Home › Electrical Machines & Transformers › Starting Methods and Speed Control, Including V/f

Starting Methods and Speed Control, Including V/f

Switched straight onto the supply, the example 7.5 kW7.5\ \text{kW} motor draws 91 A91\ \text{A}, more than six times its rated current, for the second or two it takes to run up. A 200 kW200\ \text{kW} pump motor on a weak rural feeder would dim every light in the village and might trip its own protection. And once running, the motor turns at almost constant speed, while a fan, a conveyor or a machine tool wants to choose its speed. This lesson compares the ways to start an induction motor and the ways to change its speed, ending with the method that has displaced most of the others: the variable-frequency drive with V/f control.

Safety: starters, contactors and drives switch 400 V400\ \text{V} three-phase power and store energy in capacitors. Everything here is calculation and simulation only. A motor that has been switched off can keep coasting for a long time if it drives a flywheel or fan, and while it coasts its residual flux still produces a voltage at the terminals for a short while: never touch terminals or a shaft until the machine is isolated, locked off and stationary.

Starting: why the current is high

At standstill s=1s = 1 and the rotor branch is just R2′+jX2′R_2' + jX_2', a few ohms. From the torque–slip curve, the example motor starts with I1=91.0 AI_1 = 91.0\ \text{A} (6.3IN6.3I_N) and 65.4 N m65.4\ \text{N m}. The current itself does the motor little harm for a few seconds, but it causes a voltage dip on the supply, stresses couplings with a torque step, and heats a rotor that has to accelerate a large inertia. All reduced-current methods trade starting torque for current.

Method Line current at start Starting torque Notes
Direct on line (DOL) IstI_{st} TstT_{st} simplest; normal up to a few kW, or larger on a stiff supply
Star–delta Ist/3I_{st}/3 Tst/3T_{st}/3 motor wound for delta at supply voltage, six leads; a current and torque transient at the changeover
Autotransformer, tap xx x2Istx^2 I_{st} x2Tstx^2 T_{st} taps 50–80 %; better torque per line ampere than a resistor
Soft starter (thyristors) xIstx I_{st} at voltage xVxV x2Tstx^2 T_{st} smooth ramp, current limit; for pumps and fans with low starting torque
Variable-frequency drive about INI_N to 1.5IN1.5I_N up to 1.5TN1.5T_N and more full torque from standstill; also gives speed control

Two results need a line of algebra. Star–delta: in star each winding gets VL/3V_L/\sqrt{3} instead of VLV_L, so its current falls by 3\sqrt{3}; and a star line current equals the phase current, while in delta it is 3\sqrt{3} times the phase current. Together, 1/31/3. Torque goes with voltage squared: also 1/31/3. Autotransformer: the motor sees xVxV and draws xIstxI_{st} on the motor side, which the autotransformer reflects to the line as x⋅xIstx \cdot xI_{st} (Autotransformers).

L1L2L3 KM1main U1U2 V1V2 W1W2 motor windings KM3star (start) star point

KM2 delta (run) U2 to V1V2 to W1W2 to U1

Worked example: starting the example motor

Given: the example motor (Ist=91.0 AI_{st} = 91.0\ \text{A}, Tst=65.4 N mT_{st} = 65.4\ \text{N m}, IN=14.43 AI_N = 14.43\ \text{A}, TN=48.9 N mT_N = 48.9\ \text{N m}), wound for 400 V400\ \text{V} delta so that star–delta is possible with the same per-phase (star-equivalent) circuit.

Find: line current and starting torque for star–delta, a 65 % autotransformer, and a soft starter limited to 3IN3I_N.

Solve:

star–delta:I=91.0 A3=30.3 A,T=65.4 N m3=21.8 N mautotransformer:I=0.652⋅91.0 A=38.5 A,T=0.652⋅65.4 N m=27.6 N msoft starter:x=3⋅14.43 A91.0 A=0.476,T=0.4762⋅65.4 N m=14.8 N m\begin{aligned} \text{star–delta:}&\quad I = \frac{91.0\ \text{A}}{3} = 30.3\ \text{A}, \qquad T = \frac{65.4\ \text{N m}}{3} = 21.8\ \text{N m} \\ \text{autotransformer:}&\quad I = 0.65^2 \cdot 91.0\ \text{A} = 38.5\ \text{A}, \qquad T = 0.65^2 \cdot 65.4\ \text{N m} = 27.6\ \text{N m} \\ \text{soft starter:}&\quad x = \frac{3 \cdot 14.43\ \text{A}}{91.0\ \text{A}} = 0.476, \qquad T = 0.476^2 \cdot 65.4\ \text{N m} = 14.8\ \text{N m} \end{aligned}

Check: none of the reduced-voltage methods gives even half the rated torque at standstill with this (single-cage) model. They suit centrifugal pumps and fans, whose load torque near standstill is small, but not a loaded conveyor. A real double-cage or deep-bar motor has about twice this starting torque, which is why star–delta works in practice for many machines.

Interactive: star and delta line currents at standstill (calculation only)

The three-phase lab with the locked-rotor impedance of a delta-wound version of the example motor: per winding 3×(0.963+j2.347)≈3+j7 Ω3 \times (0.963 + j2.347) \approx 3 + j7\ \Omega. In delta the lab shows a line current of 90.60 A90.60\ \text{A}; switch the connection to star and it falls to 30.20 A30.20\ \text{A}, exactly one third (the small difference from 91.0 A91.0\ \text{A} is the rounding of the impedance).

VaVbVcIaIbIcV solid, I thin (own scale)delta-pk0+pk0T2Tphase voltages, peak 325 V-pk0+pk0T2Tline currents, peak 128 AP = 24.6 kW Q = 57.5 kvar S = 62.5 kVApf = 0.394 balanced IN = 0 A

Speed control

Speed is n=(1−s) 120f/pn = (1 - s)\,120f/p, so there are three handles: the poles pp, the slip ss, and the frequency ff.

  • Pole changing. A Dahlander winding reconnects to give two speeds in a 2:12:1 ratio (for example 1500 and 3000 rpm3000\ \text{rpm}); separate windings give other ratios. Cheap and efficient, but steps only.
  • Slip control. Raising rotor resistance (wound rotor, external resistors) or lowering stator voltage (fans) increases slip. It works, but the rotor copper loss is sPagsP_\text{ag}: at half speed half the air-gap power is turned into heat. Slip-energy recovery schemes and the doubly-fed induction generator recover it with converters.
  • Frequency control. A variable-frequency drive (VFD) rectifies the supply and synthesises a new three-phase supply of variable frequency with a PWM inverter (Power Electronics & Motor Drives). Slip stays small at every speed, so efficiency stays high.

V/f control

Changing ff alone would be wrong: the flux is Φ≈V/(4.44fNkw)\Phi \approx V/(4.44fNk_w) (Rotating Field), so lowering ff at constant VV saturates the core. The drive therefore keeps V/fV/f constant below rated frequency: constant flux, the same torque capability, and a torque–speed curve that simply slides left. Above rated frequency the voltage cannot rise further, flux falls as 1/f1/f and the motor runs in the field-weakening region with roughly constant power.

At low frequency pure V/f fails because the stator resistance drop I1R1I_1R_1 is no longer small compared with VV: at 5 Hz5\ \text{Hz} the example motor's phase voltage is only 23 V23\ \text{V} and 14 A⋅0.55 Ω=8 V14\ \text{A} \cdot 0.55\ \Omega = 8\ \text{V} of it is lost in R1R_1. Drives add a boost voltage at low frequency (here 12 V12\ \text{V} per phase at 0 Hz0\ \text{Hz}, rising linearly to rated). Vector control and direct torque control go further by regulating flux and torque currents separately (Motor Control).

In Python: starting methods and a V/f family

python · try it yourself
import numpy as np
from scipy.optimize import brentq
p = 4
R1, X1, Xm, R2, X2 = 0.55, 1.0, 32.0, 0.45, 1.4      # example motor, X at 50 Hz

def motor(s, V, f):
    """Per-phase circuit at supply frequency f: returns (torque N m, stator current A)."""
    k = f / 50
    Z2 = R2 / s + 1j * X2 * k
    Zp = 1j * Xm * k * Z2 / (1j * Xm * k + Z2)
    I1 = V / (R1 + 1j * X1 * k + Zp)
    I2 = I1 * 1j * Xm * k / (1j * Xm * k + Z2)
    ws = 4 * np.pi * f / p
    return 3 * abs(I2) ** 2 * R2 / s / ws, abs(I1)

V_N = 400 / np.sqrt(3)
T0, I0 = motor(1.0, V_N, 50)
print(f"starting method             line current   starting torque")
print(f"direct on line                {I0:6.1f} A       {T0:5.1f} N m")
print(f"star-delta                    {I0/3:6.1f} A       {T0/3:5.1f} N m")
x = 0.65
print(f"autotransformer, 65 % tap     {I0*x**2:6.1f} A       {T0*x**2:5.1f} N m")
k = 3 * 14.43 / I0                                    # soft starter limited to 3 x rated current
print(f"soft starter at {k*100:.0f} % voltage   {I0*k:6.1f} A       {T0*k**2:5.1f} N m")

print("\n f (Hz)  V boost (V)  n_s (rpm)  T_max pure V/f  T_max boosted  speed and current at 50.35 N m")
V_b = 12.0                                            # boost voltage per phase at 0 Hz
for f in (50, 35, 20, 10, 5):
    V_pure = V_N * f / 50
    V_boost = V_b + (V_N - V_b) * f / 50
    s_grid = np.linspace(1e-3, 1, 4000)
    Tmax_pure = max(motor(s, V_pure, f)[0] for s in s_grid)
    Tmax_boost = max(motor(s, V_boost, f)[0] for s in s_grid)
    s_op = brentq(lambda s: motor(s, V_boost, f)[0] - 50.35, 1e-4, 0.5)
    ns = 120 * f / p
    print(f"{f:5.0f}   {V_boost:8.1f}    {ns:7.0f}     {Tmax_pure:8.1f}      {Tmax_boost:8.1f}"
          f"       {ns*(1-s_op):6.0f} rpm, {motor(s_op, V_boost, f)[1]:5.2f} A")
starting method             line current   starting torque
direct on line                  91.0 A        65.4 N m
star-delta                      30.3 A        21.8 N m
autotransformer, 65 % tap       38.5 A        27.6 N m
soft starter at 48 % voltage     43.3 A        14.8 N m

 f (Hz)  V boost (V)  n_s (rpm)  T_max pure V/f  T_max boosted  speed and current at 50.35 N m
   50      230.9       1500        162.2         162.2         1462 rpm, 14.43 A
   35      165.3       1050        147.8         154.5         1013 rpm, 14.34 A
   20       99.6        600        118.4         137.6          565 rpm, 14.13 A
   10       55.8        300         76.6         111.7          269 rpm, 13.70 A
    5       33.9        150         42.4          91.2          126 rpm, 13.19 A

With the boost the motor carries its full rated torque at 5 Hz5\ \text{Hz} (126 rpm126\ \text{rpm}) on slightly less than rated current; with pure V/f its maximum torque there (42 N m42\ \text{N m}) is below the rated load and it would stall. Note also that the slip speed at rated torque stays near 2525–40 rpm40\ \text{rpm} at every frequency: that is why V/f control is efficient.

Guided lab (simulation and datasheet)

Hand calculation. For an autotransformer tap of 80 %, compute the line current and torque at start.

Simulation. Change V_b in the code to 0 and to 20 and see how the low-speed torque changes; too much boost over-fluxes the motor at light load (watch the current at 5 Hz).

What you would measure. In a qualified lab or on commissioning (not a learner experiment: mains voltages and stored energy in the drive's DC-link capacitors, which stay charged for minutes after switch-off): a clamp meter and a power-quality recorder show the DOL inrush (6–8 INI_N for 0.50.5–2 s2\ \text{s}, with an asymmetric first peak), the star–delta changeover transient, and the drive's smooth ramp at 11–1.5IN1.5I_N. Drive manuals list the supported starting torque; expect ±5 %\pm 5\ \% agreement with the model above for the steady values.

Pitfalls

  • Star–delta on a heavily loaded machine. One third of a single-cage motor's starting torque may not break the load away; the motor then sits at low speed until the changeover, and the changeover current is nearly DOL.
  • Pure V/f at low speed without boost: weak torque, stalling.
  • Running a standard motor slowly for long periods on a drive. Its shaft-mounted fan slows too; derate or add a separately powered fan (Cooling and Insulation).
  • Forgetting the capacitor charge in a drive: wait the time on its warning label and measure before any work, which only qualified people do.

Practice

  1. A delta-wound motor draws 120 A120\ \text{A} and 90 N m90\ \text{N m} when started DOL. Find the star–delta values.
  2. A soft starter holds the voltage at 60 %. What fractions of DOL current and torque result?
  3. A 4-pole motor on a drive runs at 40 Hz40\ \text{Hz} with 30 rpm30\ \text{rpm} slip speed. Find its speed.
Answer
  1. 40 A40\ \text{A}, 30 N m30\ \text{N m}.
  2. Current 0.60.6 of DOL, torque 0.62=0.360.6^2 = 0.36 of DOL.
  3. ns=120⋅40/4=1200 rpmn_s = 120 \cdot 40/4 = 1200\ \text{rpm}, so n=1170 rpmn = 1170\ \text{rpm}.

Test yourself

Star–delta starting reduces the line current and starting torque to…

  1. 1/31/\sqrt{3} and 1/31/3
  2. 1/31/3 and 1/31/3
  3. 1/31/3 and 1/31/\sqrt{3}
  4. 1/21/2 and 1/41/4

An autotransformer starter uses a 70 % tap. The line current at start is…

  1. 70 % of DOL
  2. 49 % of DOL
  3. 84 % of DOL
  4. 35 % of DOL

Why does a V/f drive add a voltage boost at low frequency?

  1. to raise the frequency
  2. to compensate the stator resistance drop, which is large compared with the low voltage
  3. to reduce the current
  4. to cool the motor

Why is speed control by rotor resistance inefficient?

  1. the resistors are expensive
  2. rotor copper loss is sPagsP_{ag}, so at high slip much of the air-gap power becomes heat
  3. it changes the number of poles
  4. it raises the frequency