Single-Phase Induction Motors and Induction Generators
Most homes have no three-phase supply, yet washing machines, refrigerator compressors, garden pumps, desk fans and bench grinders all use induction motors. A single winding on a single-phase supply makes only a pulsating field, which cannot start a rotor. This lesson explains why such a motor nevertheless runs once it is turning, and the tricks (an auxiliary winding, a capacitor, a shaded pole) that get it started. The second half turns the machine around: drive an induction machine above synchronous speed and it becomes a generator, the workhorse of early wind farms and of many small hydro plants.
Safety: single-phase motors run from mains and induction generators feed the grid; both are calculation and simulation only here. Motor-run capacitors keep a charge after switch-off, and a self-excited induction generator can produce dangerous voltage with no grid connected at all.
The double-revolving-field idea
A pulsating MMF is the sum of two half-amplitude waves turning in opposite directions:
A rotor turning forward at slip relative to the forward field has slip relative to the backward one. Each field produces its own torque–slip curve, in opposite directions. At standstill () the two slips are equal, the torques cancel and there is no starting torque. Once the rotor turns forward the forward torque dominates, so the motor runs (in either direction, depending on which way it was pushed). The equivalent circuit puts two half-size magnetising-and-rotor branches in series, one with , one with :
The backward field costs torque and losses even at running speed, which is one reason single-phase motors are less efficient and noisier (a torque pulsation at ) than three-phase motors of the same size.
Starting methods
To start, the motor needs a second winding displaced electrical in space, the auxiliary (start) winding, carrying a current displaced in time from the main winding current. Two windings in quadrature with currents near quadrature make a (roughly) rotating field.
| Type | How the phase shift is made | Starting torque | Typical use |
|---|---|---|---|
| Split-phase | auxiliary winding of thin wire: higher , current lags less; switched out at 70–80 % speed | moderate, high current | small fans, older washers |
| Capacitor-start | electrolytic start capacitor in the auxiliary branch makes its current lead; switched out | high (2–3 ) | compressors, pumps, workshop machines |
| Permanent split capacitor (capacitor-run) | small film capacitor stays in circuit | low | fans, blowers, air handlers; quiet, better pf and efficiency |
| Capacitor-start, capacitor-run | large start and small run capacitor | high | larger single-phase motors up to a few kW |
| Shaded pole | a copper ring around part of each pole delays the flux under it | very low | small fans, under about ; low efficiency, often well under 40 % |
The centrifugal switch (or an electronic relay) matters: the start capacitor and the thin auxiliary winding are rated only for a few seconds of current. A motor that fails to reach switch-out speed burns its start winding.
Interactive: the two winding currents at standstill
The phasor lab draws one branch at a time. Take a small capacitor motor's windings at standstill, scaled to (the angles do not depend on voltage). The main winding (, ) draws a current lagging by :
The auxiliary winding (, ) in series with draws a current leading by . The two currents are apart: almost a perfect two-phase set. Change and watch the phase.
Worked example: a 0.75 kW single-phase motor
Given: , , 4 poles; main-winding circuit , , , , ; rotational loss ; running on the main winding at .
Find: speed, current, power factor, torque, output and efficiency.
Solve: . With and :
Check: the output is the rated ; 77 % is typical of a single-phase motor this size (a three-phase IE3 motor of reaches about 82 %). The backward field takes of air-gap power the wrong way.
In Python: torque against speed on one winding
import numpy as np
V, f, p = 230.0, 50, 4
ws = 4 * np.pi * f / p
R1, X1, Xm, R2, X2 = 2.4, 3.0, 100.0, 4.5, 3.0 # main winding, rotor referred to it (ohm)
P_rot = 25.0 # friction, windage, core (W)
def half(Rr): # half of the magnetising and rotor branch
Zr = Rr + 1j * X2
return 0.5 * (1j * Xm * Zr) / (1j * Xm + Zr)
def run(s):
ZF, ZB = half(R2 / s), half(R2 / (2 - s))
I = V / (R1 + 1j * X1 + ZF + ZB)
PF, PB = abs(I)**2 * ZF.real, abs(I)**2 * ZB.real # air-gap powers of the two fields
T = (PF - PB) / ws
P_out = T * ws * (1 - s) - P_rot
return abs(I), np.cos(np.angle(I)), T, P_out
print(" s n (rpm) I (A) pf T (N m) P_out (W)")
for s in (1.0, 0.5, 0.2, 0.1, 0.06, 0.05, 0.04):
I, pf, T, P = run(s)
print(f"{s:5.2f} {1500*(1-s):7.0f} {I:6.2f} {pf:5.3f} {T:7.3f} {P:8.1f}") s n (rpm) I (A) pf T (N m) P_out (W)
1.00 0 25.53 0.736 0.000 -25.0
0.50 750 22.52 0.785 9.029 684.1
0.20 1200 14.43 0.859 11.853 1464.5
0.10 1350 9.07 0.841 8.744 1211.1
0.06 1410 6.57 0.760 6.050 868.3
0.05 1425 5.97 0.715 5.208 752.2
0.04 1440 5.40 0.650 4.294 622.6
At standstill the torque is exactly zero while the current is highest: without the auxiliary winding the motor just hums and heats. Pushed to any speed, it accelerates.
Induction generators
Drive the rotor faster than and the slip goes negative. Then : the "load resistor" becomes a source, , and power flows from the shaft through the air gap into the stator and the grid. The machine still needs its magnetising current, so it takes reactive power while it delivers real power.
import numpy as np
V = 400 / np.sqrt(3); ws = 4 * np.pi * 50 / 4
R1, X1, Xm, R2, X2 = 0.55, 1.0, 32.0, 0.45, 1.4 # the example 7.5 kW motor
P_rot = 220.0
print(" s n (rpm) shaft in (W) to grid P (W) from grid Q (var) efficiency")
for s in (-0.01, -0.0255, -0.04):
Z2 = R2 / s + 1j * X2
I1 = V / (R1 + 1j * X1 + 1j * Xm * Z2 / (1j * Xm + Z2))
I2 = I1 * 1j * Xm / (1j * Xm + Z2)
S = 3 * V * np.conj(I1) # power taken from the grid (motor convention)
P_ag = 3 * abs(I2)**2 * R2 / s # negative: power flows from rotor to stator
P_shaft = -(1 - s) * P_ag + P_rot # mechanical power that must be supplied
print(f"{s:7.4f} {1500*(1-s):7.1f} {P_shaft:10.0f} {-S.real:12.0f} {S.imag:14.0f} {-S.real/P_shaft*100:5.1f} %")
Xc = X1 + Xm # no-load self-excitation: capacitor cancels X1 + Xm
C = 1 / (2 * np.pi * 50 * Xc)
print(f"self-excitation at no load: about {C*1e6:.0f} uF per phase (star), {3*V**2/Xc/1e3:.2f} kvar in total") s n (rpm) shaft in (W) to grid P (W) from grid Q (var) efficiency
-0.0100 1515.0 3665 3283 5140 89.6 %
-0.0255 1538.3 9321 8489 6330 91.1 %
-0.0400 1560.0 14781 13171 8251 89.1 %
self-excitation at no load: about 96 uF per phase (star), 4.85 kvar in total
At () the example motor delivers to the grid while drawing from it. Real power output rises steeply with speed, so a cage generator on the grid runs at nearly constant speed, just above synchronous. That made it the simple, robust choice for the fixed-speed "Danish concept" wind turbines of the 1980s–90s, with capacitor banks for power-factor correction. Most modern turbines use a doubly-fed induction generator (rotor fed through a converter) or a synchronous machine behind a full converter (Power Systems, Power Electronics).
Self-excitation. Without a grid, capacitors across the terminals can supply the magnetising current. Residual magnetism starts a small voltage; the capacitor current builds the flux up until the magnetising curve saturates and the voltage settles where the capacitor line meets it (the same build-up as a DC shunt generator). At no load the example machine needs roughly per phase; under load it needs more, and the voltage and frequency both drift with load and speed. Self-excitation is also a hazard: a motor with power-factor capacitors that is disconnected while coasting can self-excite and hold its terminals at a high voltage for a while.
Guided lab (simulation and low-voltage demonstration)
Hand calculation. Repeat the worked example at and compare with the code's table.
Simulation. In the auxiliary-winding lab, find the capacitance that puts the two currents exactly apart.
What you would measure. Single-phase mains motors and grid-connected generators are not learner experiments. A safe analogue of generator action uses a hand-cranked or drill-driven small DC motor (12 V permanent-magnet type) as a generator into a resistor, with a meter: the output rises in proportion to speed, and the crank gets harder to turn as the load resistance falls, energy conservation you can feel. Expect a few volts at a few hundred rpm (read the motor's speed constant from its datasheet, ). Keep fingers and hair clear of the rotating shaft and coupling, secure the motor in a clamp, and never connect a "generator" to a battery or supply.
Pitfalls
- Assuming a single-phase motor has some starting torque. On the main winding alone it has none; a failed start capacitor or switch leaves it humming and overheating.
- Using an electrolytic start capacitor as a run capacitor. It is rated for seconds of duty; run capacitors are film types.
- Forgetting reactive power in generators. An induction generator always absorbs reactive power; the grid or capacitors must supply it.
- Islanding. A self-excited generator can keep a disconnected network live, a danger to line workers; grid codes require protection against it.
Practice
- A single-phase rotor runs at . What is its slip relative to the backward field?
- In the worked example, how much does the backward field reduce the torque, in N m?
- The example machine generates at . From the table, what are its output and reactive power demand?
Answer
- .
- (about 5 % of the forward torque).
- About to the grid, taking (and needing at the shaft).
Test yourself
Why has a single-winding single-phase induction motor no starting torque?
- its rotor is too heavy
- at standstill the forward and backward fields produce equal and opposite torques
- the supply is DC at start
- the slip is zero
In a capacitor-start motor the capacitor is in series with…
- the main winding
- the auxiliary winding
- the rotor
- the supply fuse only
An induction machine connected to the grid runs at 1530 rpm (4 poles, 50 Hz). It…
- motors with s = 0.02
- generates with s = −0.02
- brakes with s = 1.02
- runs synchronously
What does an induction generator need from the grid (or capacitors) even while it delivers real power?
- DC excitation current
- reactive power for magnetisation
- nothing
- a starting capacitor