: 3 kW3\ \text{kW} at pf 0.80.8 lagging and 2 kW2\ \text{kW} at pf 1.01.0. What is the combined power factor?
  3. What capacitance at 50 Hz50\ \text{Hz}, 230 V230\ \text{V} supplies QC=−500 varQ_C = -500\ \text{var}?
Answer
  1. ∣S∣=1.52+0.82=1.70 kVA\lvert S \rvert = \sqrt{1.5^2 + 0.8^2} = 1.70\ \text{kVA}, I=1700/230=7.39 AI = 1700/230 = 7.39\ \text{A}, pf=1.5/1.7=0.882\text{pf} = 1.5/1.7 = 0.882 lagging.
  2. Q=3000tan⁡(arccos⁡0.8)=2250 varQ = 3000\tan(\arccos 0.8) = 2250\ \text{var}; S=5000+j2250S = 5000 + j2250, pf=5000/5483=0.912\text{pf} = 5000/5483 = 0.912 lagging.
  3. C=500/(2π⋅50⋅2302)=30.1 μFC = 500/(2\pi \cdot 50 \cdot 230^2) = 30.1\ \mu\text{F}.

Test yourself

With RMS phasors V=100∠30∘\mathbf{V} = 100\angle 30^\circ V and I=2∠−15∘\mathbf{I} = 2\angle -15^\circ A, what is SS?

  1. 200∠15∘200\angle 15^\circ VA
  2. 200∠45∘200\angle 45^\circ VA
  3. 200∠−45∘200\angle -45^\circ VA
  4. 100∠45∘100\angle 45^\circ VA

A parallel capacitor is added to an inductive load on a fixed-voltage supply. What stays the same?

  1. the supply current
  2. the load's real power PP
  3. the supply's reactive power
  4. the power factor seen by the supply

Which statement about complex power in a circuit is true?

  1. apparent powers of all elements sum to zero
  2. complex powers of all elements sum to zero
  3. only real powers are conserved
  4. reactive power is always positive

A load of 10 kW at pf 0.6 lagging is corrected to pf 1.0. How much capacitive reactive power is needed?

  1. 6.0 kvar
  2. 8.0 kvar
  3. 13.3 kvar
  4. 10 kvar