Electrical Machines & Transformers: Introduction
More than 40 % of the world's electricity is used by electric motors and the systems they drive (an IEA estimate published in 2011), and most of it was produced by synchronous generators and passed through several transformers on the way. A pump, a lift, an electric car, a wind turbine and the grid substation down the road all rest on one physical idea, a magnetic field that couples an electric circuit to motion or to another circuit, and on a handful of machine types that put it to work. This course builds each of them from that idea to a working model: an equivalent circuit you can calculate with, a torque–speed curve you can match to a load, and the tests, ratings and efficiency rules that decide what you can buy.
Safety rule for the whole course. Transformers on the mains, three-phase motors and generators, their starters and their tests (open-circuit, short-circuit, no-load, locked-rotor) work at voltages and energies that can kill, and are taught here by calculation and simulation only, in Python and ngspice. The hands-on labs use only small low-voltage DC motors, stepper motors and brushless fans powered from a current-limited bench supply of 24 V or less, hand-cranked generators, and signal-level transformers driven from a function generator. Rotating parts catch fingers, hair and loose clothing: clamp every motor to the bench, and remember that a spinning motor is a generator, a stopped one with a flywheel may not stay stopped, and an inductive winding kicks when its current is interrupted.
The map
| Section | You will be able to | Labs and tools |
|---|---|---|
| Getting started | find the force and torque of any device from field energy and co-energy; explain why each machine family runs at the speed it does | figures, SymPy, NumPy |
| Magnetics for machines | read B–H curves, predict magnetising current and its harmonics, model hysteresis and eddy losses with Steinmetz | Python |
| Transformers | build and test the equivalent circuit, compute regulation, efficiency and all-day efficiency, work in per unit, choose autotransformers and instrument transformers, read vector groups, parallel units, predict inrush | ee-netlist, ee-three-phase, ee-rc-rl-transient, ngspice |
| DC machines | use the EMF and torque equations, handle armature reaction and commutation, predict generator and motor characteristics, start, control and brake a DC motor, find its efficiency | ee-netlist, ee-rc-rl-transient, force-on-wire, solve_ivp, ngspice |
| Induction machines | explain the rotating field and slip, solve the equivalent circuit, plot torque–slip curves, extract parameters from tests, choose a starting method and V/f control, handle single-phase motors and induction generators | ee-three-phase, ee-netlist, ee-phasor-diagram |
| Synchronous machines | find synchronous reactance from tests, draw phasor diagrams, use the power-angle curve and V-curves, synchronise to an infinite bus | ee-netlist, Python |
| Special machines | explain BLDC, PMSM, stepper, switched-reluctance, universal and linear motors | Python, ee-rc-rl-transient |
| Ratings, efficiency and testing | read a nameplate, duty types, IE efficiency classes, cooling and insulation classes; plan tests and maintenance | ee-three-phase, Python |
Circuit ideas (phasors, three-phase, mutual inductance, the ideal transformer) come from Circuit Theory, in particular Three-Phase Circuits and Ideal Transformers. Field ideas (magnetic circuits, Faraday's law, forces on currents) come from Electromagnetic Theory. Power and energy measurement is in Power Measurement, and the DC motor as a control plant in Control Systems. Motor drives and inverters continue in Power Electronics & Motor Drives, and generators on the grid in Power Systems.
Motor action and generator action
Every machine in this course is reversible. Current in a conductor in a field feels a force, for a wire at right angles to the field: that is motor action. A conductor moving through a field has an EMF induced in it, : that is generator action. Both happen at once in every running machine. A motor's turning rotor induces a back-EMF that opposes the supply; a generator's load current creates a torque that opposes the prime mover. The two labs below show the halves separately.
The force lab shows a wire carrying at right angles to a field: , upward by Fleming's left-hand rule. Sweep the angle and the force follows , the same sine that sets the torque of every machine when the angle between two fields changes (Doubly Excited Systems).
The induction lab moves a magnet in and out of a coil and shows the EMF : generator action, and with a closed circuit a current whose field opposes the motion (Lenz's law), which is the braking torque a generator's load puts on its prime mover.
The machine families
| Machine | Stator | Rotor | Speed | Where you meet it |
|---|---|---|---|---|
| transformer | two or more windings on one core | none | none: it converts voltage and current at one frequency | every grid and power supply |
| DC machine | field poles (wound or magnets) | armature with commutator | set by voltage and field, any speed | small drives, toys, legacy traction, automotive auxiliaries |
| induction machine | three-phase (or single-phase) winding | squirrel cage or wound | a little below synchronous speed (slip) | pumps, fans, compressors, conveyors: most industrial motors |
| synchronous machine | three-phase winding | DC field winding or magnets | exactly synchronous | power-station generators, large motors, PMSM drives |
| special machines | various | magnets, toothed iron, commutator | electronically controlled | BLDC fans, steppers, SR drives, universal tools |
Synchronous speed, the speed of the rotating field of an AC machine, is for poles: , and for 2, 4 and 6 poles at .
Conventions in this course
| Quantity | Symbol |
|---|---|
| phasor (rms) | bold, , ; magnitude , |
| number of poles | (so pole pairs); synchronous speed rpm, rad/s |
| mechanical speed | (rpm), (rad/s); slip |
| turns ratio | (HV over LV for transformers) |
| referred quantity | primed, |
| per-unit value | lower case, , , |
| AC machine values | per phase of the star equivalent unless stated |
The course's running examples are a single-phase , transformer T1, a , , four-pole induction motor, a shunt DC motor, a permanent-magnet motor (the only one you can test yourself) and a , synchronous generator.
Worked example: reading a motor nameplate
Given: a three-phase motor nameplate: , star, , , efficiency , power factor .
Find: the number of poles, the slip, the input power, the line current, the losses and the rated torque.
Solve: is just below , so and . The rated power is the shaft output:
Check: about per kilowatt at is the usual rule of thumb for motors of this size. The induction-machine lessons derive these same numbers from the motor's equivalent circuit (Slip and the Equivalent Circuit).
import numpy as np
P_out, V_L, f, n, eta, pf = 7500.0, 400.0, 50.0, 1462.0, 0.907, 0.826
poles = int(round(120 * f / n / 2) * 2) # nearest even pole number above the running speed
n_s = 120 * f / poles
s = (n_s - n) / n_s
P_in = P_out / eta
I_L = P_in / (np.sqrt(3) * V_L * pf)
T = P_out / (n * 2 * np.pi / 60)
Q = P_in * np.tan(np.arccos(pf))
print(f"poles {poles}, synchronous {n_s:.0f} rpm, slip {s:.4f}")
print(f"input {P_in:.0f} W, losses {P_in - P_out:.0f} W, reactive {Q:.0f} var")
print(f"line current {I_L:.2f} A, rated torque {T:.1f} N m")poles 4, synchronous 1500 rpm, slip 0.0253
input 8269 W, losses 769 W, reactive 5643 var
line current 14.45 A, rated torque 49.0 N m
The motor also draws of reactive power to magnetise its air gap, which is why induction-motor plants install power-factor correction.
Guided lab: one small motor, two ways
Hand calculation. A permanent-magnet DC motor has one constant : back-EMF (V per rad/s) and torque (N·m per A), the same number in SI units (DC Machines). If a small motor runs at about () with no load, , ignoring the small no-load current drop.
Simulation. Write and in Python with your motor's values and predict the no-load speed at , and .
What you would measure. (1) As a generator: couple the shaft to a second, identical motor (a short piece of silicone tube), drive that one from the bench supply, and read the open-circuit voltage of the first with a DMM while measuring the speed with an optical tachometer or a phone app counting a reflective mark. gives . (2) As a motor: run the first motor alone at , and and measure no-load speed and current. Both methods should give within about 5 to 10 %; brush drop, friction and the tachometer's account for the difference.
Hazards and safe setup. Bench supply set to or less with a current limit of about . Clamp both motors, keep fingers, hair and loose cables clear of the coupling, and wear eye protection: a coupling tube can fly off at high speed. Don't hold a motor shaft to stall it; the stall current is many times the no-load current and the winding overheats in seconds.
Pitfalls
- Nameplate power is output. For a motor it is shaft power; for a generator it is electrical output; for a transformer it is apparent power (kVA).
- Line and phase. Three-phase nameplates give line voltage and line current.
- Poles and pole pairs. This course uses for the number of poles; some books use it for pole pairs.
- Testing mains machines yourself. Don't. Every such test here is a calculation or a simulation.
Practice
- A six-pole, motor runs at . What are its synchronous speed and slip?
- A , motor with and pf : find its line current.
- A motor delivers at . What torque would a motor of the same power deliver, and what does that suggest about its size?
Answer
- , .
- .
- ; since torque sets the rotor volume, the slower motor is larger and heavier for the same power.
Test yourself
What does the rated power on an induction motor's nameplate refer to?
- electrical input power
- apparent power in kVA
- mechanical output power at the shaft
- the air-gap power
The synchronous speed of a 4-pole machine on a 50 Hz supply is…
- 3000 rpm
- 1500 rpm
- 1000 rpm
- 750 rpm
In a running motor, the EMF induced in its own windings by the rotation…
- adds to the supply voltage
- opposes the supply voltage (back-EMF)
- is zero
- only exists in generators
Which hands-on work does this course allow?
- open-circuit tests on a mains transformer
- starting a three-phase motor star-delta
- small low-voltage DC, stepper and BLDC motors from a current-limited supply of 24 V or less
- locked-rotor tests on any motor under 1 kW