DC Generators: Excitation and Characteristics
A DC generator needs a field, and the field needs a current. Where that current comes from, a separate source, the generator's own output, or the load current itself, decides almost everything about how the machine behaves: whether it starts generating at all, how much its voltage sags under load, and whether it collapses when overloaded. DC generators are rare in new plant today (rectified alternators replaced them), but the same ideas reappear in every DC motor, in the exciters of synchronous machines and in small dynamos, and self-excitation is a classic example of a nonlinear system finding its operating point. This lesson treats the four connections, separately excited, shunt, series and compound, with one machine and its magnetisation curve.
The four connections
| Connection | Field current | Characteristic | Use |
|---|---|---|---|
| Separately excited | from a separate supply | falls slightly: , plus a little armature reaction | test sets, exciters, Ward-Leonard drives |
| Shunt | , from its own terminals | falls more: lower means lower , so lower ; collapses on overload | battery charging, general supply |
| Series | the load current itself | rises with load until saturation | historically line boosters |
| Compound | shunt field plus a series field in the line | flat or rising (cumulative), or steeply drooping (differential) | flat: supply over a feeder; differential: welding |
The magnetisation curve and self-excitation
The open-circuit characteristic (OCC) is against at a fixed speed: linear at first, then bending over as the iron saturates, and not starting at zero, because the poles keep a little residual flux. In this lesson's machine at :
A shunt generator starts from the residual voltage. That small EMF drives a small field current, which (if the field is connected the right way round) adds to the residual flux and raises , which raises , and so on. The field circuit obeys
so the voltage builds up while the OCC lies above the field-resistance line , and settles where they cross. Three conditions for build-up:
- There must be residual magnetism (a machine stored for years may need its field "flashed" from a battery).
- The field must be connected so its MMF aids the residual flux; reversed, it wipes the residual out.
- The field-circuit resistance must be below the critical field resistance, the slope of the OCC's linear part. The critical value is proportional to speed, so for a given there is also a critical speed.
Worked example: a shunt generator
Given: the OCC above at ; ; shunt field-circuit resistance ; field inductance ; load current .
Find: the critical field resistance, the no-load voltage, the terminal voltage at , and the regulation.
Solve:
The on-load equation is solved numerically (code below).
Check: substitute : , , , . With the same field held constant from a separate supply the voltage would be : the shunt machine sags about twice as much because its field weakens with its own voltage.
This is a , class machine: calculation and simulation only.
In Python: build-up, load characteristics and breakdown
import numpy as np
from scipy.optimize import brentq
from scipy.integrate import solve_ivp
# open-circuit characteristic at 1500 rpm: 6 V residual plus a saturating curve
E = lambda If: 6.0 + 280.0 * np.tanh(If / 1.0) # V, field current If in A
Ra, Lf = 0.25, 20.0 # armature resistance (ohm), field inductance (H)
print(f"critical field-circuit resistance (initial OCC slope) at 1500 rpm: {280.0/1.0:.0f} ohm")
for Rf in (150.0, 200.0, 250.0, 350.0):
If = brentq(lambda If: E(If) - (Rf + Ra) * If, 1e-6, 10)
print(f"Rf = {Rf:3.0f} ohm: no-load E = {E(If):6.1f} V (If = {If:.3f} A)")
# build-up in time for Rf = 200 ohm: Lf dIf/dt = E(If) - (Rf + Ra) If, from the residual voltage
Rf = 200.0
sol = solve_ivp(lambda t, y: [(E(y[0]) - (Rf + Ra) * y[0]) / Lf], (0, 4), [0.0],
t_eval=[0.25, 0.5, 1.0, 2.0, 3.0, 4.0], rtol=1e-8, atol=1e-10)
print("build-up:", ", ".join(f"{t:.2f} s {E(If):.0f} V" for t, If in zip(sol.t, sol.y[0])))
# terminal voltage on load: separately excited (If held at its no-load value) vs shunt (If = V/Rf)
If0 = brentq(lambda If: E(If) - (Rf + Ra) * If, 1e-6, 10)
print(" IL separately excited shunt")
for IL in (0, 20, 40, 60):
Vsep = E(If0) - IL * Ra
Vsh = brentq(lambda V: E(V / Rf) - (IL + V / Rf) * Ra - V, 60, 400)
print(f"{IL:4d} A {Vsep:6.1f} V {Vsh:6.1f} V")
# a shunt generator can only deliver so much: IL(V) = (E(V/Rf) - V)/Ra - V/Rf has a maximum
V = np.linspace(1, 238, 4000)
IL = (E(V / Rf) - V) / Ra - V / Rf
k = int(np.argmax(IL))
print(f"shunt breakdown: at most {IL[k]:.1f} A, reached at V = {V[k]:.0f} V; more load and the voltage collapses")critical field-circuit resistance (initial OCC slope) at 1500 rpm: 280 ohm
Rf = 150 ohm: no-load E = 271.3 V (If = 1.805 A)
Rf = 200 ohm: no-load E = 238.8 V (If = 1.192 A)
Rf = 250 ohm: no-load E = 175.3 V (If = 0.701 A)
Rf = 350 ohm: no-load E = 29.6 V (If = 0.085 A)
build-up: 0.25 s 42 V, 0.50 s 122 V, 1.00 s 230 V, 2.00 s 239 V, 3.00 s 239 V, 4.00 s 239 V
IL separately excited shunt
0 A 238.8 V 238.5 V
20 A 233.8 V 229.4 V
40 A 228.8 V 219.7 V
60 A 223.8 V 209.2 V
shunt breakdown: at most 144.9 A, reached at V = 119 V; more load and the voltage collapses
The field rheostat is the voltage control: gives , only , and above the critical the machine stays near its residual voltage (here , because the OCC is close to the resistance line). Build-up takes about a second. On load the shunt curve droops faster than the separately excited one, and past about no operating point exists: a short circuit on a shunt generator kills its own field, so the steady short-circuit current is small. A separately excited machine has no such protection.
The field winding is an RL circuit
Once the field current has built up, changing the excitation is an RL transient with . The lab below has the same time constant at bench scale ( and at ): after , , the current is at 63.2 %, of its final , and the coil stores .
Switch to "switch off" to see the decay. A real field opened by a switch has nowhere for that stored energy to go except an arc or a voltage spike across the winding insulation; field circuits have a discharge resistor or a diode for that reason.
Guided lab: a small PM generator on load
Hand calculation. A permanent-magnet motor used as a generator behaves like the separately excited machine: . With , and (), ; into , and .
Simulation. Replace the OCC in the Python cell with a constant and the field with nothing: the "separately excited" column with your , speed and .
What you would measure. Drive the generator motor through a coupling from a second small motor on a current-limited bench supply (as in DC Machines: Construction), or turn a hand-cranked dynamo. Load it with , and power resistors (rated at least ) and record , and speed. The points fall on a line whose slope gives (expect scatter, since brush contact resistance changes with current and speed), and the driving motor slows and draws more current as you load the generator: the load torque you feel on a hand crank is .
Hazards and safe setup. Supply at most with a current limit; clamp both motors; keep hands and hair away from the coupling; wear safety glasses. Load resistors get hot. Never short a generator spinning at speed: the current is limited only by .
Pitfalls
- "It won't build up." Check the three conditions: residual flux, field polarity, below critical (or the speed too low).
- Using the no-load OCC on load without . The terminal voltage is the OCC value minus the armature drop and any armature-reaction loss.
- Assuming a shorted shunt generator is safe. The collapse needs time and a separately excited or compound machine can deliver a huge current.
- Opening a field circuit. Stored energy arcs across the switch or punctures insulation.
Practice
- At the same machine's OCC is scaled by . What is the critical field resistance?
- Use the code to find the no-load voltage with at .
- A cumulatively compounded generator gives at no load and at full load. Is it under-, flat- or over-compounded?
Answer
- ; with it still builds up, but only just.
- About (change the loop to
(175.0,)). - Over-compounded: the series field more than makes up for the drop.
Test yourself
A shunt generator fails to build up. Which change can fix it?
- increase the field resistance
- reduce the speed
- reverse the field connection if it opposes the residual flux
- add load
The critical field resistance of a shunt generator is…
- the slope of the linear part of the OCC at that speed
- the armature resistance
- the load resistance at full load
- independent of speed
Why does a shunt generator's voltage droop more than a separately excited one's?
- more armature resistance
- its field current falls with its terminal voltage
- it runs slower
- it has no residual flux
Which generator's terminal voltage rises with load current from near zero?
- separately excited
- shunt
- series
- differentially compounded