Home › Circuit Theory & Network Analysis › An Introduction to Three-Phase Circuits

An Introduction to Three-Phase Circuits

Almost all electrical energy is generated, transmitted and used by large machines as three-phase AC: three sinusoidal voltages of equal size, 120∘120^\circ apart. Why three wires (or four) instead of two? Because a balanced three-phase load draws constant instantaneous power, so motors run smoothly; because three conductors carry three times the power of one single-phase pair with only 1.5 times the copper; and because three phases make a rotating magnetic field for free. This lesson applies the phasor tools of this course (Sinusoids and Phasors, AC Nodal and Mesh Analysis, Complex Power, Power Factor and Correction) to three-phase systems. Generation, transformers, faults and protection follow in Power Systems.

Safety. Three-phase supplies in buildings are 230/400 V or higher and can kill. In this course three-phase circuits are taught by calculation and simulation only: no hands-on work on three-phase equipment, ever. Installation and measurement on such systems is work for qualified people with rated instruments.

Phase sequence and the balanced source

A balanced three-phase source has three phase voltages (RMS phasors), here in the sequence a, b, c (also called L1, L2, L3):

Va=V∠0∘,Vb=V∠−120∘,Vc=V∠+120∘,Va+Vb+Vc=0\mathbf{V}_a = V\angle 0^\circ, \qquad \mathbf{V}_b = V\angle -120^\circ, \qquad \mathbf{V}_c = V\angle +120^\circ, \qquad \mathbf{V}_a + \mathbf{V}_b + \mathbf{V}_c = 0

Each phase voltage is measured from a line to the source's star point, the neutral N. The voltage between two lines is the line voltage:

Vab=Va−Vb=3 V∠30∘,VL=3 Vph\mathbf{V}_{ab} = \mathbf{V}_a - \mathbf{V}_b = \sqrt{3}\,V\angle 30^\circ, \qquad V_L = \sqrt{3}\,V_\text{ph}

The low-voltage public supply in Europe and many other regions is nominally 230/400 V230/400\ \text{V} at 50 Hz50\ \text{Hz} (IEC 60038, IEC standard voltages, edition 7.0, 2009, with amendment 1 of 2021): 230 V230\ \text{V} from line to neutral and 400 V400\ \text{V} between lines. Strictly 3⋅230=398.4 V\sqrt{3} \cdot 230 = 398.4\ \text{V}; 400 V is the rounded nominal value. North America uses other combinations, such as 120/208 V120/208\ \text{V} and 277/480 V277/480\ \text{V} at 60 Hz60\ \text{Hz}.

Va Vb Vc -Vb Vab = 398 V at +30 deg rotation: a, then b, then c

Star (Y) and delta (D) loads

+ Va 230 V, 0 deg line a Ia Z 20 + j10 Ohm + Vb 230 V, -120 deg line b Ib Z + Vc 230 V, +120 deg line c Ic Z N N' neutral (4-wire system) IN source (star) load (star)

A star (Y) load connects one impedance from each line to a common star point N'. Each load impedance sees a phase voltage, and its current is the line current:

star:Ia=VaZ,IL=Iph,Vph=VL3,IN=Ia+Ib+Ic\text{star:} \quad \mathbf{I}_a = \frac{\mathbf{V}_a}{Z}, \quad I_L = I_\text{ph}, \quad V_\text{ph} = \frac{V_L}{\sqrt{3}}, \quad \mathbf{I}_N = \mathbf{I}_a + \mathbf{I}_b + \mathbf{I}_c

A delta (D) load connects each impedance between two lines, so it sees a line voltage; each line current is the difference of two load currents:

delta:Iab=VabZ,Ia=Iab−Ica,IL=3 Iph (balanced)\text{delta:} \quad \mathbf{I}_{ab} = \frac{\mathbf{V}_{ab}}{Z}, \quad \mathbf{I}_a = \mathbf{I}_{ab} - \mathbf{I}_{ca}, \quad I_L = \sqrt{3}\,I_\text{ph}\ \text{(balanced)}

Balanced means all three impedances are equal. Then the three line currents are equal in size and 120∘120^\circ apart, they sum to zero, and the neutral wire carries no current: N and N' are at the same potential whether or not they are connected. That allows the key simplification of three-phase analysis, per-phase analysis: solve phase a alone as a single-phase circuit (line to neutral), then shift the answers by −120∘-120^\circ and +120∘+120^\circ for phases b and c. A balanced delta load is first replaced by its equivalent star, ZY=ZΔ/3Z_Y = Z_\Delta/3 (Delta-Wye Conversion and Bridge Circuits).

The total power of a balanced load, from either connection:

P=3VphIphcos⁡ϕ=3 VLILcos⁡ϕ,Q=3 VLILsin⁡ϕ,∣S∣=3 VLILP = 3V_\text{ph} I_\text{ph}\cos\phi = \sqrt{3}\,V_L I_L \cos\phi, \qquad Q = \sqrt{3}\,V_L I_L \sin\phi, \qquad \lvert S \rvert = \sqrt{3}\,V_L I_L

where ϕ\phi is the angle of the load impedance. The sum of the three p(t)p(t) waveforms is constant and equal to PP: the oscillating 2ω2\omega parts cancel, which is why three-phase motors produce smooth torque.

Worked example: the same load in star and in delta

Given: a balanced 230/400 V230/400\ \text{V}, 50 Hz50\ \text{Hz} supply (sequence a, b, c, Va\mathbf{V}_a as reference); three equal impedances Z=20+j10 ΩZ = 20 + j10\ \Omega per phase. (Calculation only.)

Find: line currents, neutral current and power with the load in star, then in delta.

Solve: ∣Z∣=500=22.36 Ω\lvert Z \rvert = \sqrt{500} = 22.36\ \Omega, ϕ=26.57∘\phi = 26.57^\circ, cos⁡ϕ=0.894\cos\phi = 0.894.

star:Ia=230∠0∘22.36∠26.57∘=10.29 A∠−26.57∘,IN=0PY=3⋅10.292⋅20=6348 W,QY=3⋅10.292⋅10=3174 vardelta:Iab=398.4∠30∘22.36∠26.57∘=17.82 A∠3.43∘Ia=3⋅17.82∠(3.43∘−30∘)=30.86 A∠−26.57∘PΔ=3⋅17.822⋅20=19 044 W=3PY\begin{aligned} \text{star:} \quad \mathbf{I}_a &= \frac{230\angle 0^\circ}{22.36\angle 26.57^\circ} = 10.29\ \text{A}\angle -26.57^\circ, \quad \mathbf{I}_N = 0 \\ P_Y &= 3 \cdot 10.29^2 \cdot 20 = 6348\ \text{W}, \quad Q_Y = 3 \cdot 10.29^2 \cdot 10 = 3174\ \text{var} \\ \text{delta:} \quad \mathbf{I}_{ab} &= \frac{398.4\angle 30^\circ}{22.36\angle 26.57^\circ} = 17.82\ \text{A}\angle 3.43^\circ \\ \mathbf{I}_a &= \sqrt{3} \cdot 17.82\angle(3.43^\circ - 30^\circ) = 30.86\ \text{A}\angle -26.57^\circ \\ P_\Delta &= 3 \cdot 17.82^2 \cdot 20 = 19\,044\ \text{W} = 3P_Y \end{aligned}

Check: 3⋅398.4⋅10.29⋅0.894=6348 W\sqrt{3} \cdot 398.4 \cdot 10.29 \cdot 0.894 = 6348\ \text{W}. In delta each impedance gets 3\sqrt{3} times the voltage, so 33 times the power: connecting a heater or a motor winding designed for star in delta overloads it by a factor of 3. This is also the idea behind star-delta motor starting, covered in the machines course.

An unbalanced star load: why the neutral matters

Real loads in buildings are single-phase appliances spread over the three phases, so they are never exactly balanced. With a neutral wire, each load still gets its own 230 V230\ \text{V} and the neutral carries the unbalance current. Without a neutral (3-wire), the load star point N' floats to a voltage VN′N\mathbf{V}_{N'N} given by Millman's theorem,

VN′N=Va/Za+Vb/Zb+Vc/Zc1/Za+1/Zb+1/Zc\mathbf{V}_{N'N} = \frac{\mathbf{V}_a/Z_a + \mathbf{V}_b/Z_b + \mathbf{V}_c/Z_c}{1/Z_a + 1/Z_b + 1/Z_c}

and the load voltages become unequal: some loads get more than 230 V230\ \text{V}. A broken neutral in a building is therefore dangerous for appliances, not only an inconvenience.

python · try it yourself
import numpy as np

a = np.exp(-2j * np.pi / 3)                   # 1 at -120 deg
V = 230.0                                     # phase voltage, rms
Vs = V * np.array([1, a, a ** 2])             # Va, Vb, Vc (sequence a-b-c)

def pol(z):
    return f"{abs(z):7.2f} at {np.degrees(np.angle(z)):+7.1f}"

def star(Z, neutral=True):
    Y = 1 / Z
    VN = 0 if neutral else (Vs * Y).sum() / Y.sum()   # Millman: star-point shift
    I = (Vs - VN) * Y
    return I, VN, ((Vs - VN) * np.conj(I)).sum()

Zp = 20 + 10j
Z = np.array([Zp, Zp, Zp])
I, _, S = star(Z)
print("balanced star:  Ia =", pol(I[0]), "A | IN =", f"{abs(I.sum()):.2f} A",
      f"| P = {S.real:.0f} W, Q = {S.imag:.0f} var")
Vab = Vs[0] - Vs[1]
print("line voltage Vab =", pol(Vab), "V")
Vca = Vs[2] - Vs[0]
Iab, Ica = Vab / Zp, Vca / Zp                 # delta: each load across a line voltage
print("balanced delta: Iab =", pol(Iab), "A | Ia = Iab - Ica =", pol(Iab - Ica), "A",
      f"| P = {3 * abs(Iab) ** 2 * Zp.real:.0f} W")

Z = np.array([Zp, 2 * Zp, Zp])                # phase b load impedance doubled
for neutral in (True, False):
    I, VN, S = star(Z, neutral)
    vload = np.abs(I * Z)
    print(f"unbalanced, {'4-wire' if neutral else '3-wire'}: IN = {abs(I.sum()):5.2f} A,",
          f"VN'N = {abs(VN):5.2f} V, load volts = {np.round(vload, 1)}")
balanced star:  Ia =   10.29 at   -26.6 A | IN = 0.00 A | P = 6348 W, Q = 3174 var
line voltage Vab =  398.37 at   +30.0 V
balanced delta: Iab =   17.82 at    +3.4 A | Ia = Iab - Ica =   30.86 at   -26.6 A | P = 19044 W
unbalanced, 4-wire: IN =  5.14 A, VN'N =  0.00 V, load volts = [230. 230. 230.]
unbalanced, 3-wire: IN =  0.00 A, VN'N = 46.00 V, load volts = [210.8 276.  210.8]

With the phase b load halved (its impedance doubled), the neutral carries 5.14 A5.14\ \text{A}. Remove the neutral and phase b's load sees 276 V276\ \text{V}, 20 % above its rating, while the other two get 211 V211\ \text{V}.

Guided lab (simulation only): balanced and unbalanced loads

Hand calculation. The numbers above: balanced star IL=10.29 AI_L = 10.29\ \text{A}, P=6.348 kWP = 6.348\ \text{kW}, pf=0.894\text{pf} = 0.894; delta IL=30.86 AI_L = 30.86\ \text{A}, P=19.04 kWP = 19.04\ \text{kW}; phase b load doubled: IN=5.14 AI_N = 5.14\ \text{A} with the neutral, ∣VN′N∣=46.0 V\lvert \mathbf{V}_{N'N} \rvert = 46.0\ \text{V} without it.

Simulation. The three-phase lab solves exactly these cases. At its defaults (230 V230\ \text{V} phase voltage, R=20 ΩR = 20\ \Omega, X=10 ΩX = 10\ \Omega, star, 4-wire) it reads a line voltage of 398.4 V398.4\ \text{V}, Ia=10.29 A∠−26.6∘\mathbf{I}_a = 10.29\ \text{A}\angle -26.6^\circ, a neutral current of zero, P=6.348 kWP = 6.348\ \text{kW}, Q=3.174 kvarQ = 3.174\ \text{kvar} and a power factor of 0.89440.8944. Then:

  1. Switch to delta: the line currents read 30.86 A30.86\ \text{A}, the phase current Iab=17.82 A∠3.4∘\mathbf{I}_{ab} = 17.82\ \text{A}\angle 3.4^\circ, P=19.04 kWP = 19.04\ \text{kW}.
  2. Back to star, set kb=2k_b = 2: Ib\mathbf{I}_b falls to 5.143 A5.143\ \text{A} and the neutral current reads 5.143 A∠33.4∘5.143\ \text{A}\angle 33.4^\circ.
  3. Switch the star neutral to 3-wire: the neutral shift reads 46.00 V∠60∘46.00\ \text{V}\angle 60^\circ and Ia=9.427 A∠−37.5∘\mathbf{I}_a = 9.427\ \text{A}\angle -37.5^\circ.
VaVbVcIaIbIcV solid, I thin (own scale)star, 4-wire-pk0+pk0T2Tphase voltages, peak 325 V-pk0+pk0T2Tline currents, peak 14.5 AP = 6.35 kW Q = 3.17 kvar S = 7.10 kVApf = 0.894 balanced IN = 0 A

What you would measure (professionally, not in this course). A qualified technician with a CAT III or CAT IV rated three-phase power analyser would read line voltages near 400 V400\ \text{V} (the supply may legitimately deviate by up to about ±10 %\pm 10\,\% from nominal, depending on the national rules), equal line currents within a few percent on a balanced load, and a small neutral current from residual unbalance and harmonics. You will not do this; the simulation and the calculation are the lab.

Pitfalls

  • Mixing line and phase quantities. Write VLV_L or VphV_\text{ph} every time; the factor 3\sqrt{3} applies between them, not to currents in a star load.
  • Using 3VLIL\sqrt{3} V_L I_L for unbalanced loads. That formula is for balanced systems; otherwise add the three SS values.
  • Per-phase analysis on an unbalanced 3-wire load. The star point shifts; use nodal analysis (Millman's theorem).
  • Forgetting the 30∘30^\circ shift between line and phase voltages (and between line and phase currents in delta).
  • Thinking the neutral is "safe". It is a current-carrying conductor and can be at a dangerous voltage, especially when broken.

Practice

  1. A balanced star load draws 16 A16\ \text{A} per line from a 400 V400\ \text{V} (line) supply at pf=0.85\text{pf} = 0.85 lagging. Find PP, QQ and ∣S∣\lvert S \rvert.
  2. Three 46 Ω46\ \Omega resistors are connected in delta to a 400 V400\ \text{V} line supply. Find the phase current, the line current and the total power.
  3. A balanced star load has Ia=8 A∠−30∘\mathbf{I}_a = 8\ \text{A}\angle -30^\circ (sequence a, b, c). Write Ib\mathbf{I}_b and Ic\mathbf{I}_c.
Answer
  1. ∣S∣=3⋅400⋅16=11.09 kVA\lvert S \rvert = \sqrt{3} \cdot 400 \cdot 16 = 11.09\ \text{kVA}; P=0.85⋅11.09=9.42 kWP = 0.85 \cdot 11.09 = 9.42\ \text{kW}; Q=1−0.852⋅11.09=5.84 kvarQ = \sqrt{1 - 0.85^2} \cdot 11.09 = 5.84\ \text{kvar}.
  2. Iph=400/46=8.70 AI_\text{ph} = 400/46 = 8.70\ \text{A}, IL=3⋅8.70=15.06 AI_L = \sqrt{3} \cdot 8.70 = 15.06\ \text{A}, P=3⋅8.702⋅46=10.43 kWP = 3 \cdot 8.70^2 \cdot 46 = 10.43\ \text{kW}.
  3. Ib=8 A∠−150∘\mathbf{I}_b = 8\ \text{A}\angle -150^\circ, Ic=8 A∠90∘\mathbf{I}_c = 8\ \text{A}\angle 90^\circ.

Test yourself

In a balanced star system with 230 V230\ \text{V} phase voltage, what is the line voltage?

  1. 230 V230\ \text{V}
  2. 325 V325\ \text{V}
  3. about 398 V398\ \text{V}
  4. 690 V690\ \text{V}

What current flows in the neutral of a balanced star load?

  1. the line current
  2. 3\sqrt{3} times the line current
  3. zero
  4. three times the line current

Three identical impedances take 5 kW in star. How much do they take in delta on the same supply?

  1. 1.67 kW
  2. 5 kW
  3. 8.66 kW
  4. 15 kW

Why can a broken neutral damage single-phase appliances in a building?

  1. the frequency changes
  2. the load star point floats, so lightly loaded phases can get well above 230 V
  3. the current doubles in every phase
  4. it reverses the phase sequence