The Per-Unit System for Transformers and Machines
T1's series impedance is seen from its side and from its side. A transformer may have , a generator . None of these numbers says whether the impedance is large or small for its machine. Express each one as a fraction of a base value chosen from the machine's own rating, and they all become comparable: T1 is per unit from either side, and typical distribution and power transformers fall between about and per unit whatever their size. This lesson sets up the per-unit system and uses it for a fault calculation across a transformer.
Safety: the examples are mains and medium-voltage systems, studied by calculation only.
Bases
Choose two bases, usually the rated apparent power and the rated voltage of one side; the others follow from circuit laws:
Use the same everywhere in a system, and on each side of a transformer a in the ratio of its turns. Then an impedance referred across the transformer is multiplied by , and so is the base impedance, so the per-unit value is the same on both sides: the ideal transformer disappears from the per-unit circuit.
Three-phase systems. Take as the three-phase power and as the line-to-line voltage:
The per-unit values then come out the same as for one phase of the star equivalent, and the factors vanish from the calculation.
Changing base. Nameplates give impedances in percent on the machine's own rating. To combine machines, convert to a common base:
Why engineers like it
- Sanity checks. Per-unit values cluster in narrow ranges by machine type, so a mistake shows at once. Typical orders of magnitude (from common textbook and manufacturer data, given as ranges, not guarantees): transformer leakage impedance to , magnetising current to ; induction motor magnetising reactance to , starting current to ; synchronous machine synchronous reactance to .
- Impedance voltage sets the fault current. A transformer with passes times rated current into a bolted fault on an infinitely strong supply.
- Losses read as fractions. means a full-load copper loss of of rating.
Worked example: a fault behind a transformer
Given: an supply with a three-phase fault level of , a , transformer with on its rating (treated as pure reactance), a bolted three-phase fault on the busbar.
Find: the fault current.
Solve: choose , and .
Check: in ohms on the side, and , so . The grid adds only 4 % to the impedance; the transformer sets the fault level of a low-voltage board, which is why its is chosen with the switchgear's breaking capacity in mind. Fault studies continue in Power Systems.
In Python: per-unit both ways
import numpy as np
# 1) T1 in per unit: the same value from either side
S, VH, VL = 50e3, 2400.0, 240.0
Req_H, Xeq_H = 1.02, 3.2 # ohms referred to HV
ZbH, ZbL = VH**2 / S, VL**2 / S
print(f"Zbase HV {ZbH:.1f} Ohm, LV {ZbL:.3f} Ohm")
print(f"from HV: z = {Req_H/ZbH:.5f} + j{Xeq_H/ZbH:.5f} pu")
print(f"from LV: z = {(Req_H/100)/ZbL:.5f} + j{(Xeq_H/100)/ZbL:.5f} pu")
# 2) change of base
def rebase(z, S_old, S_new, V_old=1.0, V_new=1.0):
return z * (S_new / S_old) * (V_old / V_new) ** 2
# 3) fault at the 415 V bus: 11 kV grid with a fault level of 250 MVA, 500 kVA 11 kV/415 V transformer, z = 4.75 %
Sb = 1e6 # choose 1 MVA, line voltages 11 kV and 415 V as bases
zs = 1j * Sb / 250e6 # grid impedance (taken as pure reactance)
zt = 1j * rebase(0.0475, 500e3, Sb) # transformer reactance on the new base
If = 1 / abs(zs + zt)
Ib = Sb / (np.sqrt(3) * 415)
print(f"zs = {abs(zs):.4f} pu, zt = {abs(zt):.4f} pu, If = {If:.2f} pu x {Ib:.1f} A = {If*Ib/1e3:.2f} kA")
print(f"ignoring the grid impedance: {1/abs(zt)*Ib/1e3:.2f} kA")
# 4) the same fault in ohms on the 415 V side, as a check
Zs_ohm = 415**2 / 250e6
Zt_ohm = 0.0475 * 415**2 / 500e3
print(f"in ohms: Zs = {Zs_ohm*1e3:.3f} mOhm, Zt = {Zt_ohm*1e3:.3f} mOhm, If = {415/np.sqrt(3)/(Zs_ohm+Zt_ohm)/1e3:.2f} kA")Zbase HV 115.2 Ohm, LV 1.152 Ohm
from HV: z = 0.00885 + j0.02778 pu
from LV: z = 0.00885 + j0.02778 pu
zs = 0.0040 pu, zt = 0.0950 pu, If = 10.10 pu x 1391.2 A = 14.05 kA
ignoring the grid impedance: 14.64 kA
in ohms: Zs = 0.689 mOhm, Zt = 16.361 mOhm, If = 14.05 kA
Interactive: the per-unit fault circuit
The netlist lab can work in per unit: a source is , and each reactance becomes an inductor ( for , for ). With a bolted fault (RF at ) the lab shows , i.e. , and node t (the side) at : the grid voltage hardly dips for a fault behind a small transformer. Raise the fault resistance RF to see an arcing fault draw less current; at the "fault" is the transformer's full-load resistor ( is on the base). The lab also sweeps frequency on its plot; only the readouts at the cursor matter here.
Guided lab: per-unit values of your bench transformer
Hand calculation. Take the small signal transformer from the earlier labs, choose its rated signal level and current as bases (for example , , so ), and convert your measured winding resistance, leakage reactance and magnetising reactance to per unit.
Simulation. Run the program with your numbers to confirm the per-unit value is the same from both windings.
What you would measure. Nothing new: reuse the LCR and DMM readings. The point is the comparison: a signal transformer's per-unit resistance is often to (much larger than a power transformer's ), because small windings of thin wire are relatively lossy. The per-unit values carry the same relative uncertainty as the readings (a few percent).
Hazards and safe setup. Signal levels only, as before.
Pitfalls
- Mixing bases. Every impedance in one calculation must be on the same , with voltage bases that follow the turns ratios.
- Phase and line quantities. With three-phase bases (three-phase , line ), per-unit values are the same as per phase; don't add a .
- Percent and per unit. is pu.
- Rated voltage not equal to base voltage. If a transformer's rating differs from the system base voltage, rebase with the voltage-squared factor.
Practice
- A , transformer has . Express it on a base.
- What is the bolted three-phase fault current on its side with an infinitely strong supply?
- A motor rated , , efficiency and pf draws times rated current when starting. What is its starting impedance in per unit of its own rating?
Answer
- .
- on its own rating ; .
- Rated input ; on that base the starting current is at voltage, so .
Test yourself
A transformer's per-unit leakage impedance, on its own rating, is…
- larger on the HV side
- larger on the LV side
- the same on both sides
- zero on the LV side
With three-phase power and line voltage as bases, the base current is…
A 500 kVA transformer has z = 5 %. On a 1 MVA base it is…
- 0.025 pu
- 0.05 pu
- 0.10 pu
- 0.20 pu
A transformer with pu is fed from an infinitely strong supply. Its bolted short-circuit current is about…
- 4.75 times rated
- 10 times rated
- 21 times rated
- 47.5 times rated