Three-Phase Transformers and Vector Groups
The nameplate of the transformer outside a block of flats reads something like , , Dyn11. The first two parts are the single-phase ideas of the previous lessons, scaled by three. The last part is new: it says how the windings are connected (delta on the HV side, star with an accessible neutral on the LV side) and that the LV voltages are shifted by from the HV voltages. Getting that code wrong is not a detail: two transformers with different vector groups connected in parallel short-circuit each other through their windings. This lesson explains the connections, the phase shifts and the clock notation, starting from the three-phase circuit ideas of Three-Phase Circuits.
Safety: three-phase distribution transformers work at mains and medium voltage; this lesson is calculation and simulation only.
Banks and cores
A three-phase transformer can be a bank of three single-phase units, or a single core-type unit with three limbs, one per phase, each carrying an HV and an LV winding. In the three-limb core the three fluxes sum to zero at the yokes (balanced sinusoidal fluxes add to zero), so no return limb is needed and the core is smaller and cheaper than three separate units. Large units use five-limb cores to reduce height for transport. Everything that follows works per limb: the LV winding on a limb sees the voltage of the HV winding on the same limb, divided by that pair's turns ratio.
Star and delta connections
| Connection | Winding voltage | Winding current |
|---|---|---|
| star (Y, y) | ||
| delta (D, d) |
The ratio of line voltages is not always the turns ratio: for a delta–star unit, . The power is the same either way, .
The interactive lab shows the delta relations on a resistive load: at phase voltage (line voltage ) and per branch, the branch current is at while the line current is at : larger and shifted by . That same shift is what a delta winding introduces between the two sides of a transformer.
The clock notation
The vector group is written as the HV connection in capitals (Y, D, Z for zigzag), the LV connection in lower case, n (or N) when a neutral is brought out, and a clock number: draw the HV phase-A voltage as the minute hand at 12 o'clock; the LV phase-a voltage is the hour hand, and the number is the hour it points to. Each hour is of LV lagging HV:
Yy0,Dd0: no shift.Yy6,Dd6: (one side's windings reversed).Dy1,Yd1: LV lags HV by .Dyn11,Yd11: LV lags by , i.e. leads by .
Which of 1 or 11 you get depends only on which pair of HV terminals the delta winding on each limb is connected across. The common distribution choice is Dyn11 (Dyn5 in some countries): the HV delta gives a path for triplen harmonic magnetising currents (B–H Curves and Saturation) and keeps the zero-sequence part of unbalanced LV loads circulating in the delta instead of flowing in the HV lines, and the LV star with neutral provides phase voltages for single-phase loads on a four-wire system. (IEC 60038 gives as the nominal low voltage; transformers often have a slightly higher rated no-load LV voltage such as or to allow for the drop at load.)
Worked example: a Dyn11 distribution transformer
Given: , , Dyn11.
Find: the winding voltages and currents on each side and the turns ratio per limb.
Solve:
Check: each limb carries one third of the power: and . The line-voltage ratio is the turns ratio divided by , because one side is delta and the other star.
In Python: finding the clock number
The program builds the LV line voltage from the winding on each limb and measures how many steps it lags the HV line voltage .
import numpy as np
a = np.exp(2j * np.pi / 3)
VA, VB, VC = 1, a**-1, a # HV phase-to-neutral voltages (abc sequence)
HV_line = {"AB": VA - VB, "BC": VB - VC, "CA": VC - VA}
def clock(lv_ab):
"""Clock number: how many 30-degree steps the LV line voltage ab lags the HV line voltage AB."""
lag = np.degrees(np.angle(HV_line["AB"] / lv_ab))
return int(round(lag / 30)) % 12
# Each LV winding on limb k sees the voltage of the HV winding on that limb (ideal, unit ratio per winding).
cases = {
"Yy0 (HV star, LV star)": [VA, VB, VC],
"Yy6 (LV star reversed)": [-VA, -VB, -VC],
"Dy1 (HV delta A-C, B-A, C-B; LV star)": [VA - VC, VB - VA, VC - VB],
"Dy11 (HV delta A-B, B-C, C-A; LV star)": [VA - VB, VB - VC, VC - VA],
}
for name, (va, vb, vc) in cases.items():
print(f"{name:42s} clock {clock(va - vb):2d}")
# LV delta: each LV winding is one LV line voltage. Limb A's winding across a-b gives Vab = VA;
# across c-a (from a to c) gives Vac = VA, and limb B's winding then gives Vba = VB, so Vab = -VB.
print(f"{'Yd1 (HV star; LV delta, limb A winding a-b)':42s} clock {clock(VA):2d}")
print(f"{'Yd11 (HV star; LV delta, limb A winding a-c)':42s} clock {clock(-VB):2d}")
# a 500 kVA, 11 kV / 415 V Dyn11 transformer: windings and currents
S, VH, VL = 500e3, 11e3, 415.0
IH, IL = S / (np.sqrt(3) * VH), S / (np.sqrt(3) * VL)
print(f"HV line {IH:.2f} A, HV delta winding {IH/np.sqrt(3):.2f} A at {VH:.0f} V; "
f"LV line = winding {IL:.1f} A at {VL/np.sqrt(3):.1f} V; turns ratio per limb {VH/(VL/np.sqrt(3)):.2f}")Yy0 (HV star, LV star) clock 0
Yy6 (LV star reversed) clock 6
Dy1 (HV delta A-C, B-A, C-B; LV star) clock 1
Dy11 (HV delta A-B, B-C, C-A; LV star) clock 11
Yd1 (HV star; LV delta, limb A winding a-b) clock 1
Yd11 (HV star; LV delta, limb A winding a-c) clock 11
HV line 26.24 A, HV delta winding 15.15 A at 11000 V; LV line = winding 695.6 A at 239.6 V; turns ratio per limb 45.91
Why the connection matters
- Parallel operation needs the same clock number: two units at 1 and 11 o'clock differ by , so their open-circuit LV voltages differ by per unit, and the circulating current would be about , ten or more times rated (Parallel Operation and Inrush).
- Triplen harmonics: a star–star unit without a delta winding has no path for the third-harmonic magnetising current; large Yy units get a delta tertiary winding.
- Earth faults and zero sequence: a delta blocks zero-sequence current between the systems on its two sides, which shapes how earth faults are seen by protection; this belongs to Power Systems.
- Zigzag windings (
Z,z) split each LV phase over two limbs. They give a neutral that tolerates unbalanced and harmonic loads and are used for earthing transformers.
Guided lab: phase shifts on paper and in the simulator
Hand calculation. Draw the HV line-voltage triangle, then for Dy1, Dy11 and Yd1 construct the LV phasors by copying each limb's HV winding voltage onto the LV side, as in the program. Read off the clock hour.
Simulation. Run the program; then, in the three-phase lab, compare a star and a delta load of the same per-branch impedance and confirm the factor and the shift between branch and line currents.
What you would measure. On a real installation, vector groups are checked by qualified staff with a dedicated transformer turns-ratio and phase-displacement tester applying a low test voltage to the de-energised, isolated transformer. The expected result is the nameplate's ratio within about (a typical tolerance on the declared ratio, IEC 60076-1:2011 as of 2026) and the nameplate's clock number exactly. This is not a learner experiment; the paper construction and the program are the exercise.
Hazards. Even a de-energised transformer can be back-fed from the LV side or hold charge in cables; such work needs isolation, earthing and permits.
Pitfalls
- Assuming the line-voltage ratio is the turns ratio. For Dy and Yd units it differs by .
- Clock direction. The number counts LV lagging in steps; 11 means LV leads by .
- Paralleling different groups. Same ratio and same clock number are both required.
- Forgetting the neutral.
Dyn11has an LV neutral brought out (n);Dy11does not.
Practice
- A , ,
Dyn11transformer: find the HV winding current and the LV winding voltage. - What is the clock number if the LV star of a Dy11 unit is reversed at its star point?
- A star–delta unit's LV leads its HV by . Write its vector group.
Answer
- , winding ; LV winding .
- Reversing all three LV windings adds (6 hours): , so
Dy5. - LV leads by = lags by :
Yd11.
Test yourself
In the vector group Dyn11, the '11' means…
- the LV voltage lags the HV by 11 degrees
- the LV voltage leads the HV by 30 degrees
- the LV voltage lags the HV by 30 degrees
- there are 11 turns per volt
A 500 kVA, 11 kV/415 V Dyn11 transformer has an HV delta winding current of about…
- 26.2 A
- 15.2 A
- 45.5 A
- 695.6 A
Why is a delta winding useful in a three-phase transformer?
- it removes the need for a neutral
- it provides a path for triplen harmonic currents
- it doubles the rating
- it eliminates leakage reactance
Two transformers of the same ratio, one Dy1 and one Dy11, are paralleled. What happens?
- they share load equally
- a large circulating current flows because their LV voltages differ by 60 degrees
- nothing, the phase shift cancels
- the neutral current doubles