Ratings, Duty Cycles and IE Efficiency Classes
Every machine in this course has a rating: the output it can deliver continuously without overheating, at stated voltage, frequency, ambient temperature and altitude. The rating is a thermal promise, not a magnetic limit: a motor can produce two or three times its rated torque for a few seconds, and the same frame can be rated higher for short duty or lower for frequent starts. Since the 2010s, motor choice has also been a legal matter: in many countries a new industrial induction motor must meet a minimum efficiency class. This lesson reads a nameplate, explains the IEC duty types, sizes a motor for a cycle with a thermal model, and works out what an efficiency class is worth in energy and money.
The nameplate
A motor nameplate (IEC style) typically states:
| Field | Meaning |
|---|---|
| Rated output, e.g. | mechanical shaft power (for motors) at rated conditions; for generators the electrical output; transformers in kVA |
| / Y, | the winding connection for each supply voltage (Starting Methods) |
| Rated current, power factor, speed | at rated output; speed tells you the slip and the number of poles |
| Efficiency and IE class | at full (and often 75 %, 50 %) load, measured to IEC 60034-2-1 |
| Duty (S1…S10) | the load pattern the rating applies to; S1 if not stated |
| Insulation class, temperature rise | e.g. "Ins. cl. F, temperature rise class B" (Cooling, Insulation Classes) |
| IP and IC codes | enclosure protection (IP55) and cooling method (IC 411) |
| Ambient, altitude | usually up to and ; above that the motor must be derated |
The main IEC standard is IEC 60034-1 (Rotating electrical machines – Part 1: Rating and performance; edition 15.0, March 2026, which replaced the 2022 edition). North American motors follow NEMA MG 1 and often add a service factor (1.15 means a continuous 15 % overload is allowed at a higher temperature); IEC motors have no service factor.
Duty types S1 to S10
IEC 60034-1 defines ten duty types:
| Duty | Name | Example designation |
|---|---|---|
| S1 | continuous running | S1 |
| S2 | short-time | S2 30 min |
| S3 | intermittent periodic (starting does not heat the motor) | S3 25 % |
| S4 | intermittent periodic with starting | S4 40 %, with starts per hour and inertia |
| S5 | intermittent periodic with electric braking | S5 … |
| S6 | continuous-operation periodic (load and no-load, never stopped) | S6 40 % |
| S7 | continuous-operation periodic with electric braking | S7 … |
| S8 | continuous-operation periodic with related load/speed changes | S8 … |
| S9 | non-periodic load and speed variations (drives) | S9 |
| S10 | discrete constant loads and speeds | S10 |
The periodic duties assume a cycle of at most unless stated, with the cyclic duration factor (the % on load) in the designation. For a quick check of a varying load on an S1 motor, engineers compute the rms-equivalent power (losses grow roughly with current squared, and current roughly with power):
which works when the cycle is much shorter than the motor's thermal time constant (tens of minutes for medium motors). A thermal model, below, is the better check.
Efficiency classes
IEC 60034-30-1 (first edition 2014; second edition December 2025) defines efficiency classes for line-operated motors from to (2, 4, 6 and 8 poles, and ): IE1 (standard), IE2 (high), IE3 (premium), IE4 (super premium). IE5 (ultra premium) has roughly 20 % lower losses than IE4; its limits were first set for variable-speed (converter-fed) motors in IEC TS 60034-30-2:2016, and the 2025 second edition of IEC 60034-30-1 added IE5 tables for line-operated motors (its foreword lists no change to the IE1 to IE4 limits). Each class is a table of minimum efficiency by power and pole number; for 4-pole motors, for example:
| Rated power | IE2 | IE3 | IE4 |
|---|---|---|---|
| 88.7 % | 90.4 % | 92.6 % | |
| 89.8 % | 91.4 % | 93.3 % |
In the European Union, Commission Regulation (EU) 2019/1781 (ecodesign for motors and variable speed drives, amended by (EU) 2021/341) has required since 1 July 2021 at least IE3 for 3-phase motors of to (2 to 8 poles) and IE2 for to , and since 1 July 2023 IE4 for to (2, 4 and 6 poles), with some exemptions. Other regions have similar rules (for example the US DOE rules based on NEMA Premium). Dates and thresholds change: check the current text of the regulation that applies to you.
Higher classes mean more and better copper and steel, longer cores, better fans and bearings. They often also mean lower slip, so an IE4 motor runs a little faster than the IE2 it replaces; on a centrifugal pump or fan (power ) part of the saving is eaten by the extra flow unless the pump is retuned.
Worked example: what IE3 saves
Given: a , 4-pole, pump motor delivering of rating () for ; electricity at per kWh (an assumed 2026 industrial price; use your own); efficiencies taken from the table above (the 75 % load efficiency is close to the full-load value for motors of this size).
Find: the annual energy for IE2, IE3 and IE4 and the savings against IE2.
Solve:
Check: the losses fall from to , 17 % less, consistent with each IE step cutting losses by roughly 15 to 20 %. Over a 15-year life the energy bill of this motor (about , per year) is many times its purchase price, which is why efficiency usually pays. This is a three-phase motor: calculation only.
In Python: class savings and a duty-cycle check
import numpy as np
# 1) energy cost of efficiency classes: 11 kW, 4-pole, 50 Hz pump motor at 75 % load, 6000 h/year
# nominal efficiencies at rated load from the IEC 60034-30-1 table (used here as an approximation at 75 %)
eta = {"IE2": 0.898, "IE3": 0.914, "IE4": 0.933}
P_shaft, hours, price = 0.75 * 11.0, 6000, 0.20 # kW, h/year, currency per kWh (assumed)
base = P_shaft / eta["IE2"]
for cls, e in eta.items():
Pin = P_shaft / e
print(f"{cls}: input {Pin:.3f} kW, losses {Pin-P_shaft:.3f} kW, "
f"energy {Pin*hours:7.0f} kWh/yr, saving vs IE2 {(base-Pin)*hours:4.0f} kWh = {(base-Pin)*hours*price:4.0f} per year")
# 2) a duty cycle on a motor rated 7.5 kW S1: first-order thermal model
# losses = constant part + load part (P/Pr)^2; steady temperature rise proportional to losses
Pr, P0, Pcu_r, tau = 7.5, 0.25, 0.55, 30.0 # kW rated, kW constant losses, kW load losses at rated, min
rise_rated = 80.0 # K at rated S1 load (the design target here)
k = rise_rated / (P0 + Pcu_r) # K per kW of loss
cycle = [(15.0, 2.0), (5.0, 6.0), (0.0, 2.0)] # (kW, minutes): heavy, light, idle
Peq = np.sqrt(sum(P**2 * t for P, t in cycle) / sum(t for _, t in cycle))
print(f"\nrms-equivalent load of the cycle: {Peq:.2f} kW (rating {Pr} kW)")
dt, theta, t_end, peak = 0.01, 0.0, 600.0, []
t = 0.0
while t < t_end:
for P, dur in cycle:
for _ in range(int(round(dur / dt))):
loss = P0 + Pcu_r * (P / Pr) ** 2
theta += dt * (k * loss - theta) / tau # tau dtheta/dt = k*loss - theta
peak.append(theta)
t += dur
print(f"temperature rise after 10 h of cycling: peak {max(peak[-3:]):.1f} K, "
f"minimum {min(peak[-3:]):.1f} K (S1 rated: {rise_rated:.0f} K)")IE2: input 9.187 kW, losses 0.937 kW, energy 55122 kWh/yr, saving vs IE2 0 kWh = 0 per year
IE3: input 9.026 kW, losses 0.776 kW, energy 54158 kWh/yr, saving vs IE2 965 kWh = 193 per year
IE4: input 8.842 kW, losses 0.592 kW, energy 53055 kWh/yr, saving vs IE2 2068 kWh = 414 per year
rms-equivalent load of the cycle: 7.75 kW (rating 7.5 kW)
temperature rise after 10 h of cycling: peak 88.7 K, minimum 78.0 K (S1 rated: 80 K)
The cycle ( for 2 min, for 6 min, idle 2 min) has an rms-equivalent of , 3 % above the rating, and the thermal model agrees that the motor runs too hot: its winding rise cycles between 78 and 89 K against the 80 K it was designed for. Choose the next frame size, or accept it only if the insulation class leaves margin (next lesson).
Interactive: the motor seen from the supply
An motor near full load on a supply looks to the network like a balanced star load. With and per phase the three-phase lab shows , , power factor and per line: an input that, at the IE3 efficiency of 91.4 %, delivers about at the shaft. Calculation only: mains voltages.
Guided lab: rate a small motor yourself
Hand calculation. For a small PMDC motor, use the model of DC Machine Losses to predict input power, output power and losses at the load you plan to run.
Simulation. Put a duty cycle of your own (for example a window lifter: 5 s on, 55 s off) into the thermal loop, with a thermal time constant of a few minutes for a small motor.
What you would measure. Run the motor on the load at its rated voltage from a current-limited supply; record voltage, current and speed every minute, and the case temperature with a thermocouple taped to the can (or the winding resistance, next lesson). Find the steady rise for continuous duty, then repeat with an on/off cycle and compare the peak rise. Expect continuous and cycled rises to scale with the average loss within about 15 %; case temperature lags the winding.
Hazards and safe setup. At most , current-limited; clamp the motor and its load; keep fingers and hair away from pulleys. Stop if the case passes : magnet motors can be damaged and hot cases burn. Do not leave the test unattended.
Pitfalls
- Rated output is shaft power. Input power is higher by , and the apparent power higher still by .
- Oversizing. A motor at 30 % load has poorer efficiency and power factor; buy the size the load needs.
- Ignoring ambient and altitude. At or the same motor must be derated.
- Assuming the rms method covers frequent starts. Starting currents are five to eight times rated in induction motors; that is what S4 and S5 ratings are for.
Practice
- A 4-pole motor runs at full load for . Find the annual saving in kWh of IE4 over IE2 (table values).
- A cycle is for 3 min and for 7 min. Find .
- Classify: a crane hoist motor that lifts for 30 s, waits for 90 s, and repeats all day, starting each time.
Answer
- ; times : about .
- .
- S4 (intermittent periodic duty with starting), cyclic duration factor .
Test yourself
The rated output on a motor's nameplate is…
- electrical input power
- apparent power in kVA
- mechanical shaft power
- the maximum power for one minute
Duty type S1 means…
- short-time duty
- continuous running at constant load long enough to reach thermal equilibrium
- intermittent duty with starting
- non-periodic variable load
Since 1 July 2021, EU Regulation 2019/1781 requires which minimum class for a new 11 kW 4-pole three-phase motor?
- IE1
- IE2
- IE3
- IE5
A load cycle is 15 kW for 2 min, 5 kW for 6 min and 0 for 2 min. Its rms-equivalent power is about…
- 6.0 kW
- 7.75 kW
- 10 kW
- 15 kW