Autotransformers and Instrument Transformers
Two special uses of the transformer appear everywhere in power systems. An autotransformer has one winding with a tap instead of two separate windings. When the two voltages are close, as in a grid interconnector or a to booster, it does the same job as a two-winding transformer at a fraction of the size, weight and loss. Instrument transformers go the other way: they are small, they carry almost no power, and their only job is to reproduce a dangerous voltage or a huge current as a safe or signal for meters and protection relays, with a known, tiny error.
Safety: autotransformers on the mains and instrument transformers in switchgear are studied here by calculation and simulation only. An autotransformer provides no isolation, and a current transformer must never have its secondary opened while the primary carries current.
The autotransformer
Connect T1's two windings in series, aiding, and use the winding as the common winding: the result is a autotransformer. Each winding still carries only its rated current, so the series winding carries on the HV side, and the apparent power is , eleven times the two-winding rating. In general
Only is transformed magnetically; the rest, , is conducted straight through the copper. The losses are those of the original windings, so the efficiency on the new rating is much higher, and the per-unit series impedance on the autotransformer's rating falls by the factor .
The catches: there is no galvanic isolation (the LV side is connected to the HV winding, so an open common winding puts full HV on the LV circuit), and the low impedance gives high fault currents. Autotransformers are therefore used where the ratio is small and both sides are earthed systems of similar level: grid interconnectors, motor starting (Starting Methods) and variable "Variac" laboratory supplies, which are mains-connected and not isolating.
Instrument transformers
A current transformer (CT) has a primary of one or a few turns in series with the line, and a secondary of many turns feeding a low-impedance burden (meter, relay and leads), with a rated secondary current of or . It is a transformer driven by a current source: the line current is fixed by the power system, not by the CT. Its secondary current is minus the magnetising current the core needs to develop the burden voltage. Two consequences:
- The error grows with the burden: more burden voltage needs more flux, so more magnetising current.
- An open secondary is dangerous. The whole primary MMF then goes into magnetising the core, which saturates; the rapidly changing flux at each zero crossing induces peaks that can reach kilovolts, a shock and insulation hazard, and the core overheats. Shorting links are fitted so a meter can be removed safely.
A voltage transformer (VT) is a precise, lightly loaded step-down transformer with a standard secondary such as or line-to-line. It must never be short-circuited on the secondary. Accuracy classes are defined in the IEC 61869 series (IEC 61869-2 for CTs, -3 for inductive VTs; as of 2026): measuring CTs have classes such as , , and (the ratio error limit in percent at rated current, with matching phase-displacement limits in minutes), and protection CTs classes such as 5P20, a composite error of at most 5 % at 20 times rated primary current (the accuracy limit factor). Meter-side current sensing, Rogowski coils and Hall sensors are in Current Measurement.
Worked example: a 200/5 A CT and its burden
Given: a CT (), secondary winding resistance , magnetising branch referred to the secondary in parallel with , rated burden ( at ), primary current .
Find: the secondary current and ratio error at rated burden and at five times rated burden ().
Solve: the CT is a current source feeding in parallel with :
At the same formula gives and .
Check: the error is negative (the CT reads low) because part of the current magnetises the core, and it grows roughly in proportion to the burden, as expected for a linear core. The program also gives the phase displacement: minutes of arc at rated burden, at five times. Overloading a CT's burden can push it out of its accuracy class even when the ratio error still looks small.
In Python: autotransformer rating and CT errors
import numpy as np
# 1) T1 (50 kVA, 2400/240 V, z = 0.0292 pu) reconnected as a 2640/2400 V autotransformer
S2w, VH2w, VL2w, z2w, losses = 50e3, 2400.0, 240.0, abs(0.00885 + 0.02778j), 563.0
VH, VL = VH2w + VL2w, VH2w # series winding = the 240 V winding
Sauto = S2w * VH / (VH - VL)
print(f"autotransformer {VH:.0f}/{VL:.0f} V: rating {Sauto/1e3:.0f} kVA "
f"({Sauto/S2w:.0f} x), conducted {Sauto*(1-(VH-VL)/VH)/1e3:.0f} kVA, transformed {S2w/1e3:.0f} kVA")
print(f"z on its own rating {z2w*(VH-VL)/VH*100:.3f} % (two-winding {z2w*100:.2f} %), "
f"full-load efficiency at pf 1 {Sauto/(Sauto+losses)*100:.2f} %")
# 2) a 200/5 A current transformer: secondary-referred model, ideal current source I1/n feeding Zm || (Rs + burden)
n, Rs = 40, 0.15
Zm = 1 / (1 / 1000 + 1 / 200j) # core-loss 1 kOhm parallel with magnetising 200 Ohm
I1 = 200.0
print("burden (Ohm) I2 (A) ratio error phase (min)")
for Rb in (0.2, 0.4, 1.0, 2.0, 5.0):
I2 = I1 / n * Zm / (Zm + Rs + Rb)
eps = (n * abs(I2) - I1) / I1 * 100
print(f"{Rb:8.1f} {abs(I2):6.3f} {eps:7.2f} % {np.degrees(np.angle(I2))*60:7.1f}")
print(f"open secondary: all {I1/n:.0f} A into Zm, |V| = {I1/n*abs(Zm):.0f} V rms if the core did not saturate")autotransformer 2640/2400 V: rating 550 kVA (11 x), conducted 500 kVA, transformed 50 kVA
z on its own rating 0.265 % (two-winding 2.92 %), full-load efficiency at pf 1 99.90 %
burden (Ohm) I2 (A) ratio error phase (min)
0.2 4.998 -0.04 % 6.0
0.4 4.997 -0.06 % 9.4
1.0 4.994 -0.12 % 19.7
2.0 4.989 -0.22 % 36.9
5.0 4.973 -0.54 % 88.0
open secondary: all 5 A into Zm, |V| = 981 V rms if the core did not saturate
The last line is the linear model's answer for an open secondary, nearly rms. A real core saturates long before, which limits the rms value but produces sharp peaks that are still dangerous.
Interactive: a CT and its burden
The CT model in the netlist lab (simulation only): a current source for , the magnetising branch RC, LM ( at ), the secondary resistance RS and the burden RB. At the rated the lab shows and in LM. Slide the burden to , a crude stand-in for a broken lead: the burden current falls to about and the secondary voltage rises to about , which a real CT would only reach in saturated spikes. The lab also sweeps frequency on its plot; only the readouts at the cursor matter here.
Guided lab: a current transformer at low current
Hand calculation. A small clip-on or toroidal CT sold for current sensing (for example a or ratio, with a stated burden resistor) at a low-voltage test current. Predict the burden voltage for to (primary ampere-turns: turns through the window times the wire current).
Simulation. Put the CT's ratio and burden into the program; if the datasheet gives the magnetising inductance or the excitation curve, use it for .
What you would measure. Wind turns of insulated wire through the CT window and drive to AC through them (a function generator with a small audio power amplifier into a power resistor, a few volts): that is to ampere-turns, with the burden resistor connected before the current is switched on. Read the burden voltage with a true-rms DMM and compare with ten times the wire current measured by a reference meter. Expect agreement within the CT's stated class plus the DMM's error, typically 1 to 3 % for inexpensive sensing CTs. Then halve and double the burden and watch the error change.
Hazards and safe setup. Low-voltage test circuit only; never clamp a CT around a mains conductor for this lab. Keep the burden connected whenever current flows in the primary: even a small CT can produce a painful voltage with an open secondary. The power resistor in the test circuit gets hot.
Pitfalls
- Treating an autotransformer as isolating. The LV side is connected to the HV winding.
- Rating the autotransformer by its windings. Its throughput rating is times larger.
- Opening a live CT secondary. Short it first.
- Ignoring the burden of the leads. At , of copper loop (about ) adds , which is why secondaries are preferred for long runs.
Practice
- A , two-winding transformer is connected as a autotransformer. What is its rating?
- What fraction of its power is conducted and what fraction transformed?
- For the CT in the worked example, what is the ratio error with a secondary version () and the same magnetising branch referred to the secondary scaled by (for the same core with five times the turns), at its rated burden of ?
Answer
- .
- Transformed (10 kVA); conducted (100 kVA).
- Burden at is ; scales by to , by about to . Every impedance is times larger, versus : the same circuit scaled, so the same error, . A CT's accuracy depends on its burden in VA, not on its secondary current rating.
Test yourself
A two-winding transformer rated 50 kVA, 2400/240 V, is reconnected as a 2640/2400 V autotransformer. Its rating becomes…
- 50 kVA
- 100 kVA
- 550 kVA
- 5.5 MVA
Why must a current transformer's secondary never be opened while the primary carries current?
- the primary current would stop
- all the primary MMF magnetises the core, producing dangerous voltage peaks and overheating
- the ratio would reverse
- the burden would short the line
A CT's ratio error becomes larger (more negative) when…
- the burden impedance is increased
- the burden is reduced
- the primary has more turns
- the frequency rises
The main disadvantage of an autotransformer compared with a two-winding transformer is…
- higher losses
- lower efficiency
- no galvanic isolation between the two sides
- larger size