Voltage Regulation, Efficiency and All-Day Efficiency

Two numbers decide whether a transformer is good for a job. Voltage regulation says how much the output sags from no load to full load: too much, and lamps dim and motors stall at the end of a long feeder. Efficiency says how much energy it wastes: at 98.6 %, a 50 kVA50\ \text{kVA} unit at full load still turns more than half a kilowatt into heat. For a distribution transformer that is lightly loaded most of the day, the useful figure is not even the full-load efficiency but the all-day (energy) efficiency. This lesson computes all three for transformer T1 from its test results (Open-Circuit and Short-Circuit Tests).

Safety: T1 is a 2400 V2400\ \text{V} transformer; everything here is calculation and simulation.

Voltage regulation

With the primary voltage held constant, regulation compares the secondary voltage at no load with the value at the stated load:

VR=V2,nl−V2,flV2,fl×100 %\text{VR} = \frac{V_{2,\text{nl}} - V_{2,\text{fl}}}{V_{2,\text{fl}}} \times 100\ \%

At no load V2,nl=V1/aV_{2,\text{nl}} = V_1/a (the shunt current's drop is negligible), so referred to the primary VR=(V1−V2′)/V2′\text{VR} = (V_1 - V_2')/V_2', exactly the quantity the phasor diagram gave in Transformer Phasor Diagrams:

VR≈rcos⁡φ+xsin⁡φ+(xcos⁡φ−rsin⁡φ)22\text{VR} \approx r\cos\varphi + x\sin\varphi + \frac{(x\cos\varphi - r\sin\varphi)^2}{2}

with the per-unit drops at the stated current, r=IReq/Vr = IR_\text{eq}/V, x=IXeq/Vx = IX_\text{eq}/V, and sin⁡φ>0\sin\varphi > 0 for lagging loads. Regulation is positive for lagging and resistive loads, and can be negative for leading ones. Distribution transformers often have off-circuit tap changers (typically ±2×2.5 %\pm 2 \times 2.5\ \%) to set the no-load ratio for the feeder they sit on; large power transformers have on-load tap changers.

Efficiency

The losses are the no-load loss P0P_0 (the core, present whenever the transformer is energised, the OC-test power) and the load loss PcuP_\text{cu} at rated current (the SC-test power), which scales with the square of the load. At a fraction xx of the rated apparent power SS and power factor cos⁡φ\cos\varphi:

η(x)=xScos⁡φxScos⁡φ+P0+x2Pcu\eta(x) = \frac{x S \cos\varphi}{x S\cos\varphi + P_0 + x^2 P_\text{cu}}

Setting dη/dx=0d\eta/dx = 0 shows that the efficiency is largest when the variable loss equals the constant loss:

x2Pcu=P0⇒xηmax⁡=P0Pcux^2 P_\text{cu} = P_0 \quad\Rightarrow\quad x_{\eta\max} = \sqrt{\frac{P_0}{P_\text{cu}}}

This rule holds for every machine with a constant loss and an I2RI^2R loss, DC and induction motors included (DC Machine Losses and Efficiency). Designers place the maximum where the machine spends most of its time: distribution transformers, which carry around a third to a half of their rating on average, are built with relatively low core loss.

Worked example: T1 at full load

Given: T1, 50 kVA50\ \text{kVA}, 2400/240 V2400/240\ \text{V}, Req=1.02 ΩR_\text{eq} = 1.02\ \Omega, Xeq=3.2 ΩX_\text{eq} = 3.2\ \Omega (HV side), P0=120 WP_0 = 120\ \text{W}, Pcu=443 WP_\text{cu} = 443\ \text{W} at rated current; load at rated current, power factor 0.80.8 lagging.

Find: the regulation, the efficiency, and the load for maximum efficiency.

Solve: rated HV current 20.83 A20.83\ \text{A}, so r=20.83⋅1.02/2400=0.00885r = 20.83 \cdot 1.02/2400 = 0.00885 and x=20.83⋅3.2/2400=0.0278x = 20.83 \cdot 3.2/2400 = 0.0278:

VR≈0.00885⋅0.8+0.0278⋅0.6+12(0.0278⋅0.8−0.00885⋅0.6)2=0.0238+0.00014=2.39 %η=40 000 W40 000 W+120 W+443 W=98.61 %xηmax⁡=120/443=0.520(26.0 kVA)\begin{aligned} \text{VR} &\approx 0.00885 \cdot 0.8 + 0.0278 \cdot 0.6 + \tfrac12(0.0278 \cdot 0.8 - 0.00885 \cdot 0.6)^2 = 0.0238 + 0.00014 = 2.39\ \% \\ \eta &= \frac{40\,000\ \text{W}}{40\,000\ \text{W} + 120\ \text{W} + 443\ \text{W}} = 98.61\ \% \\ x_{\eta\max} &= \sqrt{120/443} = 0.520 \quad (26.0\ \text{kVA}) \end{aligned}

Check: the exact circuit gave V2=234.36 VV_2 = 234.36\ \text{V} for V1=2400 VV_1 = 2400\ \text{V} (the equivalent circuit), so VR=(240−234.36)/234.36=2.41 %\text{VR} = (240 - 234.36)/234.36 = 2.41\ \%; the formula is within 0.020.02 points. The losses at full load, 563 W563\ \text{W}, are 1.4 %1.4\ \% of the output: right for a transformer of this size.

In Python: efficiency curves and a day of load

python · try it yourself
import numpy as np
S, P0, Pcu = 50e3, 120.0, 443.0                 # T1: rating, no-load loss, full-load copper loss (W)
eta = lambda x, pf, P0=P0, Pcu=Pcu: x * S * pf / (x * S * pf + P0 + x**2 * Pcu)

print("load   pf 1.0    pf 0.8")
for x in (0.1, 0.25, 0.5, 0.75, 1.0, 1.25):
    print(f"{x:4.2f}  {eta(x, 1)*100:7.3f} %  {eta(x, 0.8)*100:7.3f} %")
xm = np.sqrt(P0 / Pcu)
print(f"maximum efficiency at x = {xm:.3f} ({xm*S/1e3:.1f} kVA): {eta(xm, 1)*100:.3f} % at pf 1, {eta(xm, 0.8)*100:.3f} % at pf 0.8")

# all-day efficiency: (hours, per-unit load, power factor) for a typical day
day = [(8, 0.2, 0.9), (6, 0.5, 0.85), (6, 0.8, 0.8), (4, 1.0, 0.8)]
for name, p0, pcu in (("T1", P0, Pcu), ("low-loss core", 60.0, 520.0)):
    Eout = sum(h * x * S * pf for h, x, pf in day)
    Ecore = 24 * p0
    Ecu = sum(h * x**2 * pcu for h, x, pf in day)
    print(f"{name:13s}: out {Eout/1e3:6.1f} kWh, core {Ecore/1e3:.2f} kWh, copper {Ecu/1e3:.2f} kWh, "
          f"all-day efficiency {Eout/(Eout+Ecore+Ecu)*100:.3f} %, full-load efficiency {eta(1, 0.8, p0, pcu)*100:.3f} %")
load   pf 1.0    pf 0.8
0.10   97.572 %   96.983 %
0.25   98.832 %   98.545 %
0.50   99.085 %   98.859 %
0.75   99.025 %   98.784 %
1.00   98.887 %   98.612 %
1.25   98.717 %   98.402 %
maximum efficiency at x = 0.520 (26.0 kVA): 99.086 % at pf 1, 98.860 % at pf 0.8
T1           : out  551.5 kWh, core 2.88 kWh, copper 4.28 kWh, all-day efficiency 98.718 %, full-load efficiency 98.612 %
low-loss core: out  551.5 kWh, core 1.44 kWh, copper 5.02 kWh, all-day efficiency 98.842 %, full-load efficiency 98.571 %

The efficiency curve is flat over a wide range (above 98.5 % from a quarter load to beyond full load at pf 0.80.8) and drops sharply at very light load, where the constant core loss dominates. The second design halves the core loss at the cost of 17 % more copper loss: it is worse at full load but better over the day, and since its core loss is paid for every hour of 30 years or more, it is usually the better buy. Utilities compare offers with loss capitalisation: a price per watt of no-load loss and a lower price per watt of load loss, added to the purchase price.

Interactive: regulation against load

The series model of T1 in the netlist lab, now with a resistive load (calculation only). At the default 115.2 Ω115.2\ \Omega (full load at unity power factor, referred to HV) the output is V(h)=2.378 kVV(h) = 2.378\ \text{kV}, a regulation of (2400−2378)/2378=0.9 %(2400 - 2378)/2378 = 0.9\ \%, close to the 0.94 %0.94\ \% of the phasor lesson's table. Halve RL toward 57.6 Ω57.6\ \Omega (twice full load) and the drop roughly doubles; raise it toward 11.5 kΩ11.5\ \text{k}\Omega (1 % load) and the output approaches 2400 V2400\ \text{V}. The lab also sweeps frequency on its plot; only the readouts at the 50 Hz50\ \text{Hz} cursor matter here.

010002000100m1101001k10kf (Hz)|V| (V)|V(h)|phasors at f = 50.00 Hz (magnitude @ phase)V(p)2.40 kV @ 0.0 degV(e)2.38 kV @ 0.0 degV(h)2.38 kV @ -1.6 degI(V1)20.6 A @ 178.4 degI(REQ)20.6 A @ -1.6 degI(LEQ)20.6 A @ -1.6 degI(RL)20.6 A @ -1.6 deg

Regulations on transformer losses

Many countries set maximum losses for new distribution transformers. In the European Union, Commission Regulation (EU) No 548/2014 (amended by (EU) 2019/1783) sets limits on no-load and load losses by rating, with a stricter "Tier 2" from 1 July 2021; IEC TS 60076-20 defines efficiency indices such as the peak efficiency index (PEI). Utilities in other regions use their own tables (for example the US DOE efficiency limits for distribution transformers in 10 CFR 431, subpart K; a DOE final rule issued in 2024 tightens them, with compliance from April 2029; DOE reopened it for comment in 2026). These figures change over time; the editions and dates here are as of 2026 and should be checked against the current texts.

Guided lab: efficiency of a small low-voltage converter as a stand-in

A transformer efficiency test needs mains power. The same two-loss model can be practised safely on any low-voltage power converter with a fixed loss and a load-dependent loss.

Hand calculation. For a small 12 V12\ \text{V} to 5 V5\ \text{V} DC-DC module, assume a fixed loss P0P_0 and a loss kI2k I^2, and predict where the efficiency peaks: at I=P0/kI = \sqrt{P_0/k}.

Simulation. Fit P0P_0 and kk to your measured losses (Pin−PoutP_\text{in} - P_\text{out}) with np.polyfit(I, loss, 2) and replot η(I)\eta(I) with the program's formula.

What you would measure. Power the module from a current-limited bench supply at 12 V12\ \text{V}, load it with power resistors (or an electronic load) from about 5 %5\ \% to 100 %100\ \% of its rating, and read input and output voltage and current with two DMMs. Expect efficiencies of 80 to 95 % with a peak at part load, and a no-load input power of tens of milliwatts. Errors of ±0.5 %\pm 0.5\ \% on each reading give about ±1\pm 1 point on η\eta, which is why transformer efficiency is never measured by input minus output but from the separate losses.

Hazards and safe setup. Low voltage only, supply current limit set just above the expected input current. Power resistors get hot: mount them on a heat sink or a ceramic tile, and don't touch them while loaded.

Pitfalls

  • Using P0P_0 at the wrong voltage. Core loss depends on flux; at a different supply voltage use a new OC reading.
  • Forgetting that PcuP_\text{cu} scales with x2x^2, not xx.
  • Judging a distribution transformer by its full-load efficiency. Energy over its load profile is what costs money.
  • Mixing regulation definitions. State whether V1V_1 is held constant (as here) and at which load and power factor.

Practice

  1. Find T1's efficiency at half load, pf 0.90.9 lagging.
  2. A 100 kVA100\ \text{kVA} transformer has P0=300 WP_0 = 300\ \text{W} and Pcu=1200 WP_\text{cu} = 1200\ \text{W}. At what load is its efficiency maximum, and what is that efficiency at pf 1?
  3. T1 supplies a leading load at rated current, pf 0.80.8. Estimate the regulation.
Answer
  1. η=0.5⋅50 000⋅0.9/(22 500+120+0.25⋅443)=22 500/22 730.75=98.98 %\eta = 0.5 \cdot 50\,000 \cdot 0.9/(22\,500 + 120 + 0.25 \cdot 443) = 22\,500/22\,730.75 = 98.98\ \%.
  2. x=300/1200=0.5x = \sqrt{300/1200} = 0.5 (50 kVA); η=50 000/(50 000+300+300)=98.81 %\eta = 50\,000/(50\,000 + 300 + 300) = 98.81\ \%.
  3. sin⁡φ=−0.6\sin\varphi = -0.6: 0.00885⋅0.8−0.0278⋅0.6+12(0.0278⋅0.8+0.00885⋅0.6)2=0.00708−0.01667+0.00038=−0.92 %0.00885 \cdot 0.8 - 0.0278 \cdot 0.6 + \tfrac12(0.0278 \cdot 0.8 + 0.00885 \cdot 0.6)^2 = 0.00708 - 0.01667 + 0.00038 = -0.92\ \%: the output rises at full load.

Test yourself

A transformer's efficiency is maximum when…

  1. it is at full load
  2. copper loss equals core loss
  3. core loss is zero
  4. the power factor is lagging

T1 has P0=120P_0 = 120 W and Pcu=443P_\text{cu} = 443 W. At what fraction of rated load is its efficiency highest?

  1. 0.27
  2. 0.52
  3. 0.75
  4. 1.0

Why can a design with higher full-load losses have a better all-day efficiency?

  1. it runs cooler
  2. its lower core loss is saved every hour, while its higher copper loss only matters at high load
  3. copper loss is free
  4. all-day efficiency ignores the core

Regulation can be negative when the load is…

  1. resistive
  2. lagging
  3. leading
  4. very small