Synchronous Machines: Construction, EMF and Synchronous Reactance
Almost every kilowatt-hour from a thermal, nuclear or hydro power station leaves a synchronous generator: a machine whose rotor turns in lock-step with the rotating field of its stator. The same machine works as a motor where constant speed or power-factor control matters (large compressors, mills, ship propulsion). This lesson builds the machine from its parts, derives its EMF, and reduces everything inside it to one per-phase model: an EMF set by the field current behind a synchronous reactance , measured with an open-circuit and a short-circuit test.
Safety: synchronous machines in this course are generators and motors of kilovolts and megawatts. Everything here is calculation and simulation only.
Construction
- Stator (armature): a laminated core with a distributed three-phase winding, the same as an induction motor's. It carries the load current.
- Rotor (field): a DC electromagnet with poles. Its field current comes through slip rings and brushes or, in most modern machines, from a brushless exciter (a small inverted generator on the same shaft with a rotating rectifier). Small machines use permanent magnets (BLDC and PMSM).
- Cylindrical (round) rotor: a solid steel forging with the field winding in slots, uniform air gap, 2 or 4 poles; for steam and gas turbines at or (50 Hz).
- Salient-pole rotor: poles that stick out, many of them, a non-uniform gap; for hydro turbines and diesel engines at low speed. A hydro generator at on needs poles.
- Damper (amortisseur) windings: copper bars in the pole faces, a partial cage. They damp oscillations of the rotor and let a synchronous motor start as an induction motor.
The rotor turns at exactly : on a grid a 4-pole machine runs at whatever its load.
The internal EMF and the open-circuit characteristic
The rotor's field, turned by the prime mover, sweeps the stator conductors and induces in each phase (same derivation as for the stator EMF of an induction motor)
At constant speed depends only on the flux, hence on . The open-circuit characteristic (OCC) plots the terminal voltage of the unloaded machine against : a straight air-gap line at low field current, then bending over as the iron saturates.
Armature reaction and synchronous reactance
When the stator carries a current , its own rotating MMF adds to the rotor's (armature reaction). Because both fields rotate together, the armature MMF produces an extra EMF proportional to and behind it, exactly like the voltage across a reactance. Add the stator's leakage reactance and the result is one reactance, the synchronous reactance . Per phase, star equivalent, in generator convention (current leaving the machine):
is usually below 1 % of and is ignored for everything except losses. is large: about 1–2 per unit for round-rotor machines (Per-Unit System). The machine is a stiff voltage behind a big inductance.
Measuring : open- and short-circuit tests
- Open-circuit test: drive at rated speed, armature open, record against : the OCC.
- Short-circuit test: drive at rated speed, armature short-circuited through ammeters, raise until rated current flows. With , ; the flux is small, the iron unsaturated and the short-circuit characteristic (SCC) is a straight line.
At the same field current, . Taking from the air-gap line gives the unsaturated ; taking it from the OCC at rated voltage gives the saturated value, closer to the machine's behaviour near rated voltage. The short-circuit ratio is
A high SCR (small ) means a bigger, more expensive machine that is more stable on the grid (V-Curves and the Infinite Bus). Modern turbogenerators have SCR about 0.4–0.6, hydro generators about 1–1.5.
Worked example: the course's synchronous generator
Given: a , , , 4-pole, star-connected generator (used in all the synchronous lessons). OCC (line voltage against field current):
| (A) | 0 | 40 | 80 | 120 | 160 | 200 | 240 |
|---|---|---|---|---|---|---|---|
| (V) | 0 | 1900 | 3690 | 5270 | 6600 | 7670 | 8510 |
Short-circuit test: at .
Find: rated current, base impedance, unsaturated and saturated , and the SCR.
Solve:
Check: the two routes to the saturated reactance agree ( against pu). The following lessons use . An SCR near 1 is typical of a medium-speed generator set of this size.
In Python: from the tests, and the field needed under load
import numpy as np
S, VL, f = 5e6, 6600.0, 50.0 # rating: 5 MVA, 6.6 kV, star, 4 poles
V = VL / np.sqrt(3)
I_N = S / (np.sqrt(3) * VL)
Z_base = VL**2 / S
# open-circuit characteristic: field current (A) -> line voltage (V)
If_oc = np.array([0, 40, 80, 120, 160, 200, 240])
E_oc = np.array([0, 1900, 3690, 5270, 6600, 7670, 8510])
# short-circuit characteristic: linear, 437 A armature current at 147 A field
If_sc, I_sc = 147.0, 437.0
slope = E_oc[1] / If_oc[1] # air-gap line, V per field ampere
Xs_unsat = (slope * If_sc / np.sqrt(3)) / I_sc
If_rated_V = np.interp(VL, E_oc, If_oc) # field for rated voltage on open circuit
Xs_sat = V / (I_sc * If_rated_V / If_sc)
SCR = If_rated_V / If_sc
print(f"rated current {I_N:.1f} A, base impedance {Z_base:.3f} ohm")
print(f"Xs unsaturated = {Xs_unsat:.2f} ohm ({Xs_unsat/Z_base:.3f} pu)")
print(f"Xs saturated = {Xs_sat:.2f} ohm ({Xs_sat/Z_base:.3f} pu), SCR = {SCR:.3f}, 1/SCR = {1/SCR:.3f}")
Xs = 8.0 # value used in the following lessons
for pf, kind in ((0.85, "lagging"), (1.0, "unity"), (0.85, "leading")):
phi = np.arccos(pf) * (-1 if kind == "lagging" else 1)
Ia = I_N * np.exp(1j * phi)
Ef = V + 1j * Xs * Ia # generator: Ef = V + j Xs Ia
If = If_rated_V * abs(Ef) / V # linearised OCC through the rated point
print(f"pf {pf:.2f} {kind:8s}: Ef = {abs(Ef):6.0f} V phase ({abs(Ef)*np.sqrt(3)/1e3:.2f} kV line), "
f"delta = {np.degrees(np.angle(Ef)):5.1f} deg, field about {If:3.0f} A")rated current 437.4 A, base impedance 8.712 ohm
Xs unsaturated = 9.23 ohm (1.059 pu)
Xs saturated = 8.01 ohm (0.920 pu), SCR = 1.088, 1/SCR = 0.919
pf 0.85 lagging : Ef = 6388 V phase (11.06 kV line), delta = 27.7 deg, field about 268 A
pf 1.00 unity : Ef = 5173 V phase (8.96 kV line), delta = 42.6 deg, field about 217 A
pf 0.85 leading : Ef = 3566 V phase (6.18 kV line), delta = 56.5 deg, field about 150 A
Supplying a lagging (inductive) load at rated current needs an internal EMF of line, 1.68 times the terminal voltage, and of field; a leading load needs less EMF than the terminal voltage. The field estimate uses the OCC straightened through the rated point, the usual hand method; a full saturation treatment (the Potier or ASA methods) refines it by a few per cent.
Interactive: one phase delivering rated current
The netlist lab is one phase of the generator: VF is , LS is ( at ) and VBUS the terminal voltage . The lab shows (I(LS)): rated current at pf 0.85 lagging. Lower VF and the current swings round towards leading, because with the angle held fixed the difference changes direction.
Ignore the frequency plot: a real machine's EMF is tied to its speed, so it has no meaning away from .
Guided lab (data analysis and a low-voltage analogue)
Hand calculation. For an OCC and SCC of your own (or from a published generator test report), compute both reactances and the SCR.
Simulation. Change the OCC in the code to saturate earlier (for example at ) and see the SCR and field currents change.
What you would measure. On a real generator, open- and short-circuit tests are done by the manufacturer or a commissioning team (high voltage, high fault-level currents). A safe low-voltage analogue: a small permanent-magnet DC or BLDC motor driven at constant speed by a second motor (both from a bench supply set to at most with a current limit) acts as a generator with fixed excitation; its open-circuit voltage is proportional to speed (expect the datasheet's speed constant ), and loading it with resistors shows the terminal voltage falling from its internal resistance and inductance. Clamp both motors, shield the coupling, keep fingers and hair clear.
Pitfalls
- Line against phase. OCC tests read line voltage; uses phase voltage (divide by for star).
- Using the unsaturated near rated voltage. It overstates the reactance by 10–20 % here.
- Calling a physical inductor. Most of it is armature reaction; it describes steady state only. Transients use the much smaller transient and subtransient reactances (Power Systems).
- Forgetting the generator sign convention. For a motor, with current flowing in.
Practice
- A 50 Hz hydro generator turns at . How many poles?
- A generator gives rated current on short circuit at and rated voltage line on open circuit at . Find the SCR and the saturated in per unit.
- In the worked example, find at rated current and unity power factor by hand.
Answer
- poles.
- ; .
- , at .
Test yourself
What sets the internal EMF of a synchronous generator running at constant speed?
- the load current
- the field current
- the stator resistance
- the power factor
Why is the short-circuit characteristic a straight line?
- the rotor is locked
- the net flux is small, so the iron does not saturate
- the frequency is zero
- the armature resistance is large
A generator has a short-circuit ratio of 0.5. Its saturated synchronous reactance is about…
- 0.5 pu
- 1 pu
- 2 pu
- 0.25 pu
Which rotor type suits a 100 rpm hydro generator?
- cylindrical, 2 poles
- salient pole with many poles
- squirrel cage
- cylindrical, 4 poles