The Per-Unit System for Transformers and Machines

T1's series impedance is 1.02+j3.2 Ω1.02 + j3.2\ \Omega seen from its 2400 V2400\ \text{V} side and 0.0102+j0.032 Ω0.0102 + j0.032\ \Omega from its 240 V240\ \text{V} side. A 500 kVA500\ \text{kVA} transformer may have 16 mΩ16\ \text{m}\Omega, a 100 MVA100\ \text{MVA} generator 2 Ω2\ \Omega. None of these numbers says whether the impedance is large or small for its machine. Express each one as a fraction of a base value chosen from the machine's own rating, and they all become comparable: T1 is 0.0089+j0.02780.0089 + j0.0278 per unit from either side, and typical distribution and power transformers fall between about 0.020.02 and 0.150.15 per unit whatever their size. This lesson sets up the per-unit system and uses it for a fault calculation across a transformer.

Safety: the examples are mains and medium-voltage systems, studied by calculation only.

Bases

Choose two bases, usually the rated apparent power SbS_b and the rated voltage VbV_b of one side; the others follow from circuit laws:

Ib=SbVb,Zb=VbIb=Vb2Sb,zpu=ZZb,vpu=VVb,ipu=IIbI_b = \frac{S_b}{V_b}, \qquad Z_b = \frac{V_b}{I_b} = \frac{V_b^2}{S_b}, \qquad z_\text{pu} = \frac{Z}{Z_b}, \quad v_\text{pu} = \frac{V}{V_b}, \quad i_\text{pu} = \frac{I}{I_b}

Use the same SbS_b everywhere in a system, and on each side of a transformer a VbV_b in the ratio of its turns. Then an impedance referred across the transformer is multiplied by a2a^2, and so is the base impedance, so the per-unit value is the same on both sides: the ideal transformer disappears from the per-unit circuit.

Three-phase systems. Take SbS_b as the three-phase power and VbV_b as the line-to-line voltage:

Ib=Sb3 Vb,Zb=Vb2SbI_b = \frac{S_b}{\sqrt{3}\,V_b}, \qquad Z_b = \frac{V_b^2}{S_b}

The per-unit values then come out the same as for one phase of the star equivalent, and the 3\sqrt{3} factors vanish from the calculation.

Changing base. Nameplates give impedances in percent on the machine's own rating. To combine machines, convert to a common base:

znew=zold Sb,newSb,old(Vb,oldVb,new)2z_\text{new} = z_\text{old}\,\frac{S_{b,\text{new}}}{S_{b,\text{old}}}\left(\frac{V_{b,\text{old}}}{V_{b,\text{new}}}\right)^2

Why engineers like it

  • Sanity checks. Per-unit values cluster in narrow ranges by machine type, so a mistake shows at once. Typical orders of magnitude (from common textbook and manufacturer data, given as ranges, not guarantees): transformer leakage impedance 0.020.02 to 0.150.15, magnetising current 0.0050.005 to 0.030.03; induction motor magnetising reactance 22 to 44, starting current 55 to 88; synchronous machine synchronous reactance 11 to 22.
  • Impedance voltage sets the fault current. A transformer with z=0.0475z = 0.0475 passes 1/0.0475=211/0.0475 = 21 times rated current into a bolted fault on an infinitely strong supply.
  • Losses read as fractions. r=0.0089r = 0.0089 means a full-load copper loss of 0.89 %0.89\ \% of rating.

Worked example: a fault behind a transformer

~11 kV grid250 MVA fault level 500 kVA, 11 kV/415 Vz = 4.75 % F415 V bus 1 pu j0.004 j0.095 F (short)per unit on 1 MVA

Given: an 11 kV11\ \text{kV} supply with a three-phase fault level of 250 MVA250\ \text{MVA}, a 500 kVA500\ \text{kVA}, 11 kV/415 V11\ \text{kV}/415\ \text{V} transformer with z=4.75 %z = 4.75\ \% on its rating (treated as pure reactance), a bolted three-phase fault on the 415 V415\ \text{V} busbar.

Find: the fault current.

Solve: choose Sb=1 MVAS_b = 1\ \text{MVA}, Vb=11 kVV_b = 11\ \text{kV} and 415 V415\ \text{V}.

zs=SbSfault=1250=0.004 pu,zt=0.0475⋅1 MVA0.5 MVA=0.095 puif=10.004+0.095=10.10 pu,Ib=106 VA3⋅415 V=1391 AIf=10.10⋅1391 A=14.05 kA\begin{aligned} z_s &= \frac{S_b}{S_\text{fault}} = \frac{1}{250} = 0.004\ \text{pu}, \qquad z_t = 0.0475 \cdot \frac{1\ \text{MVA}}{0.5\ \text{MVA}} = 0.095\ \text{pu} \\ i_f &= \frac{1}{0.004 + 0.095} = 10.10\ \text{pu}, \qquad I_b = \frac{10^6\ \text{VA}}{\sqrt{3} \cdot 415\ \text{V}} = 1391\ \text{A} \\ I_f &= 10.10 \cdot 1391\ \text{A} = 14.05\ \text{kA} \end{aligned}

Check: in ohms on the 415 V415\ \text{V} side, Zs=4152/250×106=0.689 mΩZ_s = 415^2/250 \times 10^6 = 0.689\ \text{m}\Omega and Zt=0.0475⋅4152/500 000=16.36 mΩZ_t = 0.0475 \cdot 415^2/500\,000 = 16.36\ \text{m}\Omega, so If=239.6 V/17.05 mΩ=14.05 kAI_f = 239.6\ \text{V}/17.05\ \text{m}\Omega = 14.05\ \text{kA}. The grid adds only 4 % to the impedance; the transformer sets the fault level of a low-voltage board, which is why its zz is chosen with the switchgear's breaking capacity in mind. Fault studies continue in Power Systems.

In Python: per-unit both ways

python · try it yourself
import numpy as np
# 1) T1 in per unit: the same value from either side
S, VH, VL = 50e3, 2400.0, 240.0
Req_H, Xeq_H = 1.02, 3.2                              # ohms referred to HV
ZbH, ZbL = VH**2 / S, VL**2 / S
print(f"Zbase HV {ZbH:.1f} Ohm, LV {ZbL:.3f} Ohm")
print(f"from HV: z = {Req_H/ZbH:.5f} + j{Xeq_H/ZbH:.5f} pu")
print(f"from LV: z = {(Req_H/100)/ZbL:.5f} + j{(Xeq_H/100)/ZbL:.5f} pu")

# 2) change of base
def rebase(z, S_old, S_new, V_old=1.0, V_new=1.0):
    return z * (S_new / S_old) * (V_old / V_new) ** 2

# 3) fault at the 415 V bus: 11 kV grid with a fault level of 250 MVA, 500 kVA 11 kV/415 V transformer, z = 4.75 %
Sb = 1e6                                              # choose 1 MVA, line voltages 11 kV and 415 V as bases
zs = 1j * Sb / 250e6                                  # grid impedance (taken as pure reactance)
zt = 1j * rebase(0.0475, 500e3, Sb)                   # transformer reactance on the new base
If = 1 / abs(zs + zt)
Ib = Sb / (np.sqrt(3) * 415)
print(f"zs = {abs(zs):.4f} pu, zt = {abs(zt):.4f} pu, If = {If:.2f} pu x {Ib:.1f} A = {If*Ib/1e3:.2f} kA")
print(f"ignoring the grid impedance: {1/abs(zt)*Ib/1e3:.2f} kA")

# 4) the same fault in ohms on the 415 V side, as a check
Zs_ohm = 415**2 / 250e6
Zt_ohm = 0.0475 * 415**2 / 500e3
print(f"in ohms: Zs = {Zs_ohm*1e3:.3f} mOhm, Zt = {Zt_ohm*1e3:.3f} mOhm, If = {415/np.sqrt(3)/(Zs_ohm+Zt_ohm)/1e3:.2f} kA")
Zbase HV 115.2 Ohm, LV 1.152 Ohm
from HV: z = 0.00885 + j0.02778 pu
from LV: z = 0.00885 + j0.02778 pu
zs = 0.0040 pu, zt = 0.0950 pu, If = 10.10 pu x 1391.2 A = 14.05 kA
ignoring the grid impedance: 14.64 kA
in ohms: Zs = 0.689 mOhm, Zt = 16.361 mOhm, If = 14.05 kA

Interactive: the per-unit fault circuit

The netlist lab can work in per unit: a 1 V1\ \text{V} source is 1 pu1\ \text{pu}, and each reactance xx becomes an inductor L=x/(2π⋅50)L = x/(2\pi \cdot 50) (12.73 μH12.73\ \mu\text{H} for 0.0040.004, 302.4 μH302.4\ \mu\text{H} for 0.0950.095). With a bolted fault (RF at 0.0010.001) the lab shows 10.10 A10.10\ \text{A}, i.e. 10.10 pu10.10\ \text{pu}, and node t (the 11 kV11\ \text{kV} side) at 0.96 pu0.96\ \text{pu}: the grid voltage hardly dips for a fault behind a small transformer. Raise the fault resistance RF to see an arcing fault draw less current; at RF=2RF = 2 the "fault" is the transformer's full-load resistor (0.5 MVA0.5\ \text{MVA} is 0.5 pu0.5\ \text{pu} on the 1 MVA1\ \text{MVA} base). The lab also sweeps frequency on its plot; only the readouts at the 50 Hz50\ \text{Hz} cursor matter here.

0.00.51.0100m1101001k10kf (Hz)|V| (V)|V(b)||V(t)|phasors at f = 50.00 Hz (magnitude @ phase)V(g)1.00 V @ 0.0 degV(t)960 mV @ 0.0 degV(b)10.1 mV @ -89.4 degI(V1)10.1 A @ 90.6 degI(LS)10.1 A @ -89.4 degI(LT)10.1 A @ -89.4 degI(RF)10.1 A @ -89.4 deg

Guided lab: per-unit values of your bench transformer

Hand calculation. Take the small signal transformer from the earlier labs, choose its rated signal level and current as bases (for example 1 V1\ \text{V}, 20 mA20\ \text{mA}, so Zb=50 ΩZ_b = 50\ \Omega), and convert your measured winding resistance, leakage reactance and magnetising reactance to per unit.

Simulation. Run the program with your numbers to confirm the per-unit value is the same from both windings.

What you would measure. Nothing new: reuse the LCR and DMM readings. The point is the comparison: a signal transformer's per-unit resistance is often 0.050.05 to 0.20.2 (much larger than a power transformer's 0.010.01), because small windings of thin wire are relatively lossy. The per-unit values carry the same relative uncertainty as the readings (a few percent).

Hazards and safe setup. Signal levels only, as before.

Pitfalls

  • Mixing bases. Every impedance in one calculation must be on the same SbS_b, with voltage bases that follow the turns ratios.
  • Phase and line quantities. With three-phase bases (three-phase SS, line VV), per-unit values are the same as per phase; don't add a 3\sqrt{3}.
  • Percent and per unit. 4.75 %4.75\ \% is 0.04750.0475 pu.
  • Rated voltage not equal to base voltage. If a transformer's rating differs from the system base voltage, rebase with the voltage-squared factor.

Practice

  1. A 200 kVA200\ \text{kVA}, 11/0.4 kV11/0.4\ \text{kV} transformer has z=4 %z = 4\ \%. Express it on a 1 MVA1\ \text{MVA} base.
  2. What is the bolted three-phase fault current on its 400 V400\ \text{V} side with an infinitely strong supply?
  3. A motor rated 75 kW75\ \text{kW}, 400 V400\ \text{V}, efficiency 0.950.95 and pf 0.860.86 draws 6.56.5 times rated current when starting. What is its starting impedance in per unit of its own rating?
Answer
  1. 0.04⋅1000/200=0.20 pu0.04 \cdot 1000/200 = 0.20\ \text{pu}.
  2. IbI_b on its own rating =200 000/(3⋅400)=288.7 A= 200\,000/(\sqrt{3} \cdot 400) = 288.7\ \text{A}; If=288.7/0.04=7.22 kAI_f = 288.7/0.04 = 7.22\ \text{kA}.
  3. Rated input =75/(0.95⋅0.86)=91.8 kVA= 75/(0.95 \cdot 0.86) = 91.8\ \text{kVA}; on that base the starting current is 6.5 pu6.5\ \text{pu} at 1 pu1\ \text{pu} voltage, so zstart=1/6.5=0.154 puz_\text{start} = 1/6.5 = 0.154\ \text{pu}.

Test yourself

A transformer's per-unit leakage impedance, on its own rating, is…

  1. larger on the HV side
  2. larger on the LV side
  3. the same on both sides
  4. zero on the LV side

With three-phase power and line voltage as bases, the base current is…

  1. Sb/VbS_b/V_b
  2. Sb/(3Vb)S_b/(\sqrt{3}V_b)
  3. 3Sb/Vb\sqrt{3}S_b/V_b
  4. Vb2/SbV_b^2/S_b

A 500 kVA transformer has z = 5 %. On a 1 MVA base it is…

  1. 0.025 pu
  2. 0.05 pu
  3. 0.10 pu
  4. 0.20 pu

A transformer with z=0.0475z = 0.0475 pu is fed from an infinitely strong supply. Its bolted short-circuit current is about…

  1. 4.75 times rated
  2. 10 times rated
  3. 21 times rated
  4. 47.5 times rated