V-Curves, Synchronisation and the Infinite Bus
A generator connected to a large grid cannot change the grid's voltage or frequency; the grid is far too big. What then do its two controls do? The turbine governor sets the real power, as the power-angle curve showed. The field current sets the reactive power, and with it the armature current and the power factor. Plotting armature current against field current at constant power gives the famous V-curves, and the same idea lets a synchronous motor correct a factory's power factor. Before any of this the machine has to be connected to the grid, which is only safe when four conditions are met. This lesson covers all three: the infinite bus, V-curves and the capability chart, and synchronisation.
Safety: synchronising and operating grid-connected generators is high-voltage work done by trained operators with protection relays. This lesson is calculation and simulation only.
The infinite bus
An infinite bus is an idealised grid: a voltage source of fixed magnitude, frequency and phase with zero internal impedance. A generator on a national grid of tens of gigawatts comes very close. Two consequences:
- The machine's speed is fixed at ; the governor can only change the load angle , hence .
- The terminal voltage is fixed; the field can only change , hence and the current.
At constant the in-phase part of the current, , is fixed. Changing the field slides the tip of along a line parallel to (since is fixed), which changes only the reactive part of the current.
V-curves
Plot against at constant and each curve is a V:
- the minimum current is at unity power factor, ;
- to the right (over-excited) the current lags and the machine exports vars;
- to the left (under-excited) the current leads and the machine absorbs vars, until reaches : the steady-state stability limit, where the left end of each V stops.
Joining the minima of the Vs gives the unity-power-factor line, which bends to the right as rises. The same curves hold for a synchronous motor: an over-excited synchronous motor draws a leading current and supplies vars to the plant, cancelling the lagging current of its induction motors. Run with no shaft load, it is a synchronous condenser (compensator), still used on transmission grids for voltage support and system inertia (Power Systems).
Worked example: field currents for the course's generator
Given: the course's generator (, , , ) on an infinite bus, linearised OCC: gives . Turbine power .
Find: the minimum armature current and its field current, and the field current at the stability limit.
Solve: the in-phase current is fixed:
Check: at the whole of is perpendicular to , so , as found. Reducing the field below at would make the generator slip poles; protection (a loss-of-field relay) trips it first.
In Python: V-curves and the cost of a bad synchronisation
import numpy as np
VL, S = 6600.0, 5e6
V = VL / np.sqrt(3); Xs = 8.0 # the course's generator, per phase
I_N = S / (np.sqrt(3) * VL)
If_per_V = 160.0 / V # linearised OCC: 160 A field gives Ef = V
print(" P (pu) If at stability limit If at unity pf Ia min (A) If for rated Ia, lagging")
for p_pu in (0.0, 0.25, 0.5, 0.75, 0.85):
P = p_pu * S
Ef = np.linspace(1, 2.2 * V, 20001)
sin_d = P * Xs / (3 * V * Ef)
ok = sin_d <= 1 # beyond this the machine cannot carry P: pole slip
d = np.arcsin(sin_d[ok])
Ia = np.abs(Ef[ok] * np.exp(1j * d) - V) / Xs
If = Ef[ok] * If_per_V
k = np.argmin(Ia)
over = (If > If[k]) & (Ia >= I_N)
If_rated = If[over][0] if over.any() else float("nan")
limit = f"{If[0]:6.1f} A" if p_pu > 0 else " none "
print(f" {p_pu:4.2f} {limit} {If[k]:6.1f} A {Ia[k]:6.1f} {If_rated:6.1f} A")
print("closing out of phase (X''d = 0.15 pu, stiff grid):")
Xdpp = 0.15 * VL**2 / S
for theta in (5, 10, 30, 120):
dV = 2 * V * np.sin(np.radians(theta) / 2)
I = dV / Xdpp
print(f" {theta:3d} deg: voltage across breaker {dV:6.0f} V, current about {I:6.0f} A = {I/I_N:5.2f} x rated")
import matplotlib.pyplot as plt
for p_pu in (0.0, 0.25, 0.5, 0.75):
Ef = np.linspace(1, 2.2 * V, 2000)
sin_d = p_pu * S * Xs / (3 * V * Ef)
ok = sin_d <= 1
Ia = np.abs(Ef[ok] * np.exp(1j * np.arcsin(sin_d[ok])) - V) / Xs
plt.plot(Ef[ok] * If_per_V, Ia, label=f"P = {p_pu} pu")
plt.axhline(I_N, color="grey", ls=":")
plt.xlabel("field current If (A)"); plt.ylabel("armature current Ia (A)")
plt.ylim(0, 600); plt.legend(); plt.grid(True)
plt.show() P (pu) If at stability limit If at unity pf Ia min (A) If for rated Ia, lagging
0.00 none 160.0 A 0.0 306.9 A
0.25 36.7 A 164.2 A 109.3 304.5 A
0.50 73.5 A 176.1 A 218.7 296.5 A
0.75 110.2 A 194.3 A 328.0 279.8 A
0.85 124.9 A 203.0 A 371.8 268.3 A
closing out of phase (X''d = 0.15 pu, stiff grid):
5 deg: voltage across breaker 332 V, current about 254 A = 0.58 x rated
10 deg: voltage across breaker 664 V, current about 508 A = 1.16 x rated
30 deg: voltage across breaker 1972 V, current about 1509 A = 3.45 x rated
120 deg: voltage across breaker 6600 V, current about 5051 A = 11.55 x rated
At zero power the V touches zero current at (the field that makes ) and has no stability limit. As rises the minima move right and the stability limit moves right faster, squeezing the usable under-excited range. The last column is the field that reaches rated armature current on the lagging side: at it is the of the rated operating point.
Interactive: slide the field at constant power
This lab holds the real power fixed and lets you choose the reactive current. Current source IP injects the in-phase current (), and IQ the reactive current, entered as a lagging current at (negative values lead). The node e behind is then the internal EMF : its magnitude is what the field must produce. At the default lagging the lab shows and , the rated point. Slide IQ to (unity pf, smallest current) and to negative values: falls and rises towards .
Only the values matter; the frequency sweep has no meaning for a machine locked to the grid.
The capability chart
Operators work from a – chart that collects every limit in one picture:
- Stator (armature) heating: , a circle around the origin.
- Field (rotor) heating: the maximum , a circle of radius centred at ; it limits the over-excited, var-exporting corner. Here it meets the stator circle exactly at the rated point, by design.
- Prime mover: a horizontal line at the turbine's maximum power.
- Stability (under-excitation): at , plus a practical margin, and the stator-end heating limit at strong under-excitation. For this high-SCR machine the line lies outside the stator circle; for a turbogenerator with it would sit at and cut deep into the circle.
Synchronisation: four conditions
Before the circuit breaker closes, the incoming machine's voltage must match the bus in:
- Phase sequence (checked once at commissioning with a phase-rotation meter: wrong sequence is a short circuit).
- Voltage magnitude (set by the field; commonly within a few per cent, slightly high so the machine picks up a little reactive load).
- Frequency (set by the governor; slightly fast so it picks up a little real power instead of motoring).
- Phase angle (close at the instant the phasors coincide).
Guidance often quoted for large generators (IEEE C50.12 for salient-pole and C50.13 for cylindrical-rotor generators, as summarised in a 2012 SEL technical paper; check the current editions) is a phase error within , voltage to and slip within about . The output above shows why the angle matters: at the voltage across the breaker is and the inrush is about 3.5 times rated, with a matching torque shock on the shaft; at it is more than eleven times rated. Older plants used a synchroscope (a pointer that turns at the slip frequency) and dark-lamp or bright-lamp indicators; modern plants use an automatic synchroniser with a check-synchronising relay that blocks a bad close.
Guided lab (simulation)
Hand calculation. For , find the minimum armature current and the field current at the stability limit.
Simulation. In the netlist lab, find the reactive current at which reaches about ; in the code, compare with the field currents of the row.
What you would measure. In a power station control room (not a learner experiment) the V-curve test is run at a few power levels by stepping the field and logging , , , ; expect each V within about 2 % of the computed one near the minimum and larger deviation on the over-excited side, where saturation makes the linear OCC optimistic. A safe low-voltage hint of synchronisation: two small permanent-magnet DC motors driven at nearly equal speeds, each generating a few volts into a resistor, show beating when their AC ripple is viewed on a two-channel oscilloscope; never connect their outputs together. Keep fingers, hair and loose clothing clear of shafts and couplings.
Pitfalls
- Expecting the field to change real power on an infinite bus. It changes and ; follows the turbine.
- Under-exciting a loaded machine. The usable leading range shrinks as rises; the stability limit, not the stator current, can bind first.
- Synchronising slow. A machine slower than the grid takes power and briefly motors, which reverse-power protection may trip.
- Ignoring phase sequence after work on cables. One swapped pair turns synchronisation into a fault.
Practice
- At what is the minimum armature current of the course's generator?
- What field current is needed at for unity power factor? (Use the linearised OCC.)
- Two voltages of are apart when the breaker closes. What voltage appears across the open breaker just before?
Answer
- .
- ; ; .
- .
Test yourself
A generator on an infinite bus has its field current increased at constant turbine power. Its real power output…
- rises
- falls
- stays the same, while its reactive output rises
- drops to zero
Where is the bottom of a V-curve?
- at the stability limit
- at unity power factor
- at zero field current
- at maximum field current
An over-excited synchronous motor in a factory…
- draws a lagging current
- draws a leading current and supplies reactive power
- cannot run
- runs above synchronous speed
Which is NOT one of the conditions for synchronising a generator to the grid?
- same phase sequence
- same voltage magnitude
- same frequency and phase angle
- same number of poles as the grid's other generators