Home › Power Electronics & Motor Drives › Line Harmonics, Power Factor and Commutation Overlap

Line Harmonics, Power Factor and Commutation Overlap

The capacitor-input rectifier of Single- and Three-Phase Diode Rectifiers drew 2.96 A2.96\ \text{A} rms from 230 V230\ \text{V} to deliver 299 W299\ \text{W}: a power factor of 0.44, although its current pulses sat right on the voltage peaks. One such load hardly matters. A building full of them, or a feeder supplying thousands of LED drivers and computers, carries large currents at 150, 250 and 350 Hz that heat transformers and neutral conductors, distort the supply voltage for everyone else, and fail the limits that standards set on equipment and installations. This lesson separates power factor into its displacement and distortion parts, computes the harmonic spectra of single- and three-phase rectifiers, adds the effect of source inductance (commutation overlap), and checks a design against IEC 61000-3-2 and IEEE 519. Everything here is on mains voltage: calculation and simulation only.

Power factor with distorted current

For a sinusoidal voltage, only the fundamental component of the current carries average power. With I1I_1 the rms fundamental, φ1\varphi_1 its phase shift and II the total rms current:

PF=PVI=VI1cos⁡φ1VI=I1I⏟distortion factor⋅cos⁡φ1⏟displacement factor,THDI=I2−I12I1\text{PF} = \frac{P}{V I} = \frac{V I_1 \cos\varphi_1}{V I} = \underbrace{\frac{I_1}{I}}_{\text{distortion factor}} \cdot \underbrace{\cos\varphi_1}_{\text{displacement factor}}, \qquad \text{THD}_I = \frac{\sqrt{I^2 - I_1^2}}{I_1}

so the distortion factor is 1/1+THDI21/\sqrt{1 + \text{THD}_I^2}. A capacitor bank can correct displacement (as in Power Factor and Its Correction) but does nothing for distortion; that needs filters or active wave-shaping (Power-Factor Correction). The phasor lab shows the displacement part alone: a series RL load at 50 Hz50\ \text{Hz} with sinusoidal current.

ReImVRVLVIphi = 57.5 deg, I lags(I drawn on its own scale)-pk0+pk0T/2T3T/22Tv(t), peak 14.1 Vi(t), peak 759 mAimpedance trianglepower triangleRX|Z|PQSR = 10.0 OhmP = 2.88 WX = 15.7 OhmQ = 4.53 var|Z| = 18.6 OhmS = 5.37 VApf = cos phi = 0.537 lagging

With R=10 ΩR = 10\ \Omega and L=50 mHL = 50\ \text{mH} the lab reads φ=57.5∘\varphi = 57.5^\circ and a power factor of 0.5370.537 lagging. A rectifier with the same power factor would have almost no phase shift at all: its poor factor comes from the spectrum.

The single-phase capacitor-input rectifier

Short current pulses contain every odd harmonic with slowly falling amplitudes. ngspice's fourier command computes them from the last simulated cycle of the rectifier from the previous lesson:

bash · try it yourself
cat > harm.cir <<'EOF'
* Line-current harmonics of a capacitor-input bridge, 230 V 50 Hz (simulation only)
.model DR D(Is=10n N=1.8 Rs=10m Cjo=50p BV=1000)
VS a 0 SIN(0 325.3 50)
RS a a1 0.5
LS a1 b 200u
D1 b p DR
D2 0 p DR
D3 n b DR
D4 n 0 DR
C1 p n 220u
RL p n 320
RN n 0 1meg
.options nfreqs=12
.control
set fourgridsize=2048
tran 10u 200m 0 10u uic
fourier 50 i(VS)
.endc
.end
EOF
ngspice -b harm.cir 2>&1 | awk '/THD/ {print} $1 ~ /^[0-9]+$/ && $1 % 2 == 1 {printf "h%-3s %4s Hz  peak %.4f A  %.3f of h1\n", $1, $2, $3, $5}'
  No. Harmonics: 12, THD: 180.256 %, Gridsize: 2048, Interpolation Degree: 1
h1     50 Hz  peak 1.9030 A  1.000 of h1
h3    150 Hz  peak 1.8364 A  0.965 of h1
h5    250 Hz  peak 1.7113 A  0.899 of h1
h7    350 Hz  peak 1.5410 A  0.810 of h1
h9    450 Hz  peak 1.3428 A  0.706 of h1
h11   550 Hz  peak 1.1345 A  0.596 of h1
01 11.00 30.965 50.899 70.810 90.706 110.596 harmonic order h (bars: In/I1; dashed: Class D limit at 299 W)

The third harmonic is almost as large as the fundamental. The THD printed by ngspice covers only the first eleven harmonics; from the total rms current, THDI=2.9602−1.3462/1.346=1.96\text{THD}_I = \sqrt{2.960^2 - 1.346^2}/1.346 = 1.96. The distortion factor is 1.346/2.960=0.4551.346/2.960 = 0.455, and since the measured power factor was 0.4390.439, the displacement factor is 0.9660.966 (the fundamental leads the voltage by about 15∘15^\circ: the capacitor recharges mostly before each voltage peak, and the small source inductance does not delay the pulse enough to reverse that). In a three-phase four-wire system the triplen harmonics (3, 9, 15, …) of single-phase loads add in the neutral instead of cancelling, so neutral currents can exceed phase currents.

The six-pulse bridge and commutation overlap

A three-phase bridge with a large DC choke draws a rectangular current block of 120∘120^\circ per half cycle from each phase. Its Fourier series has only harmonics h=6k±1h = 6k \pm 1 (5, 7, 11, 13, …) with Ih=I1/hI_h = I_1/h, and I1=6πIdI_1 = \frac{\sqrt{6}}{\pi} I_d. Source inductance LsL_s prevents the current from switching instantly between phases: for an overlap angle μ\mu two diodes of the same rail conduct together, short-circuiting two phases through 2Ls2L_s, and

cos⁡α−cos⁡(α+μ)=2ωLsId2 VLL,ΔVd=3ωLsπId\cos\alpha - \cos(\alpha + \mu) = \frac{2\omega L_s I_d}{\sqrt{2}\,V_{LL}}, \qquad \Delta V_d = \frac{3\omega L_s}{\pi} I_d

The overlap rounds the current edges, which reduces the higher harmonics, and it costs a voltage drop ΔVd\Delta V_d that behaves like a resistance 3ωLs/π3\omega L_s/\pi without any loss. In a thyristor bridge the overlap also eats into the margin before 180∘180^\circ in inversion.

Worked example: a 400 V, 100 A six-pulse bridge (calculation only)

Given: a diode bridge (α=0\alpha = 0) on 400 V400\ \text{V}, 50 Hz50\ \text{Hz}, Id=100 AI_d = 100\ \text{A} smooth, Ls=0.2 mHL_s = 0.2\ \text{mH} per phase.

Find: μ\mu, ΔVd\Delta V_d, the line-current THD without and with overlap.

Solve:

1−cos⁡μ=2⋅314.16 rad/s⋅0.2 mH⋅100 A565.7 V=0.0222 ⇒ μ=12.1∘ΔVd=3⋅314.16⋅0.2×10−3 Ωπ⋅100 A=6.00 VI1=6π⋅100 A=78.0 A,I=23⋅100 A=81.6 A,THDI=(81.678.0)2−1=31 %\begin{aligned} 1 - \cos\mu &= \frac{2 \cdot 314.16\ \text{rad/s} \cdot 0.2\ \text{mH} \cdot 100\ \text{A}}{565.7\ \text{V}} = 0.0222 \ \Rightarrow\ \mu = 12.1^\circ \\ \Delta V_d &= \frac{3 \cdot 314.16 \cdot 0.2 \times 10^{-3}\ \Omega}{\pi} \cdot 100\ \text{A} = 6.00\ \text{V} \\ I_1 &= \frac{\sqrt{6}}{\pi} \cdot 100\ \text{A} = 78.0\ \text{A}, \qquad I = \sqrt{\tfrac{2}{3}} \cdot 100\ \text{A} = 81.6\ \text{A}, \qquad \text{THD}_I = \sqrt{\left(\tfrac{81.6}{78.0}\right)^2 - 1} = 31\ \% \end{aligned}

Check: the ideal spectrum is 1/h1/h: 20 %20\ \% at the fifth, 14.3 %14.3\ \% at the seventh. The code models the overlap as linear ramps and finds the THD falling to about 25 %25\ \%.

python · try it yourself
import numpy as np

# six-pulse diode bridge line current with commutation overlap (calculation only)
f, VLL, Id, Ls = 50.0, 400.0, 100.0, 0.2e-3
w = 2 * np.pi * f
mu = np.arccos(1 - 2 * w * Ls * Id / (np.sqrt(2) * VLL))     # alpha = 0 (diodes)
dVd = 3 * w * Ls * Id / np.pi
print(f"overlap angle mu = {np.degrees(mu):.1f} deg, DC voltage drop = {dVd:.2f} V")

N = 3600
th = np.arange(N) * 2 * np.pi / N
def phase_current(mu):
    # phase a conducts +Id from 30 to 150 deg and -Id from 210 to 330 deg; ramps last mu (linear approx.)
    i = np.zeros(N)
    for start, sign in ((np.pi / 6, 1), (7 * np.pi / 6, -1)):
        x = (th - start) % (2 * np.pi)
        up = np.clip(x / mu, 0, 1) if mu > 0 else (x >= 0).astype(float)
        down = np.clip((2 * np.pi / 3 + mu - x) / mu, 0, 1) if mu > 0 else (x < 2 * np.pi / 3).astype(float)
        i += sign * Id * np.minimum(up, down) * (x < 2 * np.pi / 3 + mu)
    return i

for m in (0.0, mu):
    i = phase_current(m)
    X = np.abs(np.fft.rfft(i)) / N * 2 / np.sqrt(2)          # rms of each harmonic
    I1, Irms = X[1], np.sqrt(np.mean(i**2))
    thd = np.sqrt(Irms**2 - I1**2) / I1
    hs = "  ".join(f"h{h}:{100*X[h]/I1:4.1f}%" for h in (5, 7, 11, 13))
    print(f"mu = {np.degrees(m):4.1f} deg: I1 = {I1:5.1f} A, Irms = {Irms:5.1f} A, THD = {100*thd:4.1f} %, {hs}")

# single-phase capacitor-input bridge, harmonic peaks from the ngspice run (A)
mag = {1: 1.9030, 3: 1.8364, 5: 1.7113, 7: 1.5410, 9: 1.3428, 11: 1.1345}
P = 299.08
print("IEC 61000-3-2 Class D check at 299 W (limit mA/W x P):")
for h, lim in ((3, 3.4), (5, 1.9), (7, 1.0), (9, 0.5), (11, 0.35)):
    Ih = mag[h] / np.sqrt(2)
    print(f"  h{h:2d}: {Ih:.3f} A rms vs limit {lim*P/1e3:.3f} A -> {'FAIL' if Ih > lim*P/1e3 else 'pass'}")
overlap angle mu = 12.1 deg, DC voltage drop = 6.00 V
mu =  0.0 deg: I1 =  78.0 A, Irms =  81.6 A, THD = 31.1 %, h5:20.0%  h7:14.3%  h11: 9.1%  h13: 7.7%
mu = 12.1 deg: I1 =  77.8 A, Irms =  80.3 A, THD = 25.2 %, h5:19.1%  h7:13.0%  h11: 7.2%  h13: 5.5%
IEC 61000-3-2 Class D check at 299 W (limit mA/W x P):
  h 3: 1.299 A rms vs limit 1.017 A -> FAIL
  h 5: 1.210 A rms vs limit 0.568 A -> FAIL
  h 7: 1.090 A rms vs limit 0.299 A -> FAIL
  h 9: 0.950 A rms vs limit 0.150 A -> FAIL
  h11: 0.802 A rms vs limit 0.105 A -> FAIL

Standards (as of late 2026)

  • IEC 61000-3-2 (edition 5.0, 2018, with Amendment 1:2020 and Amendment 2:2024, consolidated as edition 5.2, plus Interpretation Sheet 1:2025; as of 2026-11) limits the harmonic currents that equipment up to 16 A16\ \text{A} per phase may inject into the public low-voltage network. Class A (general equipment) has absolute limits in amperes; Class D (personal computers, monitors and television receivers from 7575 to 600 W600\ \text{W}) has limits proportional to power: 3.43.4, 1.91.9, 1.01.0, 0.50.5, 0.35 mA/W0.35\ \text{mA/W} for harmonics 3, 5, 7, 9, 11. Lighting is Class C. Equipment from 1616 to 75 A75\ \text{A} falls under IEC 61000-3-12.
  • IEEE 519-2022 sets limits at the point of common coupling of an installation rather than per device: voltage THD (8 % up to 1 kV, 5 % from 1 to 69 kV) and current TDD (total demand distortion, relative to the maximum demand current) that depend on the ratio ISC/ILI_{SC}/I_L of short-circuit current to load current; a stiff supply may accept more. The details belong to Power Quality.

The 300 W capacitor-input supply above fails Class D at every harmonic by a wide margin, which is why products in that class (and anything above 75 W75\ \text{W} in practice) have a PFC stage. Remedies for three-phase drives are AC or DC chokes (longer conduction, lower THD), 12- and 18-pulse rectifiers with phase-shifting transformers (a 12-pulse bridge cancels the 5th and 7th, an 18-pulse bridge the 5th to the 13th), passive tuned filters, and active front ends.

Guided lab: the spectrum of a low-voltage rectifier

Hand calculation. For the signal-generator bridge of the previous lesson (5 V peak, Schottky bridge, 100 μF100\ \mu\text{F}, 4.7 kΩ4.7\ \text{k}\Omega), predict qualitatively: narrow pulses, so harmonics 3, 5, 7 of similar size to the fundamental.

Simulation. Change the ngspice deck to SIN(0 5 50), RS 50 Ω50\ \Omega, LS removed, the load 4.7 kΩ4.7\ \text{k}\Omega and the capacitor 100 μF100\ \mu\text{F}; rerun fourier.

What you would measure. Insert a 10 Ω10\ \Omega shunt between the generator and the bridge, and view the shunt voltage with the scope in A minus B mode and its FFT (Hann window, 1 s record so the bins are 1 Hz). Expect odd harmonics at 50, 150, 250 Hz… within a few dB of the simulation; the generator's output impedance and the shunt broaden the pulses and lower the higher harmonics. Typical scope FFT amplitude accuracy is about ±1\pm 1 to 2 dB2\ \text{dB}.

Hazards and safe setup. Generator-level voltages only. Never measure mains current harmonics with a shunt and a scope; that is done with a power analyser and current clamps by qualified people.

Pitfalls

  • Correcting a distorted load with a capacitor bank. It cannot fix distortion, and it can resonate with the supply inductance at a harmonic frequency, amplifying it.
  • Using THD of current for IEEE 519 compliance. The standard uses TDD, referred to the maximum demand current.
  • Forgetting the neutral in buildings with many single-phase rectifier loads.
  • Ignoring overlap in thyristor-converter calculations: it lowers the output and shrinks the inversion margin.

Practice

  1. A load draws 5 A5\ \text{A} rms with a fundamental of 4 A4\ \text{A} in phase with the voltage. Find the THD and the power factor.
  2. Find the fifth and seventh harmonic currents of an ideal six-pulse bridge with Id=50 AI_d = 50\ \text{A}.
  3. In the worked example, what source inductance doubles ΔVd\Delta V_d? What happens to μ\mu?
Answer
  1. THD=25−16/4=0.75\text{THD} = \sqrt{25 - 16}/4 = 0.75; PF =4/5⋅1=0.80= 4/5 \cdot 1 = 0.80.
  2. I1=0.780⋅50=39.0 AI_1 = 0.780 \cdot 50 = 39.0\ \text{A}; I5=7.80 AI_5 = 7.80\ \text{A}, I7=5.57 AI_7 = 5.57\ \text{A}.
  3. Ls=0.4 mHL_s = 0.4\ \text{mH} gives 12.0 V12.0\ \text{V}; 1−cos⁡μ=0.04441 - \cos\mu = 0.0444, μ=17.1∘\mu = 17.1^\circ.

Test yourself

Power factor with a sinusoidal voltage and distorted current equals…

  1. cos⁡φ1\cos\varphi_1 only
  2. (I1/I)cos⁡φ1(I_1/I)\cos\varphi_1
  3. 1/THD1/\text{THD}
  4. P/(VI1)P/(V I_1)

Which harmonics does an ideal six-pulse bridge with a smooth DC current draw?

  1. all odd harmonics
  2. 3, 9, 15, …
  3. 6k±16k \pm 1: 5, 7, 11, 13, …
  4. even harmonics only

What does commutation overlap do in a diode bridge?

  1. increases the DC voltage
  2. lowers the DC voltage by 3ωLsId/π3\omega L_s I_d/\pi and slightly reduces the higher harmonics
  3. adds even harmonics
  4. dissipates power in the diodes

IEEE 519-2022 current limits are applied…

  1. to each appliance
  2. at the point of common coupling, as TDD depending on ISC/ILI_{SC}/I_L
  3. only to the neutral
  4. to the voltage only