From the Ideal to the Real Transformer: the Equivalent Circuit
The ideal transformer of Ideal Transformers and Impedance Reflection gives at any load. A real , distribution transformer fed with exactly delivers about with no load, but only about at full load and a lagging power factor; it draws a quarter of an ampere even with nothing connected, and it warms up whether loaded or not. Every one of those effects is a small, separate imperfection, and each becomes one element of the equivalent circuit. This lesson builds that circuit, which the next seven lessons use for tests, regulation, efficiency and three-phase banks.
Safety: the example transformer works at . It is studied by calculation and simulation only; the hands-on part uses a small signal transformer at signal-generator levels.
Four imperfections, four elements
| Imperfection | Effect | Element |
|---|---|---|
| copper windings have resistance | heating, voltage drop in phase with current | , in series |
| some flux links only one winding (leakage) | voltage drop leading the current by | leakage reactances , in series |
| the core needs MMF to carry flux | a no-load current lagging by | magnetising reactance in shunt |
| hysteresis and eddy currents heat the core | a no-load current in phase with | core-loss resistance in shunt |
The shunt elements come from B–H Curves and Magnetising Current and Core Losses; both depend on the flux, so they are fixed only near rated voltage and frequency. The series elements depend on the current.
From coupled coils to the T circuit
Two windings with self-inductances , and mutual inductance (Mutual Inductance) can be redrawn for any turns ratio . Define the magnetising inductance referred to winding 1 and the two leakage inductances:
Then the coupled pair is exactly a T of , and followed by an ideal transformer. The coupling coefficient is ; power transformers have above , so the leakage inductances are tiny compared with , but they still set the full-load voltage drop and the short-circuit current.
Referring to one side. Moving an impedance across an ideal transformer multiplies it by toward the high-voltage side; voltages scale by and currents by :
After referring the LV winding and the load to the HV side, the ideal transformer can be dropped, and the whole device is one circuit.
Worked example: the transformer T1 at full load
The course's single-phase example transformer T1: , , , , , , , and (referred to HV) , .
Given: T1 delivering rated current at , power factor lagging.
Find: the referred LV impedances and the primary voltage and current needed.
Solve: , so and . Rated LV current , referred at with .
Check: the supply must be above to hold at full load, a typical figure for a transformer with about 3 % impedance. The input power exceeds the output by : copper loss in and plus core loss in .
In Python: solve the exact circuit both ways
import numpy as np
# transformer T1: 50 kVA, 2400/240 V, 50 Hz; HV winding R1, X1; LV winding R2, X2; shunt branch referred to HV
S, V1n, V2n = 50e3, 2400.0, 240.0
R1, X1, R2, X2, Rc, Xm = 0.50, 1.6, 0.0052, 0.016, 48e3, 9.6e3
a = V1n / V2n
Z1, Z2r = R1 + 1j * X1, a**2 * (R2 + 1j * X2) # HV winding, LV winding referred to HV
Ysh = 1 / Rc + 1 / (1j * Xm)
pol = lambda z: f"{abs(z):8.2f} at {np.degrees(np.angle(z)):7.2f} deg"
# (a) rated load at the LV terminals: 240 V, 208.3 A, pf 0.8 lagging; what must V1 be?
V2r = a * V2n + 0j
I2r = (S / V2n) / a * np.exp(-1j * np.arccos(0.8))
VE = V2r + I2r * Z2r # voltage across the shunt branch
I1 = I2r + VE * Ysh
V1 = VE + I1 * Z1
print("referred: R2' =", round(a**2 * R2, 3), "Ohm, X2' =", round(a**2 * X2, 3), "Ohm")
print("V1 =", pol(V1), "V I1 =", pol(I1), "A")
print(f"input P = {(V1 * np.conj(I1)).real:.0f} W, output P = {(V2r * np.conj(I2r)).real:.0f} W")
# (b) the same load impedance on a 2400 V supply: what does the LV side get?
ZL = V2n / ((S / V2n) * np.exp(-1j * np.arccos(0.8))) # 1.152 Ohm at 36.87 deg
Zin = Z1 + 1 / (Ysh + 1 / (Z2r + a**2 * ZL))
I1 = V1n / Zin
VE = V1n - I1 * Z1
V2 = VE * (a**2 * ZL) / (Z2r + a**2 * ZL) / a
print(f"load ZL = {ZL.real:.4f} + j{ZL.imag:.4f} Ohm; with V1 = 2400 V: V2 = {pol(V2)} V")referred: R2' = 0.52 Ohm, X2' = 1.6 Ohm
V1 = 2457.76 at 0.95 deg V I1 = 21.03 at -37.33 deg A
input P = 40570 W, output P = 40000 W
load ZL = 0.9216 + j0.6912 Ohm; with V1 = 2400 V: V2 = 234.36 at -0.95 deg V
Part (b) is the everyday view: with the supply fixed at , the full-load impedance gets instead of .
Cross-check in SPICE: coupled coils against the T circuit
ngspice models a transformer as two inductors and a coupling coefficient K. With , : , and . The deck runs both models side by side at into the full-load impedance.
cat > t1.cir <<'EOF'
* T1 at rated load: coupled inductors (K) against the T equivalent referred to HV
V1 p 0 AC 2400
R1 p a 0.5
LP a 0 30.56284
LS b 0 0.3056284
K1 LP LS 0.999833
R2 b c 0.0052
RL c d 0.9216
LL d 0 2.2001m
* T equivalent, LV side referred to HV (a = 10)
V2 q 0 AC 2400
R1T q e 0.5
L1T e f 5.093m
RC f 0 48k
LM f 0 30.5577
R2T f g 0.52
L2T g h 5.093m
RLT h k 92.16
LLT k 0 0.22001
.control
ac lin 1 50 50
let v2coupled = vm(c)
let v2tee = vm(h)/10
print v2coupled v2tee vp(c)*180/pi
.endc
.end
EOF
ngspice -b t1.cir 2>&1 | grep -E '^(v2|vp)'v2coupled = 2.343532e+02
v2tee = 2.343592e+02
vp(c)*180/pi = -9.45953e-01
Both give at , matching Python. The difference comes from rounding to six digits: it gives the coupled pair leakage inductances of instead of . The coupled pair also lacks the core-loss resistor , which a pair of inductors cannot represent (in the T circuit it lowers by about ).
Interactive: T1 referred to the HV side
The netlist lab solves the same T circuit at (calculation only: a supply). Node h is and node f the voltage across the shunt branch. At the default full-load impedance ( in series with ) the lab shows at , so , and through the magnetising branch. Raise RL toward (a light load) and watch climb toward . The lab also sweeps frequency on its plot; only the readouts at the cursor matter here.
Guided lab: equivalent circuit of a small signal transformer
Hand calculation. For a audio or line transformer, an LCR meter reading of the primary inductance with the secondary open gives ; with the secondary shorted it gives about (because is shunted). Assume the leakage splits equally.
Simulation. Put your values into the netlist lab (replace the numbers, use a source and a frequency in the transformer's band, say ) or into the Python program.
What you would measure. Measure both winding resistances with a DMM, then open and shorted with an LCR meter at and low test level (LCR Meters). Typical small line transformers show of henries and leakage of millihenries, so above . Expect the open-circuit inductance to vary by with test level and frequency (the core is nonlinear), and the shorted reading to be stable within a few percent.
Hazards and safe setup. Signal transformers and LCR-meter levels only. Do not use a mains transformer: driving one of its low-voltage windings, even from a small source, produces a high voltage on the mains winding.
Pitfalls
- Referring the wrong way. Toward the HV side, impedances multiply by with ; toward the LV side they divide.
- Putting and in series. They are in parallel: two currents, one in phase, one in quadrature, sharing the same voltage.
- Treating the shunt branch as fixed. It is a small-signal model at rated ; it does not predict saturation or inrush.
- Expecting SPICE
Kto include core loss. Add a resistor if you need it.
Practice
- Refer T1's HV winding impedance to the LV side.
- With the LV side open and applied, what current does T1 draw (exact circuit) and at what power factor?
- Find T1's leakage inductances and the coupling coefficient if were instead.
Answer
- .
- Essentially , , pf lagging (the series changes this by less than 0.1 %).
- Leakage unchanged, each; , .
Test yourself
Which element of the equivalent circuit represents leakage flux?
- the series reactances and
- the winding resistances
An LV impedance of on a 2400/240 V transformer, referred to the HV side, is…
The no-load current of a transformer has a component in phase with the voltage. What does it supply?
- copper loss
- core (iron) loss
- magnetising MMF
- leakage flux
T1 is fed with exactly 2400 V and loaded with its full-load impedance at pf 0.8 lagging. Its LV voltage is about…
- 240 V
- 246 V
- 234 V
- 216 V