Home › Electrical Machines & Transformers › Slip and the Induction-Motor Equivalent Circuit

Slip and the Induction-Motor Equivalent Circuit

The nameplate of a 4-pole, 50 Hz50\ \text{Hz} motor says 1462 rpm1462\ \text{rpm}, not 15001500. Those missing 38 rpm38\ \text{rpm} are not a defect: they are how the motor works. A rotor turning exactly with the rotating field would see no change of flux, so no EMF, no rotor current and no torque. The rotor has to slip behind the field. This lesson turns that idea into a per-phase circuit, almost the same as the transformer equivalent circuit, with one new element, R2′/sR_2'/s, that carries the mechanical output. With it you can predict current, power factor, losses, torque and efficiency at any speed from six numbers.

Safety: the example motor is a 400 V400\ \text{V} three-phase machine. Everything in this lesson is calculation and simulation only.

Slip and rotor frequency

The rotor turns at nn while the field turns at ns=120f/pn_s = 120f/p. The slip is the relative speed difference

s=ns−nns,n=(1−s) nss = \frac{n_s - n}{n_s}, \qquad n = (1 - s)\,n_s

s=1s = 1 at standstill, s≈0s \approx 0 at no load, and 0.01–0.05 at full load for motors of a few kilowatts and more. The rotor conductors are cut by the field at the slip speed ns−n=s nsn_s - n = s\,n_s, so the rotor voltages and currents have the slip frequency

fr=sff_r = s f

At standstill the rotor is a transformer secondary at 50 Hz50\ \text{Hz}; at full load its currents alternate only once or twice a second.

From rotor circuit to equivalent circuit

Let E2E_2 be the rotor EMF per phase at standstill. At slip ss the EMF is sE2sE_2 (the flux is cut ss times as fast) and the rotor leakage reactance is sX2sX_2 (frequency sfsf). The rotor current is

I2=sE2R2+jsX2=E2R2/s+jX2\mathbf{I}_2 = \frac{s\mathbf{E}_2}{R_2 + jsX_2} = \frac{\mathbf{E}_2}{R_2/s + jX_2}

Dividing top and bottom by ss changes nothing about I2\mathbf{I}_2, but the right-hand form is a circuit at supply frequency with a fixed reactance X2X_2 and a resistance R2/sR_2/s that depends on speed. Referring it to the stator turns (primes, as for a transformer) gives the standard per-phase circuit, used here with star-equivalent phase values.

+V1230.9 V R1 = 0.55 jX1 = j1.0 jXm = j32 jX2' = j1.4 R2' = 0.45 R2'(1-s)/s= P_mech I1 Im I2' air gap: P_ag crosses here stator (values in Ohm per phase)rotor (referred)

A core-loss resistance RcR_c can sit in parallel with XmX_m, as in a transformer. For a motor it is usually left out and the core loss is lumped with friction and windage into one rotational loss ProtP_\text{rot}, which hardly changes from no load to full load. Compared with a transformer, the air gap makes XmX_m small (a few tens of ohms rather than thousands), so the magnetising current is large: 30–50 % of rated current. That is why induction motors run at a lagging power factor even at no load.

Power flow and torque

The trick that makes the circuit useful is to split the rotor resistance:

R2′s=R2′+R2′ 1−ss\frac{R_2'}{s} = R_2' + R_2'\,\frac{1 - s}{s}

The first part burns the rotor copper loss; the second is a fictitious resistance whose power is the mechanical power developed. Per machine (three phases):

Pag=3I2′2R2′sair-gap power, crosses to the rotorPcu2=3I2′2R2′=sPagrotor copper lossPmech=(1−s)Pag,Pout=Pmech−ProtTind=Pmechω=Pagωs,ωs=4πfp\begin{aligned} P_\text{ag} &= 3 I_2'^2 \frac{R_2'}{s} && \text{air-gap power, crosses to the rotor} \\ P_\text{cu2} &= 3 I_2'^2 R_2' = s P_\text{ag} && \text{rotor copper loss} \\ P_\text{mech} &= (1 - s) P_\text{ag}, \qquad P_\text{out} = P_\text{mech} - P_\text{rot} \\ T_\text{ind} &= \frac{P_\text{mech}}{\omega} = \frac{P_\text{ag}}{\omega_s}, \qquad \omega_s = \frac{4\pi f}{p} \end{aligned}

The split Pcu2:Pmech=s:(1−s)P_\text{cu2} : P_\text{mech} = s : (1 - s) is the most important number in the section: a rotor running at slip ss wastes the fraction ss of the air-gap power as heat. That is why induction motors run at small slip, and why slowing one by raising slip (rotor resistance, low voltage) is inefficient (Starting Methods and Speed Control).

The course's example motor

These parameters are used in all the induction-machine lessons. They describe a typical 7.5 kW7.5\ \text{kW} general-purpose cage motor (illustrative values, not a particular product):

Rating Value Per-phase parameter (star, referred to stator) Value
line voltage, frequency 400 V400\ \text{V}, 50 Hz50\ \text{Hz} R1R_1 0.55 Ω0.55\ \Omega
poles, connection 4, star X1X_1 1.0 Ω1.0\ \Omega
rated output 7.5 kW7.5\ \text{kW} XmX_m 32 Ω32\ \Omega
synchronous speed 1500 rpm1500\ \text{rpm} R2′R_2' 0.45 Ω0.45\ \Omega
rotational loss ProtP_\text{rot} 220 W220\ \text{W} X2′X_2' 1.4 Ω1.4\ \Omega

Worked example: the full-load operating point

Given: the example motor at s=0.0255s = 0.0255, phase voltage V1=400/3=230.9 VV_1 = 400/\sqrt{3} = 230.9\ \text{V}.

Find: speed, input current and power factor, the power flow, efficiency and torque.

Solve: speed n=(1−0.0255)⋅1500=1461.8 rpmn = (1 - 0.0255) \cdot 1500 = 1461.8\ \text{rpm}. The rotor branch is Z2=0.45/0.0255+j1.4=17.65+j1.4 ΩZ_2 = 0.45/0.0255 + j1.4 = 17.65 + j1.4\ \Omega; in parallel with j32 Ωj32\ \Omega it gives Zp=12.66+j8.03 ΩZ_p = 12.66 + j8.03\ \Omega; adding the stator,

Zin=0.55+j1.0+12.66+j8.03=13.21+j9.03 Ω=16.01 Ω∠34.4∘I1=230.9 V16.01 Ω=14.43 A,pf=cos⁡34.4∘=0.826 laggingPag=7909 W,Pcu2=0.0255⋅7909 W=202 W,Pmech=7707 WPout=7707 W−220 W=7487 W,η=7487 W8253 W=90.7 %Tind=7909 W157.08 rad/s=50.35 N m,Tshaft=7487 W153.07 rad/s=48.91 N m\begin{aligned} Z_\text{in} &= 0.55 + j1.0 + 12.66 + j8.03 = 13.21 + j9.03\ \Omega = 16.01\ \Omega \angle 34.4^\circ \\ I_1 &= \frac{230.9\ \text{V}}{16.01\ \Omega} = 14.43\ \text{A}, \quad \text{pf} = \cos 34.4^\circ = 0.826\ \text{lagging} \\ P_\text{ag} &= 7909\ \text{W}, \quad P_\text{cu2} = 0.0255 \cdot 7909\ \text{W} = 202\ \text{W}, \quad P_\text{mech} = 7707\ \text{W} \\ P_\text{out} &= 7707\ \text{W} - 220\ \text{W} = 7487\ \text{W}, \quad \eta = \frac{7487\ \text{W}}{8253\ \text{W}} = 90.7\ \% \\ T_\text{ind} &= \frac{7909\ \text{W}}{157.08\ \text{rad/s}} = 50.35\ \text{N m}, \quad T_\text{shaft} = \frac{7487\ \text{W}}{153.07\ \text{rad/s}} = 48.91\ \text{N m} \end{aligned}

The air-gap power comes from I2′=12.22 AI_2' = 12.22\ \text{A} (current divider between j32j32 and Z2Z_2): 3⋅12.222⋅17.65=7909 W3 \cdot 12.22^2 \cdot 17.65 = 7909\ \text{W}.

Check: 7.49 kW7.49\ \text{kW} is the rated 7.5 kW7.5\ \text{kW} to within 0.2 %, so s=0.0255s = 0.0255 is the rated slip. The efficiency matches what the IE3 class requires of a 4-pole 7.5 kW7.5\ \text{kW} motor (about 90 %, Ratings and IE Classes), and 14.4 A14.4\ \text{A} is a typical nameplate current for this size at 400 V400\ \text{V}.

In Python: the operating point and power flow

python · try it yourself
import numpy as np
V = 400 / np.sqrt(3)                     # star-equivalent phase voltage (V)
f, p = 50, 4
ns = 120 * f / p                         # rpm
ws = 4 * np.pi * f / p                   # rad/s
R1, X1, Xm, R2, X2 = 0.55, 1.0, 32.0, 0.45, 1.4   # ohm per phase, referred to the stator
P_rot = 220.0                            # friction, windage and core loss (W), taken as constant

s = 0.0255
Z2 = R2 / s + 1j * X2
Zin = R1 + 1j * X1 + (1j * Xm * Z2) / (1j * Xm + Z2)
I1 = V / Zin
I2 = I1 * (1j * Xm) / (1j * Xm + Z2)     # current divider
P_in = 3 * (V * np.conj(I1)).real
P_cu1 = 3 * abs(I1) ** 2 * R1
P_ag = 3 * abs(I2) ** 2 * R2 / s
P_cu2 = s * P_ag
P_mech = (1 - s) * P_ag
P_out = P_mech - P_rot
n = ns * (1 - s)
w = 2 * np.pi * n / 60
print(f"Zin = {abs(Zin):.2f} ohm at {np.degrees(np.angle(Zin)):.1f} deg")
print(f"speed n = {n:.1f} rpm, rotor frequency s*f = {s*f:.3f} Hz")
print(f"I1 = {abs(I1):.2f} A at {np.degrees(np.angle(I1)):.1f} deg, pf = {np.cos(np.angle(I1)):.3f} lagging, I2' = {abs(I2):.2f} A")
for name, val in [("input P_in", P_in), ("stator copper", P_cu1), ("air-gap P_ag", P_ag),
                  ("rotor copper s*P_ag", P_cu2), ("mechanical (1-s)P_ag", P_mech),
                  ("rotational loss", P_rot), ("output P_out", P_out)]:
    print(f"  {name:22s} {val:8.1f} W")
print(f"efficiency {P_out / P_in * 100:.1f} %")
print(f"torque: induced P_ag/ws = {P_ag / ws:.2f} N m, shaft P_out/w = {P_out / w:.2f} N m")
Zin = 16.01 ohm at 34.4 deg
speed n = 1461.8 rpm, rotor frequency s*f = 1.275 Hz
I1 = 14.43 A at -34.4 deg, pf = 0.826 lagging, I2' = 12.22 A
  input P_in               8252.7 W
  stator copper             343.5 W
  air-gap P_ag             7909.2 W
  rotor copper s*P_ag       201.7 W
  mechanical (1-s)P_ag     7707.5 W
  rotational loss           220.0 W
  output P_out             7487.5 W
efficiency 90.7 %
torque: induced P_ag/ws = 50.35 N m, shaft P_out/w = 48.91 N m

The power balance closes: 8252.7−343.5=7909.28252.7 - 343.5 = 7909.2 crosses the gap, and 7909.2−201.7−220.0=7487.57909.2 - 201.7 - 220.0 = 7487.5 leaves on the shaft.

Interactive: one phase of the motor as a netlist

The netlist lab solves the same circuit at 50 Hz50\ \text{Hz} (inductances L=X/ωL = X/\omega: 3.1833.183, 101.9101.9 and 4.456 mH4.456\ \text{mH}). The resistor RR is R2′/sR_2'/s; its slider runs from 0.45 Ω0.45\ \Omega (standstill, s=1s = 1) to 45 Ω45\ \Omega (s=0.01s = 0.01). At the default 17.65 Ω17.65\ \Omega (rated slip) the lab shows I1=14.42 AI_1 = 14.42\ \text{A} at −34.3∘-34.3^\circ, a magnetising current of 6.758 A6.758\ \text{A} and I2′=12.22 AI_2' = 12.22\ \text{A}, matching the code to rounding of the inductances. Drag RR down to 0.45 Ω0.45\ \Omega to see the starting current. Read only the values at the 50 Hz50\ \text{Hz} cursor: the lab also sweeps frequency, but a real motor's R2′/sR_2'/s and XX values change with frequency, so the rest of that plot has no meaning here.

0100200100m1101001k10kf (Hz)|V| (V)0 A5.0 A10 A|I| (A)|V(c)||I(RR)|phasors at f = 50.00 Hz (magnitude @ phase)V(a)231 V @ 0.0 degV(b)224 V @ 1.1 degV(c)216 V @ -2.0 degV(d)216 V @ -6.5 degI(V1)14.4 A @ 145.7 degI(R1)14.4 A @ -34.3 degI(L1)14.4 A @ -34.3 degI(LM)6.76 A @ -92.0 degI(L2)12.2 A @ -6.5 degI(RR)12.2 A @ -6.5 deg

Guided lab (simulation and datasheet)

Hand calculation. Repeat the worked example at s=0.04s = 0.04 (R2′/s=11.25 ΩR_2'/s = 11.25\ \Omega) and at s=1s = 1.

Simulation. Set RR in the lab to those values; the code above with s = 0.04 or s = 1 gives the power flow.

What you would measure. On a qualified motor test bed (not a learner experiment: 400 V400\ \text{V} three-phase), a dynamometer loads the motor while a power analyser records VV, II, PP and pf and a tachometer the speed. For this motor you would expect at rated load about 1460 rpm1460\ \text{rpm} (±5 rpm\pm 5\ \text{rpm}; slip also rises a little as the rotor warms, because R2′R_2' grows with temperature), 14.4 A14.4\ \text{A} (±2 %\pm 2\ \% with a class 0.5 analyser) and pf about 0.83. A manufacturer's datasheet lists the same quantities at 50, 75 and 100 % load, which is how you check a model against a real motor.

Pitfalls

  • Using line voltage in a per-phase circuit. The circuit is per phase, star equivalent: 230.9 V230.9\ \text{V}, and total powers are three times the phase values.
  • Forgetting that Pag/ωsP_\text{ag}/\omega_s is the induced torque, not Pout/ωsP_\text{out}/\omega_s. The shaft torque is Pout/ωP_\text{out}/\omega.
  • Rounding complex numbers early. Keep full precision until the end; the parallel combination of XmX_m and the rotor branch is sensitive to it.
  • Treating R2′(1−s)/sR_2'(1-s)/s as a real resistor. No heat is produced in it; it represents the shaft load.

Practice

  1. The example motor runs at 1470 rpm1470\ \text{rpm}. Find ss, the rotor frequency and the value of R2′/sR_2'/s.
  2. An induction motor takes Pag=20 kWP_\text{ag} = 20\ \text{kW} at s=0.03s = 0.03. Find the rotor copper loss and the mechanical power.
  3. A 6-pole, 50 Hz50\ \text{Hz} motor develops Pag=11 kWP_\text{ag} = 11\ \text{kW}. What induced torque does that mean?
Answer
  1. s=30/1500=0.02s = 30/1500 = 0.02, fr=1.0 Hzf_r = 1.0\ \text{Hz}, R2′/s=0.45/0.02=22.5 ΩR_2'/s = 0.45/0.02 = 22.5\ \Omega.
  2. Pcu2=0.03⋅20=0.6 kWP_\text{cu2} = 0.03 \cdot 20 = 0.6\ \text{kW}; Pmech=19.4 kWP_\text{mech} = 19.4\ \text{kW}.
  3. ωs=4π⋅50/6=104.7 rad/s\omega_s = 4\pi \cdot 50/6 = 104.7\ \text{rad/s}, T=11 000/104.7=105 N mT = 11\,000/104.7 = 105\ \text{N m}.

Test yourself

A 4-pole, 50 Hz induction motor runs at 1440 rpm. What is the frequency of its rotor currents?

  1. 0.04 Hz
  2. 2 Hz
  3. 48 Hz
  4. 50 Hz

At slip ss, what fraction of the air-gap power is lost as rotor copper loss?

  1. 1−s1 - s
  2. ss
  3. s2s^2
  4. 1/s1/s

Why is the magnetising current of an induction motor a much larger fraction of rated current than in a transformer?

  1. the rotor is short-circuited
  2. the air gap makes the magnetising reactance small
  3. the stator resistance is large
  4. the supply is three-phase

In the per-phase circuit, which element represents the mechanical output?

  1. XmX_m
  2. R1R_1
  3. R2′(1−s)/sR_2'(1 - s)/s
  4. X2′X_2'