The exact equivalent circuit of the previous lesson answers any question about a transformer, but it hides the reason behind the answer. Why does the output voltage fall more with a lagging load than with a resistive one? Why can a capacitive load push it above the no-load value? And can the shunt branch, the awkward middle of the T, simply be moved or dropped? A phasor diagram answers the first two at a glance, and a comparison with the exact circuit answers the third: for almost every loading question it can.

Safety: transformer T1 works at 2400 V2400\ \text{V} and is studied by calculation and simulation only.

Building the diagram

Take the referred output voltage V2′\mathbf{V}_2' as the reference, horizontal. A lagging load current I2′\mathbf{I}_2' points below it by the load angle φ\varphi. Walk back to the input through the series elements: the resistive drop I2′Req\mathbf{I}_2' R_\text{eq} is parallel to the current, the reactive drop jI2′Xeqj\mathbf{I}_2' X_\text{eq} is 90∘90^\circ ahead of it, and the tip of the chain is V1\mathbf{V}_1.

V2' I2' (lagging by phi) phi I R_eq j I X_eq V1

With a lagging current the reactive drop tips upward and almost lines up with V1\mathbf{V}_1, so its length adds nearly in full: V1V_1 is much longer than V2′V_2'. With a unity power factor the resistive drop is in line but the reactive drop is perpendicular, so it mostly rotates V1\mathbf{V}_1 and adds little length. With a leading current the reactive drop points partly backward and V1V_1 can be shorter than V2′V_2'. Projecting the chain onto V2′\mathbf{V}_2' gives the classic approximation for the voltage difference:

V1−V2′V2′≈rcos⁡φ+xsin⁡φ⏟in-phase part+(xcos⁡φ−rsin⁡φ)22⏟small quadrature correction\frac{V_1 - V_2'}{V_2'} \approx \underbrace{r\cos\varphi + x\sin\varphi}_{\text{in-phase part}} + \underbrace{\frac{(x\cos\varphi - r\sin\varphi)^2}{2}}_{\text{small quadrature correction}}

where r=IReq/Vr = I R_\text{eq}/V and x=IXeq/Vx = I X_\text{eq}/V are the per-unit drops and sin⁡φ>0\sin\varphi > 0 for lagging loads. The next lesson turns this into the voltage regulation (Voltage Regulation and Efficiency).

Approximate circuits

The shunt current of a power transformer is 1 to 3 % of the rated current, and the series voltage drop is a few percent. Each is small, and their interaction is smaller still, so two simplifications are standard:

  1. Shunt branch at the terminals (the "cantilever" circuit): move Rc∥XmR_c \parallel X_m to the input terminals and combine Req=R1+R2′R_\text{eq} = R_1 + R_2', Xeq=X1+X2′X_\text{eq} = X_1 + X_2'. The no-load current is still drawn, at the full input voltage instead of the slightly lower internal one.
  2. Series only: drop the shunt branch. Good for regulation, short-circuit currents and load sharing; useless for no-load current and core loss.

For T1: Req=0.50+0.52=1.02 ΩR_\text{eq} = 0.50 + 0.52 = 1.02\ \Omega and Xeq=1.6+1.6=3.2 ΩX_\text{eq} = 1.6 + 1.6 = 3.2\ \Omega referred to HV.

Worked example: T1 at three power factors

Given: T1 delivering rated current, 20.83 A20.83\ \text{A} referred to HV, at V2′=2400 VV_2' = 2400\ \text{V}, with power factor 0.80.8 lagging, unity and 0.80.8 leading.

Find: the input voltage by the series-only circuit.

Solve: with I2′=20.83∠−36.87∘ A=16.67−j12.50 A\mathbf{I}_2' = 20.83\angle{-36.87^\circ}\ \text{A} = 16.67 - j12.50\ \text{A} for the lagging case,

V1=V2′+I2′(Req+jXeq)=2400+(16.67−j12.50)(1.02+j3.2)=2400+(17.00+40.00)+j(53.33−12.75)=2457.0+j40.6 V,V1=2457.3 V\begin{aligned} \mathbf{V}_1 &= \mathbf{V}_2' + \mathbf{I}_2'(R_\text{eq} + jX_\text{eq}) = 2400 + (16.67 - j12.50)(1.02 + j3.2) \\ &= 2400 + (17.00 + 40.00) + j(53.33 - 12.75) = 2457.0 + j40.6\ \text{V}, \qquad V_1 = 2457.3\ \text{V} \end{aligned}

The unity and leading cases are the same sum with I2′=20.83 A\mathbf{I}_2' = 20.83\ \text{A} and 16.67+j12.50 A16.67 + j12.50\ \text{A}: 2422.2 V2422.2\ \text{V} and 2377.9 V2377.9\ \text{V}.

Check: the per-unit formula with r=20.83⋅1.02/2400=0.00885r = 20.83 \cdot 1.02/2400 = 0.00885 and x=20.83⋅3.2/2400=0.0278x = 20.83 \cdot 3.2/2400 = 0.0278 gives 0.00885⋅0.8+0.0278⋅0.6=0.02380.00885 \cdot 0.8 + 0.0278 \cdot 0.6 = 0.0238, plus a correction of 0.000140.00014: 2.39 %2.39\ \%, so V1=2457.5 VV_1 = 2457.5\ \text{V}. The leading load needs less than 2400 V2400\ \text{V} in: a lightly loaded cable network with a lot of capacitance raises the voltage at the far end, the Ferranti effect in miniature.

In Python: how good are the approximations?

python · try it yourself
import numpy as np
import matplotlib.pyplot as plt
# T1 referred to HV: windings Z1, Z2', shunt branch Ysh; rated load 20.83 A at V2' = 2400 V
Z1, Z2 = 0.50 + 1.6j, 0.52 + 1.6j
Zeq, Ysh = Z1 + Z2, 1 / 48e3 + 1 / (9.6e3j)
V2, I = 2400.0, 50e3 / 2400

print("load          exact V1 (V)   approx V1 (V)  V1 error   VR      formula VR")
for name, phi in (("0.8 lagging", -np.arccos(0.8)), ("unity", 0.0), ("0.8 leading", np.arccos(0.8))):
    I2 = I * np.exp(1j * phi)
    VE = V2 + I2 * Z2
    ve = VE + (I2 + VE * Ysh) * Z1              # exact T circuit
    va = V2 + I2 * Zeq                          # shunt branch moved to the terminals or dropped
    c, s = np.cos(-phi), np.sin(-phi)           # s > 0 for a lagging load
    R, X = Zeq.real * I / V2, Zeq.imag * I / V2 # per-unit drops at rated current
    vr_f = R * c + X * s + (X * c - R * s) ** 2 / 2
    print(f"{name:12s}  {abs(ve):7.1f}        {abs(va):7.1f}       {(abs(va) - abs(ve)) / abs(ve) * 100:5.2f} %  "
          f"{(abs(ve) - V2) / V2 * 100:5.2f} %   {vr_f * 100:5.2f} %")

# phasor diagram, series model, lagging load; the drops are drawn 10 times larger so they are visible
I2 = I * np.exp(-1j * np.arccos(0.8))
VR, VX = 10 * I2 * Zeq.real, 10 * 1j * I2 * Zeq.imag
fig, ax = plt.subplots(figsize=(6, 3.4))
for z0, dz, lab, col in ((0, V2, "V2'", "tab:blue"), (V2, VR, "I R_eq", "tab:green"),
                         (V2 + VR, VX, "j I X_eq", "tab:purple"), (0, V2 + VR + VX, "V1", "tab:red")):
    ax.annotate("", xy=((z0 + dz).real, (z0 + dz).imag), xytext=(np.real(z0), np.imag(z0)),
                arrowprops=dict(arrowstyle="->", color=col, lw=2))
    ax.text((z0 + dz).real + 30, (z0 + dz).imag + 30, lab, color=col)
ax.annotate("", xy=(I2.real * 60, I2.imag * 60), xytext=(0, 0), arrowprops=dict(arrowstyle="->", color="tab:orange", lw=2))
ax.text(I2.real * 60, I2.imag * 60 - 140, "I2' (x60)", color="tab:orange")
ax.set_xlim(-100, 3700); ax.set_ylim(-900, 1000); ax.set_aspect("equal")
ax.set_xlabel("real (V)"); ax.set_ylabel("imaginary (V)"); ax.set_title("T1, full load, pf 0.8 lagging (drops x10)")
plt.tight_layout()
plt.show()
load          exact V1 (V)   approx V1 (V)  V1 error   VR      formula VR
0.8 lagging    2457.8         2457.3       -0.02 %   2.41 %    2.39 %
unity          2422.6         2422.2       -0.02 %   0.94 %    0.92 %
0.8 leading    2378.3         2377.9       -0.02 %  -0.90 %   -0.92 %

The series-only circuit is within 0.02 %0.02\ \% of the exact one, and the per-unit formula within 0.020.02 percentage points. That is why regulation, fault currents and parallel load sharing are always worked with Req+jXeqR_\text{eq} + jX_\text{eq} alone. Keep the shunt branch when the question is about no-load current, core loss or efficiency at light load.

Interactive: a leading load raises the voltage

The lab uses the series-only T1 circuit (calculation only: 2400 V2400\ \text{V}) with a full-load leading load, 92.16 Ω92.16\ \Omega in series with 46.05 μF46.05\ \mu\text{F} (pf 0.80.8 leading at rated current, referred to HV). It shows V(h)=2.422 kVV(h) = 2.422\ \text{kV}: the output is 0.9 %0.9\ \% above the 2400 V2400\ \text{V} supply. Slide CL up to 2 mF2\ \text{mF}, where the capacitor hardly matters and the load is nearly resistive, and the output falls to about 2.374 kV2.374\ \text{kV}, below the supply. The lab also sweeps frequency on its plot; only the readouts at the 50 Hz50\ \text{Hz} cursor matter here.

010002000100m1101001k10kf (Hz)|V| (V)|V(h)|phasors at f = 50.00 Hz (magnitude @ phase)V(p)2.40 kV @ 0.0 degV(e)2.38 kV @ -0.3 degV(h)2.42 kV @ -1.6 degV(k)1.45 kV @ -54.7 degI(V1)21.0 A @ -144.7 degI(REQ)21.0 A @ 35.3 degI(LEQ)21.0 A @ 35.3 degI(RL)21.0 A @ 35.3 degI(CL)21.0 A @ 35.3 deg

Guided lab: phasors of a series circuit on the bench

Hand calculation. A transformer's series model is an RR–LL in series with the load, so a bench analogue at safe levels is a 10 Ω10\ \Omega resistor and a 10 mH10\ \text{mH} inductor (the "transformer") feeding a 100 Ω100\ \Omega resistor or a 100 Ω100\ \Omega + 100 μF100\ \mu\text{F} load from a 5 V5\ \text{V} rms, 200 Hz200\ \text{Hz} function generator. Predict the load voltage for both loads with the phasor sum.

Simulation. Enter the same components into the netlist lab (replace the netlist values) or the Python program.

What you would measure. With an oscilloscope, measure the generator and load voltages and their phase difference, and with a true-rms DMM their magnitudes. Expect the capacitive load's voltage to come out higher than with the plain resistor, and to agree with the prediction within the tolerances of the parts: ±5 %\pm 5\ \% for typical inductors and ±20 %\pm 20\ \% for electrolytic capacitors dominate, the meters add about 1 %1\ \%.

Hazards and safe setup. Function-generator levels only (a few volts). Electrolytic capacitors must not see reverse DC: use a bipolar (non-polarised) type for AC, or a film capacitor.

Pitfalls

  • Sign of sin⁡φ\sin\varphi. In the regulation formula it is positive for a lagging load and negative for a leading one.
  • Mixing referred and actual quantities. Draw the whole diagram on one side, then convert the answer.
  • Dropping the shunt branch for efficiency. At light load the core loss is most of the loss.
  • Drawing the drops to scale. At a few percent they are invisible; enlarge them and say so.

Practice

  1. With the series-only circuit, find T1's input voltage for rated current at pf 0.60.6 lagging.
  2. At what lagging power factor is the in-phase part rcos⁡φ+xsin⁡φr\cos\varphi + x\sin\varphi of T1 largest?
  3. A transformer has r=0.01r = 0.01 and x=0.05x = 0.05 per unit. At what leading power factor is the in-phase voltage drop zero?
Answer
  1. I2′=20.83∠−53.13∘=12.50−j16.67 A\mathbf{I}_2' = 20.83\angle{-53.13^\circ} = 12.50 - j16.67\ \text{A}; V1=2400+(12.50−j16.67)(1.02+j3.2)=2466.1+j23.0 V\mathbf{V}_1 = 2400 + (12.50 - j16.67)(1.02 + j3.2) = 2466.1 + j23.0\ \text{V}, V1=2466.2 VV_1 = 2466.2\ \text{V} (2.76 % above V2′V_2').
  2. When tan⁡φ=x/r=0.0278/0.00885=3.14\tan\varphi = x/r = 0.0278/0.00885 = 3.14: φ=72.3∘\varphi = 72.3^\circ, pf 0.300.30 lagging, where the drop equals r2+x2=2.92 %\sqrt{r^2 + x^2} = 2.92\ \%.
  3. rcos⁡φ=xsin⁡φr\cos\varphi = x\sin\varphi with a leading angle: tan⁡φ=r/x=0.2\tan\varphi = r/x = 0.2, φ=11.3∘\varphi = 11.3^\circ, pf 0.9810.981 leading.

Test yourself

For the same current, which load gives the largest drop in transformer output voltage?

  1. unity power factor
  2. lagging power factor
  3. leading power factor
  4. they are all equal

Why can the shunt branch be dropped when computing voltage regulation?

  1. it carries no current
  2. its current is a small fraction of the load current and barely changes the series drop
  3. it is in series with the load
  4. it is always resistive

With r=0.009r = 0.009, x=0.028x = 0.028 per unit and pf 0.8 lagging, the in-phase voltage drop is about…

  1. 0.9 %
  2. 2.4 %
  3. 3.7 %
  4. -0.9 %

In the netlist lab, T1 with a full-load leading load shows an output of 2.422 kV from a 2400 V supply. This is because…

  1. the core saturates
  2. the reactive drop points partly backward against the supply voltage
  3. the capacitor stores the core loss
  4. the lab ignores resistance