Starting Methods and Speed Control, Including V/f
Switched straight onto the supply, the example motor draws , more than six times its rated current, for the second or two it takes to run up. A pump motor on a weak rural feeder would dim every light in the village and might trip its own protection. And once running, the motor turns at almost constant speed, while a fan, a conveyor or a machine tool wants to choose its speed. This lesson compares the ways to start an induction motor and the ways to change its speed, ending with the method that has displaced most of the others: the variable-frequency drive with V/f control.
Safety: starters, contactors and drives switch three-phase power and store energy in capacitors. Everything here is calculation and simulation only. A motor that has been switched off can keep coasting for a long time if it drives a flywheel or fan, and while it coasts its residual flux still produces a voltage at the terminals for a short while: never touch terminals or a shaft until the machine is isolated, locked off and stationary.
Starting: why the current is high
At standstill and the rotor branch is just , a few ohms. From the torque–slip curve, the example motor starts with () and . The current itself does the motor little harm for a few seconds, but it causes a voltage dip on the supply, stresses couplings with a torque step, and heats a rotor that has to accelerate a large inertia. All reduced-current methods trade starting torque for current.
| Method | Line current at start | Starting torque | Notes |
|---|---|---|---|
| Direct on line (DOL) | simplest; normal up to a few kW, or larger on a stiff supply | ||
| Star–delta | motor wound for delta at supply voltage, six leads; a current and torque transient at the changeover | ||
| Autotransformer, tap | taps 50–80 %; better torque per line ampere than a resistor | ||
| Soft starter (thyristors) | at voltage | smooth ramp, current limit; for pumps and fans with low starting torque | |
| Variable-frequency drive | about to | up to and more | full torque from standstill; also gives speed control |
Two results need a line of algebra. Star–delta: in star each winding gets instead of , so its current falls by ; and a star line current equals the phase current, while in delta it is times the phase current. Together, . Torque goes with voltage squared: also . Autotransformer: the motor sees and draws on the motor side, which the autotransformer reflects to the line as (Autotransformers).
Worked example: starting the example motor
Given: the example motor (, , , ), wound for delta so that star–delta is possible with the same per-phase (star-equivalent) circuit.
Find: line current and starting torque for star–delta, a 65 % autotransformer, and a soft starter limited to .
Solve:
Check: none of the reduced-voltage methods gives even half the rated torque at standstill with this (single-cage) model. They suit centrifugal pumps and fans, whose load torque near standstill is small, but not a loaded conveyor. A real double-cage or deep-bar motor has about twice this starting torque, which is why star–delta works in practice for many machines.
Interactive: star and delta line currents at standstill (calculation only)
The three-phase lab with the locked-rotor impedance of a delta-wound version of the example motor: per winding . In delta the lab shows a line current of ; switch the connection to star and it falls to , exactly one third (the small difference from is the rounding of the impedance).
Speed control
Speed is , so there are three handles: the poles , the slip , and the frequency .
- Pole changing. A Dahlander winding reconnects to give two speeds in a ratio (for example 1500 and ); separate windings give other ratios. Cheap and efficient, but steps only.
- Slip control. Raising rotor resistance (wound rotor, external resistors) or lowering stator voltage (fans) increases slip. It works, but the rotor copper loss is : at half speed half the air-gap power is turned into heat. Slip-energy recovery schemes and the doubly-fed induction generator recover it with converters.
- Frequency control. A variable-frequency drive (VFD) rectifies the supply and synthesises a new three-phase supply of variable frequency with a PWM inverter (Power Electronics & Motor Drives). Slip stays small at every speed, so efficiency stays high.
V/f control
Changing alone would be wrong: the flux is (Rotating Field), so lowering at constant saturates the core. The drive therefore keeps constant below rated frequency: constant flux, the same torque capability, and a torque–speed curve that simply slides left. Above rated frequency the voltage cannot rise further, flux falls as and the motor runs in the field-weakening region with roughly constant power.
At low frequency pure V/f fails because the stator resistance drop is no longer small compared with : at the example motor's phase voltage is only and of it is lost in . Drives add a boost voltage at low frequency (here per phase at , rising linearly to rated). Vector control and direct torque control go further by regulating flux and torque currents separately (Motor Control).
In Python: starting methods and a V/f family
import numpy as np
from scipy.optimize import brentq
p = 4
R1, X1, Xm, R2, X2 = 0.55, 1.0, 32.0, 0.45, 1.4 # example motor, X at 50 Hz
def motor(s, V, f):
"""Per-phase circuit at supply frequency f: returns (torque N m, stator current A)."""
k = f / 50
Z2 = R2 / s + 1j * X2 * k
Zp = 1j * Xm * k * Z2 / (1j * Xm * k + Z2)
I1 = V / (R1 + 1j * X1 * k + Zp)
I2 = I1 * 1j * Xm * k / (1j * Xm * k + Z2)
ws = 4 * np.pi * f / p
return 3 * abs(I2) ** 2 * R2 / s / ws, abs(I1)
V_N = 400 / np.sqrt(3)
T0, I0 = motor(1.0, V_N, 50)
print(f"starting method line current starting torque")
print(f"direct on line {I0:6.1f} A {T0:5.1f} N m")
print(f"star-delta {I0/3:6.1f} A {T0/3:5.1f} N m")
x = 0.65
print(f"autotransformer, 65 % tap {I0*x**2:6.1f} A {T0*x**2:5.1f} N m")
k = 3 * 14.43 / I0 # soft starter limited to 3 x rated current
print(f"soft starter at {k*100:.0f} % voltage {I0*k:6.1f} A {T0*k**2:5.1f} N m")
print("\n f (Hz) V boost (V) n_s (rpm) T_max pure V/f T_max boosted speed and current at 50.35 N m")
V_b = 12.0 # boost voltage per phase at 0 Hz
for f in (50, 35, 20, 10, 5):
V_pure = V_N * f / 50
V_boost = V_b + (V_N - V_b) * f / 50
s_grid = np.linspace(1e-3, 1, 4000)
Tmax_pure = max(motor(s, V_pure, f)[0] for s in s_grid)
Tmax_boost = max(motor(s, V_boost, f)[0] for s in s_grid)
s_op = brentq(lambda s: motor(s, V_boost, f)[0] - 50.35, 1e-4, 0.5)
ns = 120 * f / p
print(f"{f:5.0f} {V_boost:8.1f} {ns:7.0f} {Tmax_pure:8.1f} {Tmax_boost:8.1f}"
f" {ns*(1-s_op):6.0f} rpm, {motor(s_op, V_boost, f)[1]:5.2f} A")starting method line current starting torque
direct on line 91.0 A 65.4 N m
star-delta 30.3 A 21.8 N m
autotransformer, 65 % tap 38.5 A 27.6 N m
soft starter at 48 % voltage 43.3 A 14.8 N m
f (Hz) V boost (V) n_s (rpm) T_max pure V/f T_max boosted speed and current at 50.35 N m
50 230.9 1500 162.2 162.2 1462 rpm, 14.43 A
35 165.3 1050 147.8 154.5 1013 rpm, 14.34 A
20 99.6 600 118.4 137.6 565 rpm, 14.13 A
10 55.8 300 76.6 111.7 269 rpm, 13.70 A
5 33.9 150 42.4 91.2 126 rpm, 13.19 A
With the boost the motor carries its full rated torque at () on slightly less than rated current; with pure V/f its maximum torque there () is below the rated load and it would stall. Note also that the slip speed at rated torque stays near – at every frequency: that is why V/f control is efficient.
Guided lab (simulation and datasheet)
Hand calculation. For an autotransformer tap of 80 %, compute the line current and torque at start.
Simulation. Change V_b in the code to 0 and to 20 and see how the low-speed torque changes; too much boost over-fluxes the motor at light load (watch the current at 5 Hz).
What you would measure. In a qualified lab or on commissioning (not a learner experiment: mains voltages and stored energy in the drive's DC-link capacitors, which stay charged for minutes after switch-off): a clamp meter and a power-quality recorder show the DOL inrush (6–8 for –, with an asymmetric first peak), the star–delta changeover transient, and the drive's smooth ramp at –. Drive manuals list the supported starting torque; expect agreement with the model above for the steady values.
Pitfalls
- Star–delta on a heavily loaded machine. One third of a single-cage motor's starting torque may not break the load away; the motor then sits at low speed until the changeover, and the changeover current is nearly DOL.
- Pure V/f at low speed without boost: weak torque, stalling.
- Running a standard motor slowly for long periods on a drive. Its shaft-mounted fan slows too; derate or add a separately powered fan (Cooling and Insulation).
- Forgetting the capacitor charge in a drive: wait the time on its warning label and measure before any work, which only qualified people do.
Practice
- A delta-wound motor draws and when started DOL. Find the star–delta values.
- A soft starter holds the voltage at 60 %. What fractions of DOL current and torque result?
- A 4-pole motor on a drive runs at with slip speed. Find its speed.
Answer
- , .
- Current of DOL, torque of DOL.
- , so .
Test yourself
Star–delta starting reduces the line current and starting torque to…
- and
- and
- and
- and
An autotransformer starter uses a 70 % tap. The line current at start is…
- 70 % of DOL
- 49 % of DOL
- 84 % of DOL
- 35 % of DOL
Why does a V/f drive add a voltage boost at low frequency?
- to raise the frequency
- to compensate the stator resistance drop, which is large compared with the low voltage
- to reduce the current
- to cool the motor
Why is speed control by rotor resistance inefficient?
- the resistors are expensive
- rotor copper loss is , so at high slip much of the air-gap power becomes heat
- it changes the number of poles
- it raises the frequency