Three-Phase Transformers and Vector Groups

The nameplate of the transformer outside a block of flats reads something like 500 kVA500\ \text{kVA}, 11 000/415 V11\,000/415\ \text{V}, Dyn11. The first two parts are the single-phase ideas of the previous lessons, scaled by three. The last part is new: it says how the windings are connected (delta on the HV side, star with an accessible neutral on the LV side) and that the LV voltages are shifted by 30∘30^\circ from the HV voltages. Getting that code wrong is not a detail: two transformers with different vector groups connected in parallel short-circuit each other through their windings. This lesson explains the connections, the phase shifts and the clock notation, starting from the three-phase circuit ideas of Three-Phase Circuits.

Safety: three-phase distribution transformers work at mains and medium voltage; this lesson is calculation and simulation only.

Banks and cores

A three-phase transformer can be a bank of three single-phase units, or a single core-type unit with three limbs, one per phase, each carrying an HV and an LV winding. In the three-limb core the three fluxes sum to zero at the yokes (balanced sinusoidal fluxes add to zero), so no return limb is needed and the core is smaller and cheaper than three separate units. Large units use five-limb cores to reduce height for transport. Everything that follows works per limb: the LV winding on a limb sees the voltage of the HV winding on the same limb, divided by that pair's turns ratio.

Star and delta connections

Connection Winding voltage Winding current
star (Y, y) VL/3V_L/\sqrt{3} ILI_L
delta (D, d) VLV_L IL/3I_L/\sqrt{3}

The ratio of line voltages is not always the turns ratio: for a delta–star unit, VL,LV/VL,HV=3 N2/N1V_{L,\text{LV}}/V_{L,\text{HV}} = \sqrt{3}\,N_2/N_1. The power is the same either way, S=3VLILS = \sqrt{3} V_L I_L.

The interactive lab shows the delta relations on a resistive load: at 230 V230\ \text{V} phase voltage (line voltage 398.4 V398.4\ \text{V}) and 20 Ω20\ \Omega per branch, the branch current is Iab=19.92 AI_{ab} = 19.92\ \text{A} at 30∘30^\circ while the line current is Ia=34.50 AI_a = 34.50\ \text{A} at 0∘0^\circ: 3\sqrt{3} larger and shifted by 30∘30^\circ. That same 30∘30^\circ shift is what a delta winding introduces between the two sides of a transformer.

VaVbVcIaIbIcV solid, I thin (own scale)delta-pk0+pk0T2Tphase voltages, peak 325 V-pk0+pk0T2Tline currents, peak 48.8 AP = 23.8 kW Q = 0 var S = 23.8 kVApf = 1.000 balanced IN = 0 A

The clock notation

A (12)BC HV delta: A at 12 o'clock a (11)bc n 30 deg LV star: a leads A by 30 deg

The vector group is written as the HV connection in capitals (Y, D, Z for zigzag), the LV connection in lower case, n (or N) when a neutral is brought out, and a clock number: draw the HV phase-A voltage as the minute hand at 12 o'clock; the LV phase-a voltage is the hour hand, and the number is the hour it points to. Each hour is 30∘30^\circ of LV lagging HV:

  • Yy0, Dd0: no shift. Yy6, Dd6: 180∘180^\circ (one side's windings reversed).
  • Dy1, Yd1: LV lags HV by 30∘30^\circ.
  • Dyn11, Yd11: LV lags by 330∘330^\circ, i.e. leads by 30∘30^\circ.

Which of 1 or 11 you get depends only on which pair of HV terminals the delta winding on each limb is connected across. The common distribution choice is Dyn11 (Dyn5 in some countries): the HV delta gives a path for triplen harmonic magnetising currents (B–H Curves and Saturation) and keeps the zero-sequence part of unbalanced LV loads circulating in the delta instead of flowing in the HV lines, and the LV star with neutral provides 230 V230\ \text{V} phase voltages for single-phase loads on a four-wire system. (IEC 60038 gives 230/400 V230/400\ \text{V} as the nominal low voltage; transformers often have a slightly higher rated no-load LV voltage such as 415415 or 420 V420\ \text{V} to allow for the drop at load.)

Worked example: a Dyn11 distribution transformer

Given: 500 kVA500\ \text{kVA}, 11 000/415 V11\,000/415\ \text{V}, Dyn11.

Find: the winding voltages and currents on each side and the turns ratio per limb.

Solve:

IL,HV=500 000 VA3⋅11 000 V=26.24 A,Iwinding,HV=26.24 A3=15.15 A at 11 000 VIL,LV=500 000 VA3⋅415 V=695.6 A (also the winding current) at 415 V3=239.6 VN1N2=11 000 V239.6 V=45.91\begin{aligned} I_{L,\text{HV}} &= \frac{500\,000\ \text{VA}}{\sqrt{3} \cdot 11\,000\ \text{V}} = 26.24\ \text{A}, \qquad I_\text{winding,HV} = \frac{26.24\ \text{A}}{\sqrt{3}} = 15.15\ \text{A}\ \text{at}\ 11\,000\ \text{V} \\ I_{L,\text{LV}} &= \frac{500\,000\ \text{VA}}{\sqrt{3} \cdot 415\ \text{V}} = 695.6\ \text{A}\ \text{(also the winding current)}\ \text{at}\ \frac{415\ \text{V}}{\sqrt{3}} = 239.6\ \text{V} \\ \frac{N_1}{N_2} &= \frac{11\,000\ \text{V}}{239.6\ \text{V}} = 45.91 \end{aligned}

Check: each limb carries one third of the power: 11 000⋅15.15=166.7 kVA11\,000 \cdot 15.15 = 166.7\ \text{kVA} and 239.6⋅695.6=166.7 kVA239.6 \cdot 695.6 = 166.7\ \text{kVA}. The line-voltage ratio 11 000/415=26.511\,000/415 = 26.5 is the turns ratio divided by 3\sqrt{3}, because one side is delta and the other star.

In Python: finding the clock number

The program builds the LV line voltage Vab\mathbf{V}_{ab} from the winding on each limb and measures how many 30∘30^\circ steps it lags the HV line voltage VAB\mathbf{V}_{AB}.

python · try it yourself
import numpy as np
a = np.exp(2j * np.pi / 3)
VA, VB, VC = 1, a**-1, a                                  # HV phase-to-neutral voltages (abc sequence)
HV_line = {"AB": VA - VB, "BC": VB - VC, "CA": VC - VA}

def clock(lv_ab):
    """Clock number: how many 30-degree steps the LV line voltage ab lags the HV line voltage AB."""
    lag = np.degrees(np.angle(HV_line["AB"] / lv_ab))
    return int(round(lag / 30)) % 12

# Each LV winding on limb k sees the voltage of the HV winding on that limb (ideal, unit ratio per winding).
cases = {
    "Yy0  (HV star, LV star)":                    [VA, VB, VC],
    "Yy6  (LV star reversed)":                    [-VA, -VB, -VC],
    "Dy1  (HV delta A-C, B-A, C-B; LV star)":      [VA - VC, VB - VA, VC - VB],
    "Dy11 (HV delta A-B, B-C, C-A; LV star)":      [VA - VB, VB - VC, VC - VA],
}
for name, (va, vb, vc) in cases.items():
    print(f"{name:42s} clock {clock(va - vb):2d}")
# LV delta: each LV winding is one LV line voltage. Limb A's winding across a-b gives Vab = VA;
# across c-a (from a to c) gives Vac = VA, and limb B's winding then gives Vba = VB, so Vab = -VB.
print(f"{'Yd1  (HV star; LV delta, limb A winding a-b)':42s} clock {clock(VA):2d}")
print(f"{'Yd11 (HV star; LV delta, limb A winding a-c)':42s} clock {clock(-VB):2d}")

# a 500 kVA, 11 kV / 415 V Dyn11 transformer: windings and currents
S, VH, VL = 500e3, 11e3, 415.0
IH, IL = S / (np.sqrt(3) * VH), S / (np.sqrt(3) * VL)
print(f"HV line {IH:.2f} A, HV delta winding {IH/np.sqrt(3):.2f} A at {VH:.0f} V; "
      f"LV line = winding {IL:.1f} A at {VL/np.sqrt(3):.1f} V; turns ratio per limb {VH/(VL/np.sqrt(3)):.2f}")
Yy0  (HV star, LV star)                    clock  0
Yy6  (LV star reversed)                    clock  6
Dy1  (HV delta A-C, B-A, C-B; LV star)     clock  1
Dy11 (HV delta A-B, B-C, C-A; LV star)     clock 11
Yd1  (HV star; LV delta, limb A winding a-b) clock  1
Yd11 (HV star; LV delta, limb A winding a-c) clock 11
HV line 26.24 A, HV delta winding 15.15 A at 11000 V; LV line = winding 695.6 A at 239.6 V; turns ratio per limb 45.91

Why the connection matters

  • Parallel operation needs the same clock number: two units at 1 and 11 o'clock differ by 60∘60^\circ, so their open-circuit LV voltages differ by 2sin⁡30∘=12\sin 30^\circ = 1 per unit, and the circulating current would be about 1/(z1+z2)1/(z_1 + z_2), ten or more times rated (Parallel Operation and Inrush).
  • Triplen harmonics: a star–star unit without a delta winding has no path for the third-harmonic magnetising current; large Yy units get a delta tertiary winding.
  • Earth faults and zero sequence: a delta blocks zero-sequence current between the systems on its two sides, which shapes how earth faults are seen by protection; this belongs to Power Systems.
  • Zigzag windings (Z, z) split each LV phase over two limbs. They give a neutral that tolerates unbalanced and harmonic loads and are used for earthing transformers.

Guided lab: phase shifts on paper and in the simulator

Hand calculation. Draw the HV line-voltage triangle, then for Dy1, Dy11 and Yd1 construct the LV phasors by copying each limb's HV winding voltage onto the LV side, as in the program. Read off the clock hour.

Simulation. Run the program; then, in the three-phase lab, compare a star and a delta load of the same per-branch impedance and confirm the 3\sqrt{3} factor and the 30∘30^\circ shift between branch and line currents.

What you would measure. On a real installation, vector groups are checked by qualified staff with a dedicated transformer turns-ratio and phase-displacement tester applying a low test voltage to the de-energised, isolated transformer. The expected result is the nameplate's ratio within about ±0.5 %\pm 0.5\ \% (a typical tolerance on the declared ratio, IEC 60076-1:2011 as of 2026) and the nameplate's clock number exactly. This is not a learner experiment; the paper construction and the program are the exercise.

Hazards. Even a de-energised transformer can be back-fed from the LV side or hold charge in cables; such work needs isolation, earthing and permits.

Pitfalls

  • Assuming the line-voltage ratio is the turns ratio. For Dy and Yd units it differs by 3\sqrt{3}.
  • Clock direction. The number counts LV lagging in 30∘30^\circ steps; 11 means LV leads by 30∘30^\circ.
  • Paralleling different groups. Same ratio and same clock number are both required.
  • Forgetting the neutral. Dyn11 has an LV neutral brought out (n); Dy11 does not.

Practice

  1. A 1 MVA1\ \text{MVA}, 22/0.42 kV22/0.42\ \text{kV}, Dyn11 transformer: find the HV winding current and the LV winding voltage.
  2. What is the clock number if the LV star of a Dy11 unit is reversed at its star point?
  3. A star–delta unit's LV leads its HV by 30∘30^\circ. Write its vector group.
Answer
  1. IL,HV=106/(3⋅22 000)=26.24 AI_{L,\text{HV}} = 10^6/(\sqrt{3} \cdot 22\,000) = 26.24\ \text{A}, winding 15.15 A15.15\ \text{A}; LV winding 420/3=242.5 V420/\sqrt{3} = 242.5\ \text{V}.
  2. Reversing all three LV windings adds 180∘180^\circ (6 hours): 11+6=17→511 + 6 = 17 \to 5, so Dy5.
  3. LV leads by 30∘30^\circ = lags by 330∘330^\circ: Yd11.

Test yourself

In the vector group Dyn11, the '11' means…

  1. the LV voltage lags the HV by 11 degrees
  2. the LV voltage leads the HV by 30 degrees
  3. the LV voltage lags the HV by 30 degrees
  4. there are 11 turns per volt

A 500 kVA, 11 kV/415 V Dyn11 transformer has an HV delta winding current of about…

  1. 26.2 A
  2. 15.2 A
  3. 45.5 A
  4. 695.6 A

Why is a delta winding useful in a three-phase transformer?

  1. it removes the need for a neutral
  2. it provides a path for triplen harmonic currents
  3. it doubles the rating
  4. it eliminates leakage reactance

Two transformers of the same ratio, one Dy1 and one Dy11, are paralleled. What happens?

  1. they share load equally
  2. a large circulating current flows because their LV voltages differ by 60 degrees
  3. nothing, the phase shift cancels
  4. the neutral current doubles