Mini Project: A Pump Drive from Test Data to Motor Choice
A water-treatment plant needs a new drive for a centrifugal pump. The pump wants about at , its torque rising with the square of speed. The maintenance team has a four-pole induction motor in stock, with only a test report, and the motor would be fed from a small transformer that also supplies other loads. In this project you take the motor from test readings to an equivalent circuit, find where it will run on the pump, check its efficiency class, choose a starting method and check the voltage dip it causes, cross-check the operating point in SPICE, and write it up as a short engineering note. It draws on almost every section of the course.
Safety: calculation and simulation only. The motor, the pump, the transformer and the starters are three-phase equipment. Their tests and their commissioning are work for qualified electricians and test engineers. The guided lab at the end uses a fan as a safe stand-in for the pump characteristic.
The specification
| Item | Value |
|---|---|
| supply | , , from a Dyn11 transformer, , |
| load | centrifugal pump, (4 N·m breakaway) |
| inertia | (motor, coupling and impeller) |
| motor | , , 4 poles, delta-run (so a star–delta starter is possible) |
| test report (per IEEE 112-style tests) | DC resistance between two terminals; no-load , , ; blocked rotor at : , , (line values) |
| requirements | run within the motor's rating; efficiency at rated output at or above the IE3 limit; voltage dip at the transformer during starting below about (the plant's own rule for this board) |
These are the readings of the course's example motor (No-Load and Blocked-Rotor Tests).
Step 1: the equivalent circuit from the tests
Work per phase of the star equivalent (Slip and the Equivalent Circuit). The DC test gives . The blocked-rotor test, at a quarter of rated frequency so that the rotor currents have the frequency they have in service, gives the series branch; its reactance is scaled from to and split between stator and rotor (the split for a design B motor). The no-load test gives and the rotational loss.
Step 2: the operating point on the pump
The motor runs where its torque, less the friction and windage torque, equals the pump's (The Torque–Slip Curve). brentq finds that slip.
Step 3: efficiency class
IEC 60034-30-1 classes are judged at rated output, from tests to IEC 60034-2-1 (Ratings, Duty Cycles and IE Classes). The program finds the slip at which the model delivers and its efficiency there. The comparison value, for IE3 at , four poles, , is from the IEC 60034-30-1:2014 table (the 2025 second edition lists no change to the IE1 to IE4 limits in its foreword).
import numpy as np
# Step 1: equivalent circuit from test readings (400 V star, 50 Hz, 4 poles, 7.5 kW)
R_dc = 1.10 # between two terminals
V_nl, I_nl, P_nl = 400.0, 7.00, 301.0 # no-load, line values
V_br, I_br, P_br, f_br = 28.4, 14.4, 601.0, 12.5 # blocked rotor at reduced frequency
R1 = R_dc / 2
Zbr = (V_br / np.sqrt(3)) / I_br
Rbr = P_br / (3 * I_br**2)
Xbr = np.sqrt(Zbr**2 - Rbr**2) * 50 / f_br # scale the reactance to 50 Hz
X1, X2 = 0.4 * Xbr, 0.6 * Xbr # NEMA design B split
Vnl = V_nl / np.sqrt(3)
Xnl = np.sqrt((Vnl / I_nl)**2 - (P_nl / (3 * I_nl**2))**2)
Xm = Xnl - X1
R2 = (Rbr - R1) * ((X2 + Xm) / Xm)**2 # refer the measured rotor resistance through Xm
P_rot = P_nl - 3 * I_nl**2 * R1
print(f"R1 {R1:.3f} X1 {X1:.3f} Xm {Xm:.2f} R2' {R2:.4f} X2' {X2:.3f} Ohm rotational loss {P_rot:.1f} W")
# Step 2: operating point with the pump, T_L = 4 + 41 (n/1460)^2 N m
from scipy.optimize import brentq
ns, ws = 1500.0, 2 * np.pi * 1500 / 60
def motor(s, V=Vnl):
Z2 = R2 / s + 1j * X2
Zp = 1j * Xm * Z2 / (1j * Xm + Z2)
I1 = V / (R1 + 1j * X1 + Zp)
I2 = I1 * 1j * Xm / (1j * Xm + Z2)
Pag = 3 * abs(I2)**2 * R2 / s
return I1, Pag / ws, Pag
TL = lambda n: 4 + 41 * (n / 1460)**2
s0 = brentq(lambda s: motor(s)[1] - P_rot / (ws * (1 - s)) - TL(ns * (1 - s)), 1e-4, 0.2)
I1, Te, Pag = motor(s0)
n0 = ns * (1 - s0)
P_in = 3 * (Vnl * np.conj(I1)).real
P_out = Pag * (1 - s0) - P_rot
print(f"operating point: s = {s0:.4f}, {n0:.1f} rpm, load {TL(n0):.2f} N m, I = {abs(I1):.2f} A, "
f"pf {np.cos(np.angle(I1)):.3f}, P_out {P_out:.0f} W ({P_out/7500*100:.0f} % of rating), efficiency {P_out/P_in*100:.1f} %")
# Step 3: efficiency at the rated 7.5 kW output, for the IE class check
def out(s):
I1, _, Pag = motor(s)
return Pag * (1 - s) - P_rot, 3 * (Vnl * np.conj(I1)).real, abs(I1)
sr = brentq(lambda s: out(s)[0] - 7500, 1e-4, 0.2)
Po, Pi, Ir = out(sr)
print(f"rated output at s = {sr:.4f} ({ns*(1-sr):.0f} rpm): I = {Ir:.2f} A, efficiency {Po/Pi*100:.2f} % "
f"(IE3 limit for 7.5 kW, 4 poles, 50 Hz: 90.4 %)")R1 0.550 X1 0.964 Xm 31.96 R2' 0.4546 X2' 1.446 Ohm rotational loss 220.1 W
operating point: s = 0.0237, 1464.5 rpm, load 45.25 N m, I = 13.60 A, pf 0.811, P_out 6940 W (93 % of rating), efficiency 90.8 %
rated output at s = 0.0258 (1461 rpm): I = 14.46 A, efficiency 90.70 % (IE3 limit for 7.5 kW, 4 poles, 50 Hz: 90.4 %)
The model gives , , , and with rotational loss. On the pump the motor runs at (slip ) and delivers , 93 % of its rating, at and pf : a good match, with a little margin for a pump that may later work against a lower head (more flow, more torque). At rated output its efficiency is , just above the IE3 limit. Note how sensitive the test method is: a slightly different treatment of the no-load reading (subtracting the stator copper loss before finding ) moves by about , and the efficiency by much less; the efficiency margin over IE3, points, is much smaller than the tolerance IEC 60034-1 allows between declared and tested efficiency ( of for machines up to , about points here) and than the model's own uncertainty, so a certified test, not a model, settles the class.
Step 4: starting method and voltage dip
The motor is fed through the transformer, whose impedance on the side is per phase at (The Per-Unit System). The program computes the direct-on-line starting current and the voltage at the motor terminals, then integrates for three starters (Starting Methods and Speed Control): direct on line, star–delta switching over at , and a soft starter ramping from to full voltage. A delta-run motor connected in star has each phase of its star equivalent three times larger, which the model's factor m represents.
import numpy as np
# the motor from step 1 (per phase, star equivalent) and the pump, J = motor + pump + coupling
R1, X1, Xm, R2, X2, P_rot = 0.550, 0.964, 31.96, 0.4546, 1.446, 220.1
V, ns, J = 400 / np.sqrt(3), 1500.0, 0.10
ws = 2 * np.pi * ns / 60
TL = lambda n: 4 + 41 * (n / 1460)**2
Zt = 0.04 * 400**2 / 100e3 * (1 + 3j) / np.sqrt(10) # 100 kVA supply transformer, z = 4 %, X/R = 3
def motor(s, k=1.0, Zsrc=0.0, m=1):
"""Line current, torque and motor phase voltage at slip s, supply k*V behind Zsrc.
m = 3 for a delta-run motor connected in star: each phase of its star equivalent is 3 times larger."""
Z2 = m * (R2 / s + 1j * X2)
Zm = m * (R1 + 1j * X1) + 1j * m * Xm * Z2 / (1j * m * Xm + Z2)
I1 = k * V / (Zm + Zsrc)
I2 = I1 * 1j * m * Xm / (1j * m * Xm + Z2)
return I1, 3 * abs(I2)**2 * m * R2 / s / ws, I1 * Zm
I_dol, T_dol, Vm = motor(1.0, Zsrc=Zt)
print(f"DOL through the transformer: {abs(I_dol):.1f} A, {T_dol:.1f} N m, motor terminals at "
f"{abs(Vm)/V*100:.1f} % ({(1-abs(Vm)/V)*100:.1f} % dip)")
def run_up(k_of_n, m_of_n, label, dt=1e-3):
"""Euler steps of J dw/dt = T_motor - T_pump - T_friction until 95 % of the running speed."""
n, t, T_fr = 0.0, 0.0, P_rot / (2 * np.pi * 1464.5 / 60)
while n < 0.95 * 1464.5 and t < 30:
I, T, _ = motor(max(1 - n / ns, 1e-4), k_of_n(n), Zt, m_of_n(n))
n += (T - TL(n) - T_fr) / J * dt * 60 / (2 * np.pi)
t += dt
print(f"{label:36s} reaches 95 % speed in {t:5.2f} s")
run_up(lambda n: 1.0, lambda n: 1, "direct on line")
run_up(lambda n: 1.0, lambda n: 3 if n < 1300 else 1, "star-delta, change-over at 1300 rpm")
run_up(lambda n: min(1.0, 0.45 + 0.55 * n / 1400), lambda n: 1, "soft start ramp 45 % to 100 %")
for label, k, m in (("star connection", 1.0, 3), ("soft start at 45 %", 0.45, 1)):
I, T, _ = motor(1.0, k, Zt, m)
print(f"at standstill, {label:19s}: {abs(I):5.1f} A, {T:5.1f} N m (pump needs {TL(0):.0f} N m)")DOL through the transformer: 88.6 A, 62.3 N m, motor terminals at 97.6 % (2.4 % dip)
direct on line reaches 95 % speed in 0.17 s
star-delta, change-over at 1300 rpm reaches 95 % speed in 0.71 s
soft start ramp 45 % to 100 % reaches 95 % speed in 0.55 s
at standstill, star connection : 30.0 A, 21.5 N m (pump needs 4 N m)
at standstill, soft start at 45 % : 39.9 A, 12.6 N m (pump needs 4 N m)
Direct on line, the motor draws (about six times its running current) and dips the board by , inside the plant's rule; it reaches speed in under , because a centrifugal pump needs little torque at low speed. Star–delta cuts the starting current to and the torque to , still five times the pump's breakaway torque, at the cost of a current and torque transient at the change-over that this quasi-static model does not show. A soft starter gives a smooth ramp and the gentlest hydraulic start, which matters for water hammer in long pipes. Recommendation: direct on line is electrically acceptable here; choose a soft starter if the pipework needs a gentle start, or a variable-frequency drive if the flow must be controlled (see Extensions).
Step 5: cross-check in SPICE
The operating point is one phase of an AC circuit, so ngspice can check it: the slip enters as the resistor , and the reactances become inductances at .
cat > motor.cir <<'EOF'
* 7.5 kW induction motor, one phase of the star equivalent, at the pump's operating slip s = 0.0237
V1 a 0 AC 230.94
R1 a b 0.550
L1 b c 3.0686m
LM c 0 101.73m
L2 c d 4.6027m
R2S d 0 19.181
.control
ac lin 1 50 50
let i1 = mag(i(V1))
let pf = cos(ph(-i(V1)))
let i2 = mag(v(d))/19.181
let tq = 3*i2*i2*19.181*(1-0.0237)/(2*pi*1464.5/60)
print i1 pf i2 tq
.endc
.end
EOF
ngspice -b motor.cir 2>&1 | grep -E '^(i1|pf|i2|tq)'i1 = 1.361459e+01
pf = 8.108008e-01
i2 = 1.129565e+01
tq = 4.673907e+01
SPICE gives at pf and an induced torque of , which is the pump's plus of friction and windage, within (the slip was rounded to four digits for the deck).
Guided lab: what you would measure
On the real drive, the commissioning engineer records, and you would compare with the model: the running current on each phase with a clamp meter ( expected, for supply voltage and pump head variation), the speed with an optical tachometer (, ), the starting current peak on a power-quality recorder (around rms in the first cycles plus an asymmetric first peak), and the board voltage dip during start (about ). These are measurements for qualified staff on live equipment.
The safe stand-in you can do yourself. A brushless PC fan is a small fan-law load on a motor you are allowed to touch. Power it from a bench supply with a current limit of , step the voltage from to , and record current and speed (from the fan's tachometer wire, usually two pulses per revolution, on an oscilloscope or a frequency counter). Plot input power against speed on log–log axes: a fan load gives a slope near (power because torque ), minus the fan electronics' fixed consumption. Expect on speed and on power from the meters. Hazards: keep fingers out of the blades and the fan clamped; don't block the blades to stall it.
Your write-up
Use this template for a one- or two-page note:
- Purpose: the drive to be specified and the constraints (supply, load, dip limit).
- Data: the test readings and the load and inertia assumptions, with their sources.
- Model: the equivalent-circuit parameters and how they were obtained (method, split, scaling).
- Results: operating point, load factor, efficiency against IE3, starting currents, run-up times and voltage dip, the SPICE cross-check.
- Recommendation: starter type and why; any risks (efficiency margin, star–delta transient, water hammer).
- Uncertainty: which inputs matter most (pump curve, blocked-rotor reading, inertia) and by how much a change moves the answers.
- Safety note: who commissions and tests the drive, and what was simulated only.
Extensions
- Variable speed. For 80 % flow a pump runs at about 80 % speed and, by the affinity laws, needs about of the power. Use the V/f model of the course (Starting Methods and Speed Control) to find the frequency, current and efficiency at that point, and compare the energy with throttling a valve at full speed. Drives themselves are in Power Electronics & Motor Drives.
- Sensitivity. Rerun step 2 with the pump torque and the supply at (IEC 60038's tolerance band), and report the worst-case current and slip.
- A second motor. The transformer also feeds of other load at pf . Add it to the dip calculation as a constant-impedance load and see whether the rule still holds.
Test yourself
Why is the blocked-rotor test of a larger induction motor done at reduced frequency?
- to reduce the current
- so the rotor currents have roughly the low frequency they have in normal running
- to avoid saturating the stator
- because the standard forbids 50 Hz
The motor's model efficiency at rated output is 90.70 % against an IE3 limit of 90.4 %. What settles the class?
- the model
- a certified efficiency test to IEC 60034-2-1
- the nameplate power factor
- the starting current
A delta-run motor is started in star. Compared with direct-on-line delta starting, its line current and torque are…
- both halved
- both one third
- current one third, torque unchanged
- current unchanged, torque one third
Why does the pump reach speed so quickly even with a reduced-voltage start?
- its inertia is zero
- a centrifugal pump's torque rises with the square of speed, so it needs little torque at low speed
- the motor is oversized
- the transformer boosts the voltage