An Introduction to Three-Phase Circuits
Almost all electrical energy is generated, transmitted and used by large machines as three-phase AC: three sinusoidal voltages of equal size, apart. Why three wires (or four) instead of two? Because a balanced three-phase load draws constant instantaneous power, so motors run smoothly; because three conductors carry three times the power of one single-phase pair with only 1.5 times the copper; and because three phases make a rotating magnetic field for free. This lesson applies the phasor tools of this course (Sinusoids and Phasors, AC Nodal and Mesh Analysis, Complex Power, Power Factor and Correction) to three-phase systems. Generation, transformers, faults and protection follow in Power Systems.
Safety. Three-phase supplies in buildings are 230/400 V or higher and can kill. In this course three-phase circuits are taught by calculation and simulation only: no hands-on work on three-phase equipment, ever. Installation and measurement on such systems is work for qualified people with rated instruments.
Phase sequence and the balanced source
A balanced three-phase source has three phase voltages (RMS phasors), here in the sequence a, b, c (also called L1, L2, L3):
Each phase voltage is measured from a line to the source's star point, the neutral N. The voltage between two lines is the line voltage:
The low-voltage public supply in Europe and many other regions is nominally at (IEC 60038, IEC standard voltages, edition 7.0, 2009, with amendment 1 of 2021): from line to neutral and between lines. Strictly ; 400 V is the rounded nominal value. North America uses other combinations, such as and at .
Star (Y) and delta (D) loads
A star (Y) load connects one impedance from each line to a common star point N'. Each load impedance sees a phase voltage, and its current is the line current:
A delta (D) load connects each impedance between two lines, so it sees a line voltage; each line current is the difference of two load currents:
Balanced means all three impedances are equal. Then the three line currents are equal in size and apart, they sum to zero, and the neutral wire carries no current: N and N' are at the same potential whether or not they are connected. That allows the key simplification of three-phase analysis, per-phase analysis: solve phase a alone as a single-phase circuit (line to neutral), then shift the answers by and for phases b and c. A balanced delta load is first replaced by its equivalent star, (Delta-Wye Conversion and Bridge Circuits).
The total power of a balanced load, from either connection:
where is the angle of the load impedance. The sum of the three waveforms is constant and equal to : the oscillating parts cancel, which is why three-phase motors produce smooth torque.
Worked example: the same load in star and in delta
Given: a balanced , supply (sequence a, b, c, as reference); three equal impedances per phase. (Calculation only.)
Find: line currents, neutral current and power with the load in star, then in delta.
Solve: , , .
Check: . In delta each impedance gets times the voltage, so times the power: connecting a heater or a motor winding designed for star in delta overloads it by a factor of 3. This is also the idea behind star-delta motor starting, covered in the machines course.
An unbalanced star load: why the neutral matters
Real loads in buildings are single-phase appliances spread over the three phases, so they are never exactly balanced. With a neutral wire, each load still gets its own and the neutral carries the unbalance current. Without a neutral (3-wire), the load star point N' floats to a voltage given by Millman's theorem,
and the load voltages become unequal: some loads get more than . A broken neutral in a building is therefore dangerous for appliances, not only an inconvenience.
import numpy as np
a = np.exp(-2j * np.pi / 3) # 1 at -120 deg
V = 230.0 # phase voltage, rms
Vs = V * np.array([1, a, a ** 2]) # Va, Vb, Vc (sequence a-b-c)
def pol(z):
return f"{abs(z):7.2f} at {np.degrees(np.angle(z)):+7.1f}"
def star(Z, neutral=True):
Y = 1 / Z
VN = 0 if neutral else (Vs * Y).sum() / Y.sum() # Millman: star-point shift
I = (Vs - VN) * Y
return I, VN, ((Vs - VN) * np.conj(I)).sum()
Zp = 20 + 10j
Z = np.array([Zp, Zp, Zp])
I, _, S = star(Z)
print("balanced star: Ia =", pol(I[0]), "A | IN =", f"{abs(I.sum()):.2f} A",
f"| P = {S.real:.0f} W, Q = {S.imag:.0f} var")
Vab = Vs[0] - Vs[1]
print("line voltage Vab =", pol(Vab), "V")
Vca = Vs[2] - Vs[0]
Iab, Ica = Vab / Zp, Vca / Zp # delta: each load across a line voltage
print("balanced delta: Iab =", pol(Iab), "A | Ia = Iab - Ica =", pol(Iab - Ica), "A",
f"| P = {3 * abs(Iab) ** 2 * Zp.real:.0f} W")
Z = np.array([Zp, 2 * Zp, Zp]) # phase b load impedance doubled
for neutral in (True, False):
I, VN, S = star(Z, neutral)
vload = np.abs(I * Z)
print(f"unbalanced, {'4-wire' if neutral else '3-wire'}: IN = {abs(I.sum()):5.2f} A,",
f"VN'N = {abs(VN):5.2f} V, load volts = {np.round(vload, 1)}")balanced star: Ia = 10.29 at -26.6 A | IN = 0.00 A | P = 6348 W, Q = 3174 var
line voltage Vab = 398.37 at +30.0 V
balanced delta: Iab = 17.82 at +3.4 A | Ia = Iab - Ica = 30.86 at -26.6 A | P = 19044 W
unbalanced, 4-wire: IN = 5.14 A, VN'N = 0.00 V, load volts = [230. 230. 230.]
unbalanced, 3-wire: IN = 0.00 A, VN'N = 46.00 V, load volts = [210.8 276. 210.8]
With the phase b load halved (its impedance doubled), the neutral carries . Remove the neutral and phase b's load sees , 20 % above its rating, while the other two get .
Guided lab (simulation only): balanced and unbalanced loads
Hand calculation. The numbers above: balanced star , , ; delta , ; phase b load doubled: with the neutral, without it.
Simulation. The three-phase lab solves exactly these cases. At its defaults ( phase voltage, , , star, 4-wire) it reads a line voltage of , , a neutral current of zero, , and a power factor of . Then:
- Switch to delta: the line currents read , the phase current , .
- Back to star, set : falls to and the neutral current reads .
- Switch the star neutral to 3-wire: the neutral shift reads and .
What you would measure (professionally, not in this course). A qualified technician with a CAT III or CAT IV rated three-phase power analyser would read line voltages near (the supply may legitimately deviate by up to about from nominal, depending on the national rules), equal line currents within a few percent on a balanced load, and a small neutral current from residual unbalance and harmonics. You will not do this; the simulation and the calculation are the lab.
Pitfalls
- Mixing line and phase quantities. Write or every time; the factor applies between them, not to currents in a star load.
- Using for unbalanced loads. That formula is for balanced systems; otherwise add the three values.
- Per-phase analysis on an unbalanced 3-wire load. The star point shifts; use nodal analysis (Millman's theorem).
- Forgetting the shift between line and phase voltages (and between line and phase currents in delta).
- Thinking the neutral is "safe". It is a current-carrying conductor and can be at a dangerous voltage, especially when broken.
Practice
- A balanced star load draws per line from a (line) supply at lagging. Find , and .
- Three resistors are connected in delta to a line supply. Find the phase current, the line current and the total power.
- A balanced star load has (sequence a, b, c). Write and .
Answer
- ; ; .
- , , .
- , .
Test yourself
In a balanced star system with phase voltage, what is the line voltage?
- about
What current flows in the neutral of a balanced star load?
- the line current
- times the line current
- zero
- three times the line current
Three identical impedances take 5 kW in star. How much do they take in delta on the same supply?
- 1.67 kW
- 5 kW
- 8.66 kW
- 15 kW
Why can a broken neutral damage single-phase appliances in a building?
- the frequency changes
- the load star point floats, so lightly loaded phases can get well above 230 V
- the current doubles in every phase
- it reverses the phase sequence