Voltage Regulation, Efficiency and All-Day Efficiency
Two numbers decide whether a transformer is good for a job. Voltage regulation says how much the output sags from no load to full load: too much, and lamps dim and motors stall at the end of a long feeder. Efficiency says how much energy it wastes: at 98.6 %, a unit at full load still turns more than half a kilowatt into heat. For a distribution transformer that is lightly loaded most of the day, the useful figure is not even the full-load efficiency but the all-day (energy) efficiency. This lesson computes all three for transformer T1 from its test results (Open-Circuit and Short-Circuit Tests).
Safety: T1 is a transformer; everything here is calculation and simulation.
Voltage regulation
With the primary voltage held constant, regulation compares the secondary voltage at no load with the value at the stated load:
At no load (the shunt current's drop is negligible), so referred to the primary , exactly the quantity the phasor diagram gave in Transformer Phasor Diagrams:
with the per-unit drops at the stated current, , , and for lagging loads. Regulation is positive for lagging and resistive loads, and can be negative for leading ones. Distribution transformers often have off-circuit tap changers (typically ) to set the no-load ratio for the feeder they sit on; large power transformers have on-load tap changers.
Efficiency
The losses are the no-load loss (the core, present whenever the transformer is energised, the OC-test power) and the load loss at rated current (the SC-test power), which scales with the square of the load. At a fraction of the rated apparent power and power factor :
Setting shows that the efficiency is largest when the variable loss equals the constant loss:
This rule holds for every machine with a constant loss and an loss, DC and induction motors included (DC Machine Losses and Efficiency). Designers place the maximum where the machine spends most of its time: distribution transformers, which carry around a third to a half of their rating on average, are built with relatively low core loss.
Worked example: T1 at full load
Given: T1, , , , (HV side), , at rated current; load at rated current, power factor lagging.
Find: the regulation, the efficiency, and the load for maximum efficiency.
Solve: rated HV current , so and :
Check: the exact circuit gave for (the equivalent circuit), so ; the formula is within points. The losses at full load, , are of the output: right for a transformer of this size.
In Python: efficiency curves and a day of load
import numpy as np
S, P0, Pcu = 50e3, 120.0, 443.0 # T1: rating, no-load loss, full-load copper loss (W)
eta = lambda x, pf, P0=P0, Pcu=Pcu: x * S * pf / (x * S * pf + P0 + x**2 * Pcu)
print("load pf 1.0 pf 0.8")
for x in (0.1, 0.25, 0.5, 0.75, 1.0, 1.25):
print(f"{x:4.2f} {eta(x, 1)*100:7.3f} % {eta(x, 0.8)*100:7.3f} %")
xm = np.sqrt(P0 / Pcu)
print(f"maximum efficiency at x = {xm:.3f} ({xm*S/1e3:.1f} kVA): {eta(xm, 1)*100:.3f} % at pf 1, {eta(xm, 0.8)*100:.3f} % at pf 0.8")
# all-day efficiency: (hours, per-unit load, power factor) for a typical day
day = [(8, 0.2, 0.9), (6, 0.5, 0.85), (6, 0.8, 0.8), (4, 1.0, 0.8)]
for name, p0, pcu in (("T1", P0, Pcu), ("low-loss core", 60.0, 520.0)):
Eout = sum(h * x * S * pf for h, x, pf in day)
Ecore = 24 * p0
Ecu = sum(h * x**2 * pcu for h, x, pf in day)
print(f"{name:13s}: out {Eout/1e3:6.1f} kWh, core {Ecore/1e3:.2f} kWh, copper {Ecu/1e3:.2f} kWh, "
f"all-day efficiency {Eout/(Eout+Ecore+Ecu)*100:.3f} %, full-load efficiency {eta(1, 0.8, p0, pcu)*100:.3f} %")load pf 1.0 pf 0.8
0.10 97.572 % 96.983 %
0.25 98.832 % 98.545 %
0.50 99.085 % 98.859 %
0.75 99.025 % 98.784 %
1.00 98.887 % 98.612 %
1.25 98.717 % 98.402 %
maximum efficiency at x = 0.520 (26.0 kVA): 99.086 % at pf 1, 98.860 % at pf 0.8
T1 : out 551.5 kWh, core 2.88 kWh, copper 4.28 kWh, all-day efficiency 98.718 %, full-load efficiency 98.612 %
low-loss core: out 551.5 kWh, core 1.44 kWh, copper 5.02 kWh, all-day efficiency 98.842 %, full-load efficiency 98.571 %
The efficiency curve is flat over a wide range (above 98.5 % from a quarter load to beyond full load at pf ) and drops sharply at very light load, where the constant core loss dominates. The second design halves the core loss at the cost of 17 % more copper loss: it is worse at full load but better over the day, and since its core loss is paid for every hour of 30 years or more, it is usually the better buy. Utilities compare offers with loss capitalisation: a price per watt of no-load loss and a lower price per watt of load loss, added to the purchase price.
Interactive: regulation against load
The series model of T1 in the netlist lab, now with a resistive load (calculation only). At the default (full load at unity power factor, referred to HV) the output is , a regulation of , close to the of the phasor lesson's table. Halve RL toward (twice full load) and the drop roughly doubles; raise it toward (1 % load) and the output approaches . The lab also sweeps frequency on its plot; only the readouts at the cursor matter here.
Regulations on transformer losses
Many countries set maximum losses for new distribution transformers. In the European Union, Commission Regulation (EU) No 548/2014 (amended by (EU) 2019/1783) sets limits on no-load and load losses by rating, with a stricter "Tier 2" from 1 July 2021; IEC TS 60076-20 defines efficiency indices such as the peak efficiency index (PEI). Utilities in other regions use their own tables (for example the US DOE efficiency limits for distribution transformers in 10 CFR 431, subpart K; a DOE final rule issued in 2024 tightens them, with compliance from April 2029; DOE reopened it for comment in 2026). These figures change over time; the editions and dates here are as of 2026 and should be checked against the current texts.
Guided lab: efficiency of a small low-voltage converter as a stand-in
A transformer efficiency test needs mains power. The same two-loss model can be practised safely on any low-voltage power converter with a fixed loss and a load-dependent loss.
Hand calculation. For a small to DC-DC module, assume a fixed loss and a loss , and predict where the efficiency peaks: at .
Simulation. Fit and to your measured losses () with np.polyfit(I, loss, 2) and replot with the program's formula.
What you would measure. Power the module from a current-limited bench supply at , load it with power resistors (or an electronic load) from about to of its rating, and read input and output voltage and current with two DMMs. Expect efficiencies of 80 to 95 % with a peak at part load, and a no-load input power of tens of milliwatts. Errors of on each reading give about point on , which is why transformer efficiency is never measured by input minus output but from the separate losses.
Hazards and safe setup. Low voltage only, supply current limit set just above the expected input current. Power resistors get hot: mount them on a heat sink or a ceramic tile, and don't touch them while loaded.
Pitfalls
- Using at the wrong voltage. Core loss depends on flux; at a different supply voltage use a new OC reading.
- Forgetting that scales with , not .
- Judging a distribution transformer by its full-load efficiency. Energy over its load profile is what costs money.
- Mixing regulation definitions. State whether is held constant (as here) and at which load and power factor.
Practice
- Find T1's efficiency at half load, pf lagging.
- A transformer has and . At what load is its efficiency maximum, and what is that efficiency at pf 1?
- T1 supplies a leading load at rated current, pf . Estimate the regulation.
Answer
- .
- (50 kVA); .
- : : the output rises at full load.
Test yourself
A transformer's efficiency is maximum when…
- it is at full load
- copper loss equals core loss
- core loss is zero
- the power factor is lagging
T1 has W and W. At what fraction of rated load is its efficiency highest?
- 0.27
- 0.52
- 0.75
- 1.0
Why can a design with higher full-load losses have a better all-day efficiency?
- it runs cooler
- its lower core loss is saved every hour, while its higher copper loss only matters at high load
- copper loss is free
- all-day efficiency ignores the core
Regulation can be negative when the load is…
- resistive
- lagging
- leading
- very small