TExcelTAD
Home › Power Electronics & Motor Drives › Thyristors, Triacs and Phase-Controlled Rectifiers

Thyristors, Triacs and Phase-Controlled Rectifiers

A diode bridge gives one fixed DC voltage. Replace the diodes by switches that can be told when to start conducting, and the average output becomes adjustable from full positive through zero to negative, with the energy flowing either way. The thyristor (silicon-controlled rectifier, SCR) is exactly such a switch: a diode that waits for a gate pulse before it conducts, and then latches on until its current falls to zero. It is the oldest power-semiconductor switch still in heavy use, because nothing else blocks thousands of volts and carries thousands of amperes as cheaply and as ruggedly: HVDC converter valves, large DC motor drives, soft starters, welding sets, and, in its bidirectional form, the triac, every incandescent-lamp dimmer and many fan regulators. This lesson covers the devices as concepts and the phase-controlled rectifier by calculation.

Safety: calculation and simulation only. Thyristor rectifiers and triac controllers work directly on the mains. The only hands-on part of this lesson is a 12 V DC experiment on SCR latching.

How a thyristor behaves

AKG fires on a gate pulse,turns off only whenits current falls to zero alpha = 60 degdashed line: Vd = 0.9 V cos(alpha) supply (blue), bridge output (orange)

A thyristor is a four-layer PNPN structure, which can be modelled as a PNP and an NPN transistor feeding each other's bases. A gate current into the NPN's base starts the loop; once the product of the two current gains exceeds one, the device turns itself fully on and stays on without gate current. Its key properties:

  • Forward blocking until a gate pulse arrives (or, unwanted, until the anode voltage rises too fast: the critical dv/dtdv/dt rating).
  • Latching current ILI_L: the anode current must exceed it before the gate pulse ends, or the device drops out.
  • Holding current IHI_H (below ILI_L, often by a factor of two or so): once the anode current falls below it, the device turns off. The gate cannot turn a normal SCR off.
  • Turn-off time tqt_q: after the current reaches zero the device needs tens to hundreds of microseconds of reverse voltage before it can block forward voltage again. In a rectifier the AC supply reverses the voltage for it: line commutation.
  • Critical di/dtdi/dt at turn-on: the conducting area spreads from the gate outwards, and a fast current rise burns a hot spot.

A triac is two thyristors in antiparallel on one die with one gate, triggered by gate current of either polarity. A GTO (gate turn-off thyristor) and its successor the IGCT can also be turned off by a large negative gate current; they survive in very high-power medium-voltage drives.

The phase-controlled bridge

Replace the four diodes of a single-phase bridge by thyristors and fire each pair at an angle α\alpha after the point where its diode would have started conducting. With a highly inductive load (a DC motor armature or a large choke) the current never stops, so each pair conducts for 180∘180^\circ from α\alpha, including a stretch where the supply is already negative:

Vd=22πVcos⁡α=0.900 Vcos⁡α(single-phase),Vd=1.350 VLLcos⁡α(three-phase)V_d = \frac{2\sqrt{2}}{\pi} V \cos\alpha = 0.900\,V\cos\alpha \quad \text{(single-phase)}, \qquad V_d = 1.350\,V_{LL}\cos\alpha \quad \text{(three-phase)}

For 0<α<90∘0 < \alpha < 90^\circ the bridge rectifies. For 90∘<α<180∘90^\circ < \alpha < 180^\circ (in practice up to about 150∘150^\circ, leaving margin for tqt_q and commutation overlap) VdV_d is negative while the current keeps its direction: power flows from the DC side to the AC supply. The bridge is then an inverter (line-commutated), which is how a DC motor regenerates into the grid while braking and how a classic HVDC link delivers power.

With a resistive load the current falls to zero with the voltage, so the output is ∣vs∣\lvert v_s \rvert from α\alpha to π\pi only:

Vd=2πV(1+cos⁡α)=0.450 V(1+cos⁡α)V_d = \frac{\sqrt{2}}{\pi} V (1 + \cos\alpha) = 0.450\,V (1 + \cos\alpha)

The price of phase control is power factor. The line current is a square block delayed by α\alpha, so the displacement factor is cos⁡α\cos\alpha, and for a three-phase bridge with smooth DC current the total power factor is about 3πcos⁡α=0.955cos⁡α\frac{3}{\pi}\cos\alpha = 0.955\cos\alpha. A DC drive running a motor at low speed draws large reactive power from the grid (Line Harmonics, Power Factor and Commutation Overlap).

Worked example: a three-phase thyristor DC drive (calculation only)

Given: a fully controlled three-phase bridge on 400 V400\ \text{V} line-to-line feeds a DC motor armature that needs 400 V400\ \text{V} at full speed; the armature current is smooth.

Find: the firing angle, the power factor at that point, and VdV_d when the drive brakes at α=150∘\alpha = 150^\circ.

Solve:

Vd0=1.350⋅400 V=540.2 V,α=arccos⁡400540.2=42.2∘cos⁡α=0.740,PF≈0.955⋅0.740=0.707Vd(150∘)=540.2 V⋅cos⁡150∘=−467.8 V\begin{aligned} V_{d0} &= 1.350 \cdot 400\ \text{V} = 540.2\ \text{V}, \qquad \alpha = \arccos\frac{400}{540.2} = 42.2^\circ \\ \cos\alpha &= 0.740, \qquad \text{PF} \approx 0.955 \cdot 0.740 = 0.707 \\ V_d(150^\circ) &= 540.2\ \text{V} \cdot \cos 150^\circ = -467.8\ \text{V} \end{aligned}

Check: at full speed the drive already has a power factor of only about 0.7; at half speed (α≈68∘\alpha \approx 68^\circ) it would be near 0.35. With α=150∘\alpha = 150^\circ the bridge holds −467.8 V-467.8\ \text{V} against the motor's back-EMF; for regenerative current to flow the motor's EMF must have the opposite polarity and a slightly larger magnitude, so the armature (or field) connection must be reversed first, which is why four-quadrant DC drives use two antiparallel bridges.

python · try it yourself
import numpy as np

# phase-controlled rectifier averages (calculation only), numerical check of the formulas
f, V, VLL = 50.0, 230.0, 400.0
k1, k3 = 2 * np.sqrt(2) / np.pi, 3 * np.sqrt(2) / np.pi    # 0.900 and 1.350
th = np.linspace(0, 2 * np.pi, 360000, endpoint=False)       # electrical angle over one cycle
vs = np.sqrt(2) * V * np.sin(th)

def full_bridge_inductive(alpha):
    # continuous load current: the output follows +vs from alpha to alpha+pi, then -vs
    phase = (th - alpha) % (2 * np.pi)
    return np.where(phase < np.pi, vs, -vs)

def full_bridge_resistive(alpha):
    # current stops at each zero crossing: output is |vs| only after the firing angle
    phase = th % np.pi
    return np.where(phase >= alpha, np.abs(vs), 0.0)

print(" alpha   inductive: num / 0.9 V cos a    resistive: num / 0.45 V (1 + cos a)")
for a_deg in (0, 30, 60, 90, 120):
    a = np.radians(a_deg)
    vi, vr = full_bridge_inductive(a).mean(), full_bridge_resistive(a).mean()
    print(f"{a_deg:5d}   {vi:8.1f} / {k1*V*np.cos(a):8.1f} V        {vr:8.1f} / {k1/2*V*(1+np.cos(a)):8.1f} V")

# three-phase fully controlled bridge feeding a DC motor armature
Vd_needed = 400.0
a = np.degrees(np.arccos(Vd_needed / (k3 * VLL)))
print(f"3-phase: Vd0 = {k3*VLL:.1f} V; for {Vd_needed:.0f} V fire at alpha = {a:.1f} deg")
print(f"  displacement factor cos(alpha) = {np.cos(np.radians(a)):.3f}, power factor about {3/np.pi*np.cos(np.radians(a)):.3f}")
print(f"  inverting (regenerating) at alpha = 150 deg: Vd = {k3*VLL*np.cos(np.radians(150)):.1f} V")

# triac dimmer on a resistive load: rms output vs firing angle
for a_deg in (45, 90, 135):
    a = np.radians(a_deg)
    v = np.where((th % np.pi) >= a, vs, 0.0)
    vrms = np.sqrt((v**2).mean())
    formula = V * np.sqrt(1 - a / np.pi + np.sin(2 * a) / (2 * np.pi))
    print(f"triac alpha {a_deg:3d} deg: Vrms = {vrms:6.1f} V (formula {formula:6.1f} V), power {100*(vrms/V)**2:5.1f} %")
 alpha   inductive: num / 0.9 V cos a    resistive: num / 0.45 V (1 + cos a)
    0      207.1 /    207.1 V           207.1 /    207.1 V
   30      179.3 /    179.3 V           193.2 /    193.2 V
   60      103.5 /    103.5 V           155.3 /    155.3 V
   90        0.0 /      0.0 V           103.5 /    103.5 V
  120     -103.5 /   -103.5 V            51.8 /     51.8 V
3-phase: Vd0 = 540.2 V; for 400 V fire at alpha = 42.2 deg
  displacement factor cos(alpha) = 0.740, power factor about 0.707
  inverting (regenerating) at alpha = 150 deg: Vd = -467.8 V
triac alpha  45 deg: Vrms =  219.3 V (formula  219.3 V), power  90.9 %
triac alpha  90 deg: Vrms =  162.6 V (formula  162.6 V), power  50.0 %
triac alpha 135 deg: Vrms =   69.3 V (formula   69.3 V), power   9.1 %

The numerical averages of the constructed waveforms reproduce both formulas at every angle. The triac rows are the AC phase controller (a dimmer): it does not rectify, it chops each half-cycle, and at α=90∘\alpha = 90^\circ a resistive load gets exactly half its full power. Light dimmers, soft starters for induction motors and heater controls work this way, and they too distort the line current.

Guided lab: SCR latching and holding at 12 V DC

Hand calculation. Take a small SCR (a TO-92 or TO-220 part rated 0.8 to 4 A). From its datasheet note IGTI_{GT}, VGTV_{GT}, ILI_L and IHI_H. For a gate supplied from 5 V5\ \text{V} through RGR_G, choose RGR_G for about three times IGTI_{GT} plus the current taken by the 1 kΩ1\ \text{k}\Omega gate–cathode resistor used below (0.8 V/1 kΩ=0.8 mA0.8\ \text{V}/1\ \text{k}\Omega = 0.8\ \text{mA}): with IGT=200 μAI_{GT} = 200\ \mu\text{A} and VGT=0.8 VV_{GT} = 0.8\ \text{V}, RG=(5−0.8) V/(0.6+0.8) mA=3.0 kΩR_G = (5 - 0.8)\ \text{V}/(0.6 + 0.8)\ \text{mA} = 3.0\ \text{k}\Omega (use 2.7 kΩ2.7\ \text{k}\Omega). Without that allowance the shunt would take all the gate current and the SCR would never fire.

Simulation. None is needed beyond the formulas; the code's firing-angle function shows what the same latching behaviour produces on AC.

What you would measure. A bench supply at 12 V12\ \text{V} with a 0.3 A0.3\ \text{A} limit, a 100 Ω100\ \Omega, 5 W resistor (or a 12 V lamp) from the supply to the anode, cathode to ground, a push-button feeding the gate through RGR_G and a 1 kΩ1\ \text{k}\Omega resistor from gate to cathode. Press the button: the load turns on (about 0.11 A0.11\ \text{A}) and stays on after release. Now insert a 10 kΩ10\ \text{k}\Omega potentiometer plus a 1 kΩ1\ \text{k}\Omega resistor in series instead of the load and raise the resistance slowly with a meter in series: the SCR drops out when the current falls below IHI_H, typically 1 to 5 mA for small parts with a wide spread (±50 %\pm 50\ \% is normal) and a strong temperature dependence. Only removing the anode current, never the gate, turns it off.

Hazards and safe setup. 12 V12\ \text{V} DC, current-limited; the load resistor warms. Never try the same on a lamp dimmer or anything plugged into the wall: triac circuits are not isolated from the mains, even their knobs' shafts can be live.

Pitfalls

  • Expecting the gate to turn an SCR off. Only bringing the current below IHI_H does (or a GTO/IGCT).
  • False triggering by dv/dtdv/dt. A fast voltage step through the anode-gate capacitance fires the device; RC snubbers protect it (Snubbers and Layout).
  • Firing too close to 180∘180^\circ in inversion. Without margin for tqt_q and overlap, commutation fails and the bridge short-circuits the DC source through the supply (commutation failure).
  • Confusing the resistive and inductive formulas. Which one applies depends on whether the current is continuous.

Practice

  1. A single-phase fully controlled bridge on 230 V230\ \text{V} feeds a highly inductive load at α=45∘\alpha = 45^\circ. Find VdV_d.
  2. The same bridge feeds a resistor. Find VdV_d at α=45∘\alpha = 45^\circ.
  3. A three-phase bridge on 690 V690\ \text{V} must deliver 600 V600\ \text{V}. Find α\alpha and the approximate power factor.
Answer
  1. Vd=0.900⋅230⋅cos⁡45∘=146.4 VV_d = 0.900 \cdot 230 \cdot \cos 45^\circ = 146.4\ \text{V}.
  2. Vd=0.450⋅230⋅(1+0.707)=176.7 VV_d = 0.450 \cdot 230 \cdot (1 + 0.707) = 176.7\ \text{V}.
  3. Vd0=1.350⋅690=931.8 VV_{d0} = 1.350 \cdot 690 = 931.8\ \text{V}; α=arccos⁡(600/931.8)=49.9∘\alpha = \arccos(600/931.8) = 49.9^\circ; PF ≈0.955⋅0.644=0.61\approx 0.955 \cdot 0.644 = 0.61.

Test yourself

Once a thyristor is conducting, how is it turned off?

  1. by a negative gate pulse
  2. by removing the gate current
  3. by bringing its anode current below the holding current, then applying reverse voltage for at least tqt_q
  4. by raising the gate voltage

A fully controlled bridge with a highly inductive load is fired at α=120∘\alpha = 120^\circ. What happens?

  1. the output is zero
  2. the average DC voltage is negative and power flows from the DC side back to the AC supply
  3. the bridge stops conducting
  4. the output doubles

Why does a thyristor DC drive have a poor power factor at low speed?

  1. the motor is inductive
  2. the line current is delayed by the firing angle, so the displacement factor is cos⁡α\cos\alpha, which is small when VdV_d is small
  3. the thyristors have high losses
  4. the gate pulses distort the current

A triac dimmer on a resistive load fired at α=90∘\alpha = 90^\circ delivers what fraction of full power?

  1. 25 %
  2. 50 %
  3. 71 %
  4. 100 %