Complex Power, Power Factor and Correction
A workshop compressor takes of real power from a , supply, but its current is , not the that suggests. The wiring, the fuse and the supply transformer must all carry the larger current, the cables lose on it, and many electricity tariffs for business customers charge for it. A capacitor of about connected across the motor brings the current down to without changing the power the motor receives. This lesson builds the tool that makes such calculations one line long: complex power. The physics of and is in Instantaneous and Average Power.
Safety note. Everything at in this lesson is calculation and simulation only. Mains wiring and power-factor capacitors on mains are work for qualified electricians; mains-rated capacitors also store a lethal charge after disconnection unless a discharge resistor is fitted. The hands-on part uses a function generator at signal level.
Complex power
For an element with RMS phasors across it and into it (passive sign convention), define
The conjugate is what makes the angle come out as , the load angle. One complex number now carries everything:
| quantity | formula | unit |
|---|---|---|
| complex power | VA | |
| apparent power | VA | |
| real (active) power | W | |
| reactive power | var | |
| power factor | , "lagging" if , "leading" if | none |
With , : the complex power has the angle of the impedance.
Conservation. In any circuit, the complex powers of all elements sum to zero (Tellegen's theorem): the delivered by the sources equals the absorbed by the resistances, and the same holds separately for . So the total of several loads on one supply is simply the sum of their values, whether they are in series or in parallel. (Apparent powers do not add.)
The power triangle and correction
Drawn as a vector, is the hypotenuse of a right triangle with legs and . Most industrial loads (motors, transformers, fluorescent ballasts) are inductive, . A capacitor in parallel has and no . Adding it leaves the load's voltage, current and untouched but shortens the leg of the supply's triangle, and so the supply current:
Correcting all the way to is rarely worth it: the last few hundredths cost a lot of capacitance, the load varies, and overcorrection makes the plant leading. Targets of 0.9 to 0.98 are typical. Whether and how a utility charges for reactive power depends on the country and the tariff; as of 2026 many tariffs for commercial and industrial customers set a minimum power factor (values such as 0.9 or 0.95 are common) or bill reactive energy in kvarh, while household tariffs usually do not. Check your own supplier's current tariff rather than relying on a general figure.
Worked example: the compressor (calculation only)
Given: a single-phase load of at lagging, on RMS, .
Find: , and the current; the parallel capacitor that raises the pf to ; the new current.
Solve:
Check: . The current falls by 26 %, so the loss in the supply cable falls by . The motor's own current is unchanged at 12.42 A; only the current from the supply drops.
In Python
The first part computes for an impedance chosen to represent the compressor (); the second sizes the capacitor for several targets.
import numpy as np
# 1. complex power from phasors: S = V I*
V = 230.0 # rms, reference phase
Z = 12.96 + 13.22j # inductive load: 2 kW at pf 0.70
I = V / Z
S = V * np.conj(I)
print(f"I = {abs(I):.2f} A at {np.degrees(np.angle(I)):.1f} deg")
print(f"S = {S.real:.0f} W {S.imag:+.0f}j var, |S| = {abs(S):.0f} VA, pf = {S.real / abs(S):.3f}")
# 2. capacitor for power-factor correction (parallel, 50 Hz)
def correction(P, pf_old, pf_new, V=230.0, f=50.0):
Qc = P * (np.tan(np.arccos(pf_old)) - np.tan(np.arccos(pf_new)))
return Qc, Qc / (2 * np.pi * f * V ** 2)
P = S.real
print(" target pf Qc (var) C (uF) line current (A)")
for pf_new in (0.90, 0.95, 0.99, 1.00):
Qc, C = correction(P, 0.70, pf_new)
print(f"{pf_new:9.2f} {Qc:10.0f} {C * 1e6:9.1f} {P / (pf_new * V):12.2f}")I = 12.42 A at -45.6 deg
S = 2000 W +2040j var, |S| = 2857 VA, pf = 0.700
target pf Qc (var) C (uF) line current (A)
0.90 1072 64.5 9.66
0.95 1383 83.2 9.15
0.99 1756 105.6 8.79
1.00 2041 122.8 8.70
Going from 0.95 to 1.00 needs 48 % more capacitance for a further 5 % cut in current: diminishing returns.
Guided lab: power-factor correction at signal level
Hand calculation. A scaled model: a function generator at , peak drives an "inductive load" of in series with (, lagging). Without correction the generator supplies peak. For the parallel capacitor must cancel the load's susceptance: . The nearest standard value, , gives and a source current of peak, while stays the same.
Simulation. The netlist lab models it with peak phasors (source magnitude 5). Slide from its smallest value up through and watch pass through a minimum while , the load's own current, does not move.
At the default the lab reads at (SPICE's sign convention, so the current delivered by the source is at , almost in phase with the voltage), while stays at at ; set (nearly no correction) and it reads , close to the uncorrected .
What you would measure. Insert a sense resistor in the generator's ground return and watch its voltage on the scope (it adds to the source path, which lowers the readings by about 3 %). Without the capacitor expect about peak across the sense resistor, phase-shifted about behind the generator; with about peak and nearly in phase. Capacitor () and inductor (, plus winding resistance) tolerances move the minimum, so sweep a few values; the trend, not the third digit, is the result.
Hazards and safe setup. Function generator at peak only. Do not scale this experiment up to mains: the same circuit at 230 V needs mains-rated parts, enclosures and qualified work.
Pitfalls
- Forgetting the conjugate. (no conjugate) has the angle , which means nothing.
- Adding apparent powers. Add as complex numbers; overestimates unless the angles are equal.
- Peak phasors in . With peak values, .
- Putting the correction capacitor in series. Series correction changes the load voltage; power-factor capacitors go in parallel.
- Overcorrection. Too much capacitance gives a leading power factor and, with light loads, raised voltages.
Practice
- A load draws . Find the current and the power factor. (Calculation only.)
- Two loads share a supply: at pf lagging and at pf . What is the combined power factor?
- What capacitance at , supplies ?
Answer
- , , lagging.
- ; , lagging.
- .
Test yourself
With RMS phasors V and A, what is ?
- VA
- VA
- VA
- VA
A parallel capacitor is added to an inductive load on a fixed-voltage supply. What stays the same?
- the supply current
- the load's real power
- the supply's reactive power
- the power factor seen by the supply
Which statement about complex power in a circuit is true?
- apparent powers of all elements sum to zero
- complex powers of all elements sum to zero
- only real powers are conserved
- reactive power is always positive
A load of 10 kW at pf 0.6 lagging is corrected to pf 1.0. How much capacitive reactive power is needed?
- 6.0 kvar
- 8.0 kvar
- 13.3 kvar
- 10 kvar