Home › Electrical Machines & Transformers › Synchronous Machines: Construction, EMF and Synchronous Reactance

Synchronous Machines: Construction, EMF and Synchronous Reactance

Almost every kilowatt-hour from a thermal, nuclear or hydro power station leaves a synchronous generator: a machine whose rotor turns in lock-step with the rotating field of its stator. The same machine works as a motor where constant speed or power-factor control matters (large compressors, mills, ship propulsion). This lesson builds the machine from its parts, derives its EMF, and reduces everything inside it to one per-phase model: an EMF Ef\mathbf{E}_f set by the field current behind a synchronous reactance XsX_s, measured with an open-circuit and a short-circuit test.

Safety: synchronous machines in this course are generators and motors of kilovolts and megawatts. Everything here is calculation and simulation only.

Construction

  • Stator (armature): a laminated core with a distributed three-phase winding, the same as an induction motor's. It carries the load current.
  • Rotor (field): a DC electromagnet with pp poles. Its field current IfI_f comes through slip rings and brushes or, in most modern machines, from a brushless exciter (a small inverted generator on the same shaft with a rotating rectifier). Small machines use permanent magnets (BLDC and PMSM).
  • Cylindrical (round) rotor: a solid steel forging with the field winding in slots, uniform air gap, 2 or 4 poles; for steam and gas turbines at 30003000 or 1500 rpm1500\ \text{rpm} (50 Hz).
  • Salient-pole rotor: poles that stick out, many of them, a non-uniform gap; for hydro turbines and diesel engines at low speed. A hydro generator at 100 rpm100\ \text{rpm} on 50 Hz50\ \text{Hz} needs p=120⋅50/100=60p = 120 \cdot 50/100 = 60 poles.
  • Damper (amortisseur) windings: copper bars in the pole faces, a partial cage. They damp oscillations of the rotor and let a synchronous motor start as an induction motor.

The rotor turns at exactly ns=120f/pn_s = 120f/p: on a 50 Hz50\ \text{Hz} grid a 4-pole machine runs at 1500 rpm1500\ \text{rpm} whatever its load.

The internal EMF and the open-circuit characteristic

The rotor's field, turned by the prime mover, sweeps the stator conductors and induces in each phase (same derivation as for the stator EMF of an induction motor)

Ef=4.44 f N kw Φf(If)E_f = 4.44\, f\, N\, k_w\, \Phi_f(I_f)

At constant speed EfE_f depends only on the flux, hence on IfI_f. The open-circuit characteristic (OCC) plots the terminal voltage of the unloaded machine against IfI_f: a straight air-gap line at low field current, then bending over as the iron saturates.

Armature reaction and synchronous reactance

When the stator carries a current Ia\mathbf{I}_a, its own rotating MMF adds to the rotor's (armature reaction). Because both fields rotate together, the armature MMF produces an extra EMF proportional to Ia\mathbf{I}_a and 90∘90^\circ behind it, exactly like the voltage across a reactance. Add the stator's leakage reactance XℓX_\ell and the result is one reactance, the synchronous reactance Xs=Xar+XℓX_s = X_\text{ar} + X_\ell. Per phase, star equivalent, in generator convention (current leaving the machine):

Ef=V+(Ra+jXs) Ia≈V+jXsIa\mathbf{E}_f = \mathbf{V} + (R_a + jX_s)\,\mathbf{I}_a \approx \mathbf{V} + jX_s\mathbf{I}_a

RaR_a is usually below 1 % of XsX_s and is ignored for everything except losses. XsX_s is large: about 1–2 per unit for round-rotor machines (Per-Unit System). The machine is a stiff voltage behind a big inductance.

Efset by If+ Ra jXs = j8.0 Ohm Ia load or grid +V = 3810.5 V- per phase, star equivalent, generator convention

Measuring XsX_s: open- and short-circuit tests

  • Open-circuit test: drive at rated speed, armature open, record VV against IfI_f: the OCC.
  • Short-circuit test: drive at rated speed, armature short-circuited through ammeters, raise IfI_f until rated current flows. With V=0V = 0, Ef=XsIscE_f = X_s I_{sc}; the flux is small, the iron unsaturated and the short-circuit characteristic (SCC) is a straight line.

At the same field current, Xs=Ef/IscX_s = E_f/I_{sc}. Taking EfE_f from the air-gap line gives the unsaturated XsX_s; taking it from the OCC at rated voltage gives the saturated value, closer to the machine's behaviour near rated voltage. The short-circuit ratio is

SCR=If for rated voltage on open circuitIf for rated current on short circuit≈1Xs,sat (pu)\text{SCR} = \frac{I_f \text{ for rated voltage on open circuit}}{I_f \text{ for rated current on short circuit}} \approx \frac{1}{X_{s,\text{sat}}\ (\text{pu})}

A high SCR (small XsX_s) means a bigger, more expensive machine that is more stable on the grid (V-Curves and the Infinite Bus). Modern turbogenerators have SCR about 0.4–0.6, hydro generators about 1–1.5.

Worked example: the course's synchronous generator

Given: a 5 MVA5\ \text{MVA}, 6.6 kV6.6\ \text{kV}, 50 Hz50\ \text{Hz}, 4-pole, star-connected generator (used in all the synchronous lessons). OCC (line voltage against field current):

IfI_f (A) 0 40 80 120 160 200 240
VLV_L (V) 0 1900 3690 5270 6600 7670 8510

Short-circuit test: 437 A437\ \text{A} at If=147 AI_f = 147\ \text{A}.

Find: rated current, base impedance, unsaturated and saturated XsX_s, and the SCR.

Solve:

IN=5×106 VA3⋅6600 V=437.4 A,Zbase=(6600 V)25×106 VA=8.712 ΩXs,unsat=(1900/40) V/A⋅147 A/3437 A=4031 V437 A=9.23 Ω=1.06 puXs,sat=3810.5 V437 A⋅160/147=3810.5 V475.6 A=8.01 Ω=0.920 puSCR=160 A147 A=1.088,1SCR=0.919 pu\begin{aligned} I_N &= \frac{5 \times 10^6\ \text{VA}}{\sqrt{3} \cdot 6600\ \text{V}} = 437.4\ \text{A}, \qquad Z_\text{base} = \frac{(6600\ \text{V})^2}{5 \times 10^6\ \text{VA}} = 8.712\ \Omega \\ X_{s,\text{unsat}} &= \frac{(1900/40)\ \text{V/A} \cdot 147\ \text{A}/\sqrt{3}}{437\ \text{A}} = \frac{4031\ \text{V}}{437\ \text{A}} = 9.23\ \Omega = 1.06\ \text{pu} \\ X_{s,\text{sat}} &= \frac{3810.5\ \text{V}}{437\ \text{A} \cdot 160/147} = \frac{3810.5\ \text{V}}{475.6\ \text{A}} = 8.01\ \Omega = 0.920\ \text{pu} \\ \text{SCR} &= \frac{160\ \text{A}}{147\ \text{A}} = 1.088, \qquad \frac{1}{\text{SCR}} = 0.919\ \text{pu} \end{aligned}

Check: the two routes to the saturated reactance agree (0.9200.920 against 0.9190.919 pu). The following lessons use Xs=8.0 ΩX_s = 8.0\ \Omega. An SCR near 1 is typical of a medium-speed generator set of this size.

In Python: XsX_s from the tests, and the field needed under load

python · try it yourself
import numpy as np
S, VL, f = 5e6, 6600.0, 50.0                  # rating: 5 MVA, 6.6 kV, star, 4 poles
V = VL / np.sqrt(3)
I_N = S / (np.sqrt(3) * VL)
Z_base = VL**2 / S

# open-circuit characteristic: field current (A) -> line voltage (V)
If_oc = np.array([0, 40, 80, 120, 160, 200, 240])
E_oc = np.array([0, 1900, 3690, 5270, 6600, 7670, 8510])
# short-circuit characteristic: linear, 437 A armature current at 147 A field
If_sc, I_sc = 147.0, 437.0

slope = E_oc[1] / If_oc[1]                     # air-gap line, V per field ampere
Xs_unsat = (slope * If_sc / np.sqrt(3)) / I_sc
If_rated_V = np.interp(VL, E_oc, If_oc)       # field for rated voltage on open circuit
Xs_sat = V / (I_sc * If_rated_V / If_sc)
SCR = If_rated_V / If_sc
print(f"rated current {I_N:.1f} A, base impedance {Z_base:.3f} ohm")
print(f"Xs unsaturated = {Xs_unsat:.2f} ohm ({Xs_unsat/Z_base:.3f} pu)")
print(f"Xs saturated   = {Xs_sat:.2f} ohm ({Xs_sat/Z_base:.3f} pu), SCR = {SCR:.3f}, 1/SCR = {1/SCR:.3f}")

Xs = 8.0                                      # value used in the following lessons
for pf, kind in ((0.85, "lagging"), (1.0, "unity"), (0.85, "leading")):
    phi = np.arccos(pf) * (-1 if kind == "lagging" else 1)
    Ia = I_N * np.exp(1j * phi)
    Ef = V + 1j * Xs * Ia                      # generator: Ef = V + j Xs Ia
    If = If_rated_V * abs(Ef) / V              # linearised OCC through the rated point
    print(f"pf {pf:.2f} {kind:8s}: Ef = {abs(Ef):6.0f} V phase ({abs(Ef)*np.sqrt(3)/1e3:.2f} kV line), "
          f"delta = {np.degrees(np.angle(Ef)):5.1f} deg, field about {If:3.0f} A")
rated current 437.4 A, base impedance 8.712 ohm
Xs unsaturated = 9.23 ohm (1.059 pu)
Xs saturated   = 8.01 ohm (0.920 pu), SCR = 1.088, 1/SCR = 0.919
pf 0.85 lagging : Ef =   6388 V phase (11.06 kV line), delta =  27.7 deg, field about 268 A
pf 1.00 unity   : Ef =   5173 V phase (8.96 kV line), delta =  42.6 deg, field about 217 A
pf 0.85 leading : Ef =   3566 V phase (6.18 kV line), delta =  56.5 deg, field about 150 A

Supplying a lagging (inductive) load at rated current needs an internal EMF of 11.1 kV11.1\ \text{kV} line, 1.68 times the terminal voltage, and 268 A268\ \text{A} of field; a leading load needs less EMF than the terminal voltage. The field estimate uses the OCC straightened through the rated point, the usual hand method; a full saturation treatment (the Potier or ASA methods) refines it by a few per cent.

Interactive: one phase delivering rated current

The netlist lab is one phase of the generator: VF is Ef=6388 V∠27.7∘\mathbf{E}_f = 6388\ \text{V} \angle 27.7^\circ, LS is XsX_s (25.46 mH25.46\ \text{mH} at 50 Hz50\ \text{Hz}) and VBUS the terminal voltage 3810.5 V3810.5\ \text{V}. The lab shows Ia=437.1 A∠−31.9∘I_a = 437.1\ \text{A} \angle -31.9^\circ (I(LS)): rated current at pf 0.85 lagging. Lower VF and the current swings round towards leading, because with the angle held fixed the difference Ef−V\mathbf{E}_f - \mathbf{V} changes direction.

0200040006000100m1101001k10kf (Hz)|V| (V)0 A100 kA200 kA|I| (A)|V(e)||I(LS)|phasors at f = 50.00 Hz (magnitude @ phase)V(e)6.39 kV @ 27.7 degV(bus)3.81 kV @ 0.0 degI(VF)437 A @ 148.1 degI(LS)437 A @ -31.9 degI(VBUS)437 A @ -31.9 deg

Ignore the frequency plot: a real machine's EMF is tied to its speed, so it has no meaning away from 50 Hz50\ \text{Hz}.

Guided lab (data analysis and a low-voltage analogue)

Hand calculation. For an OCC and SCC of your own (or from a published generator test report), compute both reactances and the SCR.

Simulation. Change the OCC in the code to saturate earlier (for example 6600 V6600\ \text{V} at 180 A180\ \text{A}) and see the SCR and field currents change.

What you would measure. On a real generator, open- and short-circuit tests are done by the manufacturer or a commissioning team (high voltage, high fault-level currents). A safe low-voltage analogue: a small permanent-magnet DC or BLDC motor driven at constant speed by a second motor (both from a bench supply set to at most 12 V12\ \text{V} with a current limit) acts as a generator with fixed excitation; its open-circuit voltage is proportional to speed (expect the datasheet's speed constant ±10 %\pm 10\ \%), and loading it with resistors shows the terminal voltage falling from its internal resistance and inductance. Clamp both motors, shield the coupling, keep fingers and hair clear.

Pitfalls

  • Line against phase. OCC tests read line voltage; XsX_s uses phase voltage (divide by 3\sqrt{3} for star).
  • Using the unsaturated XsX_s near rated voltage. It overstates the reactance by 10–20 % here.
  • Calling XsX_s a physical inductor. Most of it is armature reaction; it describes steady state only. Transients use the much smaller transient and subtransient reactances (Power Systems).
  • Forgetting the generator sign convention. For a motor, V=Ef+jXsIa\mathbf{V} = \mathbf{E}_f + jX_s\mathbf{I}_a with current flowing in.

Practice

  1. A 50 Hz hydro generator turns at 150 rpm150\ \text{rpm}. How many poles?
  2. A generator gives rated current 1000 A1000\ \text{A} on short circuit at If=300 AI_f = 300\ \text{A} and rated voltage 11 kV11\ \text{kV} line on open circuit at If=250 AI_f = 250\ \text{A}. Find the SCR and the saturated XsX_s in per unit.
  3. In the worked example, find EfE_f at rated current and unity power factor by hand.
Answer
  1. p=120⋅50/150=40p = 120 \cdot 50/150 = 40 poles.
  2. SCR=250/300=0.833\text{SCR} = 250/300 = 0.833; Xs≈1/0.833=1.2 puX_s \approx 1/0.833 = 1.2\ \text{pu}.
  3. Ef=3810.5+j8⋅437.4=3810.5+j3499 V\mathbf{E}_f = 3810.5 + j8 \cdot 437.4 = 3810.5 + j3499\ \text{V}, ∣Ef∣=5173 V\lvert\mathbf{E}_f\rvert = 5173\ \text{V} at δ=42.6∘\delta = 42.6^\circ.

Test yourself

What sets the internal EMF EfE_f of a synchronous generator running at constant speed?

  1. the load current
  2. the field current
  3. the stator resistance
  4. the power factor

Why is the short-circuit characteristic a straight line?

  1. the rotor is locked
  2. the net flux is small, so the iron does not saturate
  3. the frequency is zero
  4. the armature resistance is large

A generator has a short-circuit ratio of 0.5. Its saturated synchronous reactance is about…

  1. 0.5 pu
  2. 1 pu
  3. 2 pu
  4. 0.25 pu

Which rotor type suits a 100 rpm hydro generator?

  1. cylindrical, 2 poles
  2. salient pole with many poles
  3. squirrel cage
  4. cylindrical, 4 poles