Home › Electrical Machines & Transformers › Ratings, Duty Cycles and IE Efficiency Classes

Ratings, Duty Cycles and IE Efficiency Classes

Every machine in this course has a rating: the output it can deliver continuously without overheating, at stated voltage, frequency, ambient temperature and altitude. The rating is a thermal promise, not a magnetic limit: a motor can produce two or three times its rated torque for a few seconds, and the same frame can be rated higher for short duty or lower for frequent starts. Since the 2010s, motor choice has also been a legal matter: in many countries a new industrial induction motor must meet a minimum efficiency class. This lesson reads a nameplate, explains the IEC duty types, sizes a motor for a cycle with a thermal model, and works out what an efficiency class is worth in energy and money.

The nameplate

A motor nameplate (IEC style) typically states:

Field Meaning
Rated output, e.g. 11 kW11\ \text{kW} mechanical shaft power (for motors) at rated conditions; for generators the electrical output; transformers in kVA
400 V400\ \text{V} Δ\Delta / 690 V690\ \text{V} Y, 50 Hz50\ \text{Hz} the winding connection for each supply voltage (Starting Methods)
Rated current, power factor, speed at rated output; speed tells you the slip and the number of poles
Efficiency and IE class at full (and often 75 %, 50 %) load, measured to IEC 60034-2-1
Duty (S1…S10) the load pattern the rating applies to; S1 if not stated
Insulation class, temperature rise e.g. "Ins. cl. F, temperature rise class B" (Cooling, Insulation Classes)
IP and IC codes enclosure protection (IP55) and cooling method (IC 411)
Ambient, altitude usually up to 40 ∘C40\,^\circ\text{C} and 1000 m1000\ \text{m}; above that the motor must be derated

The main IEC standard is IEC 60034-1 (Rotating electrical machines – Part 1: Rating and performance; edition 15.0, March 2026, which replaced the 2022 edition). North American motors follow NEMA MG 1 and often add a service factor (1.15 means a continuous 15 % overload is allowed at a higher temperature); IEC motors have no service factor.

Duty types S1 to S10

S1 continuous constant load,steady temperature S2 short-time load for a set time,then rest to ambient S3 intermittent identical on/off cycles,e.g. S3 40 % on load (solid)temperature (dashed)

IEC 60034-1 defines ten duty types:

Duty Name Example designation
S1 continuous running S1
S2 short-time S2 30 min
S3 intermittent periodic (starting does not heat the motor) S3 25 %
S4 intermittent periodic with starting S4 40 %, with starts per hour and inertia
S5 intermittent periodic with electric braking S5 …
S6 continuous-operation periodic (load and no-load, never stopped) S6 40 %
S7 continuous-operation periodic with electric braking S7 …
S8 continuous-operation periodic with related load/speed changes S8 …
S9 non-periodic load and speed variations (drives) S9
S10 discrete constant loads and speeds S10

The periodic duties assume a cycle of at most 10 min10\ \text{min} unless stated, with the cyclic duration factor (the % on load) in the designation. For a quick check of a varying load on an S1 motor, engineers compute the rms-equivalent power (losses grow roughly with current squared, and current roughly with power):

Peq=∑Pi2 ti∑tiP_\text{eq} = \sqrt{\frac{\sum P_i^2\, t_i}{\sum t_i}}

which works when the cycle is much shorter than the motor's thermal time constant (tens of minutes for medium motors). A thermal model, below, is the better check.

Efficiency classes

IEC 60034-30-1 (first edition 2014; second edition December 2025) defines efficiency classes for line-operated motors from 0.120.12 to 1000 kW1000\ \text{kW} (2, 4, 6 and 8 poles, 5050 and 60 Hz60\ \text{Hz}): IE1 (standard), IE2 (high), IE3 (premium), IE4 (super premium). IE5 (ultra premium) has roughly 20 % lower losses than IE4; its limits were first set for variable-speed (converter-fed) motors in IEC TS 60034-30-2:2016, and the 2025 second edition of IEC 60034-30-1 added IE5 tables for line-operated motors (its foreword lists no change to the IE1 to IE4 limits). Each class is a table of minimum efficiency by power and pole number; for 4-pole 50 Hz50\ \text{Hz} motors, for example:

Rated power IE2 IE3 IE4
7.5 kW7.5\ \text{kW} 88.7 % 90.4 % 92.6 %
11 kW11\ \text{kW} 89.8 % 91.4 % 93.3 %

In the European Union, Commission Regulation (EU) 2019/1781 (ecodesign for motors and variable speed drives, amended by (EU) 2021/341) has required since 1 July 2021 at least IE3 for 3-phase motors of 0.750.75 to 1000 kW1000\ \text{kW} (2 to 8 poles) and IE2 for 0.120.12 to 0.75 kW0.75\ \text{kW}, and since 1 July 2023 IE4 for 7575 to 200 kW200\ \text{kW} (2, 4 and 6 poles), with some exemptions. Other regions have similar rules (for example the US DOE rules based on NEMA Premium). Dates and thresholds change: check the current text of the regulation that applies to you.

Higher classes mean more and better copper and steel, longer cores, better fans and bearings. They often also mean lower slip, so an IE4 motor runs a little faster than the IE2 it replaces; on a centrifugal pump or fan (power ∝n3\propto n^3) part of the saving is eaten by the extra flow unless the pump is retuned.

Worked example: what IE3 saves

Given: a 11 kW11\ \text{kW}, 4-pole, 50 Hz50\ \text{Hz} pump motor delivering 75 %75\ \% of rating (8.25 kW8.25\ \text{kW}) for 6000 h/year6000\ \text{h/year}; electricity at 0.200.20 per kWh (an assumed 2026 industrial price; use your own); efficiencies taken from the table above (the 75 % load efficiency is close to the full-load value for motors of this size).

Find: the annual energy for IE2, IE3 and IE4 and the savings against IE2.

Solve:

Pin,IE2=8.25 kW0.898=9.187 kW,Pin,IE3=8.250.914=9.026 kWΔE=(9.187−9.026) kW⋅6000 h=965 kWh/year ⇒ 193 per year\begin{aligned} P_\text{in,IE2} &= \frac{8.25\ \text{kW}}{0.898} = 9.187\ \text{kW}, \qquad P_\text{in,IE3} = \frac{8.25}{0.914} = 9.026\ \text{kW} \\ \Delta E &= (9.187 - 9.026)\ \text{kW} \cdot 6000\ \text{h} = 965\ \text{kWh/year} \ \Rightarrow\ 193\ \text{per year} \end{aligned}

Check: the losses fall from 0.9370.937 to 0.776 kW0.776\ \text{kW}, 17 % less, consistent with each IE step cutting losses by roughly 15 to 20 %. Over a 15-year life the energy bill of this motor (about 55 000 kWh55\,000\ \text{kWh}, 11 00011\,000 per year) is many times its purchase price, which is why efficiency usually pays. This is a 400 V400\ \text{V} three-phase motor: calculation only.

In Python: class savings and a duty-cycle check

python · try it yourself
import numpy as np

# 1) energy cost of efficiency classes: 11 kW, 4-pole, 50 Hz pump motor at 75 % load, 6000 h/year
# nominal efficiencies at rated load from the IEC 60034-30-1 table (used here as an approximation at 75 %)
eta = {"IE2": 0.898, "IE3": 0.914, "IE4": 0.933}
P_shaft, hours, price = 0.75 * 11.0, 6000, 0.20       # kW, h/year, currency per kWh (assumed)
base = P_shaft / eta["IE2"]
for cls, e in eta.items():
    Pin = P_shaft / e
    print(f"{cls}: input {Pin:.3f} kW, losses {Pin-P_shaft:.3f} kW, "
          f"energy {Pin*hours:7.0f} kWh/yr, saving vs IE2 {(base-Pin)*hours:4.0f} kWh = {(base-Pin)*hours*price:4.0f} per year")

# 2) a duty cycle on a motor rated 7.5 kW S1: first-order thermal model
# losses = constant part + load part (P/Pr)^2; steady temperature rise proportional to losses
Pr, P0, Pcu_r, tau = 7.5, 0.25, 0.55, 30.0             # kW rated, kW constant losses, kW load losses at rated, min
rise_rated = 80.0                                      # K at rated S1 load (the design target here)
k = rise_rated / (P0 + Pcu_r)                          # K per kW of loss
cycle = [(15.0, 2.0), (5.0, 6.0), (0.0, 2.0)]          # (kW, minutes): heavy, light, idle
Peq = np.sqrt(sum(P**2 * t for P, t in cycle) / sum(t for _, t in cycle))
print(f"\nrms-equivalent load of the cycle: {Peq:.2f} kW (rating {Pr} kW)")
dt, theta, t_end, peak = 0.01, 0.0, 600.0, []
t = 0.0
while t < t_end:
    for P, dur in cycle:
        for _ in range(int(round(dur / dt))):
            loss = P0 + Pcu_r * (P / Pr) ** 2
            theta += dt * (k * loss - theta) / tau      # tau dtheta/dt = k*loss - theta
        peak.append(theta)
        t += dur
print(f"temperature rise after 10 h of cycling: peak {max(peak[-3:]):.1f} K, "
      f"minimum {min(peak[-3:]):.1f} K (S1 rated: {rise_rated:.0f} K)")
IE2: input 9.187 kW, losses 0.937 kW, energy   55122 kWh/yr, saving vs IE2    0 kWh =    0 per year
IE3: input 9.026 kW, losses 0.776 kW, energy   54158 kWh/yr, saving vs IE2  965 kWh =  193 per year
IE4: input 8.842 kW, losses 0.592 kW, energy   53055 kWh/yr, saving vs IE2 2068 kWh =  414 per year

rms-equivalent load of the cycle: 7.75 kW (rating 7.5 kW)
temperature rise after 10 h of cycling: peak 88.7 K, minimum 78.0 K (S1 rated: 80 K)

The cycle (15 kW15\ \text{kW} for 2 min, 5 kW5\ \text{kW} for 6 min, idle 2 min) has an rms-equivalent of 7.75 kW7.75\ \text{kW}, 3 % above the 7.5 kW7.5\ \text{kW} rating, and the thermal model agrees that the motor runs too hot: its winding rise cycles between 78 and 89 K against the 80 K it was designed for. Choose the next frame size, or accept it only if the insulation class leaves margin (next lesson).

Interactive: the motor seen from the supply

An 11 kW11\ \text{kW} motor near full load on a 400 V400\ \text{V} supply looks to the network like a balanced star load. With R=10 ΩR = 10\ \Omega and X=6 ΩX = 6\ \Omega per phase the three-phase lab shows P=11.67 kWP = 11.67\ \text{kW}, ∣S∣=13.61 kVA|S| = 13.61\ \text{kVA}, power factor 0.85750.8575 and 19.72 A19.72\ \text{A} per line: an input that, at the IE3 efficiency of 91.4 %, delivers about 10.7 kW10.7\ \text{kW} at the shaft. Calculation only: mains voltages.

VaVbVcIaIbIcV solid, I thin (own scale)star, 4-wire-pk0+pk0T2Tphase voltages, peak 325 V-pk0+pk0T2Tline currents, peak 27.9 AP = 11.7 kW Q = 7.00 kvar S = 13.6 kVApf = 0.857 balanced IN = 0 A

Guided lab: rate a small motor yourself

Hand calculation. For a small 12 V12\ \text{V} PMDC motor, use the model of DC Machine Losses to predict input power, output power and losses at the load you plan to run.

Simulation. Put a duty cycle of your own (for example a window lifter: 5 s on, 55 s off) into the thermal loop, with a thermal time constant of a few minutes for a small motor.

What you would measure. Run the motor on the load at its rated voltage from a current-limited supply; record voltage, current and speed every minute, and the case temperature with a thermocouple taped to the can (or the winding resistance, next lesson). Find the steady rise for continuous duty, then repeat with an on/off cycle and compare the peak rise. Expect continuous and cycled rises to scale with the average loss within about 15 %; case temperature lags the winding.

Hazards and safe setup. At most 24 V24\ \text{V}, current-limited; clamp the motor and its load; keep fingers and hair away from pulleys. Stop if the case passes 80 ∘C80\,^\circ\text{C}: magnet motors can be damaged and hot cases burn. Do not leave the test unattended.

Pitfalls

  • Rated output is shaft power. Input power is higher by 1/η1/\eta, and the apparent power higher still by 1/cos⁡φ1/\cos\varphi.
  • Oversizing. A motor at 30 % load has poorer efficiency and power factor; buy the size the load needs.
  • Ignoring ambient and altitude. At 50 ∘C50\,^\circ\text{C} or 2000 m2000\ \text{m} the same motor must be derated.
  • Assuming the rms method covers frequent starts. Starting currents are five to eight times rated in induction motors; that is what S4 and S5 ratings are for.

Practice

  1. A 4-pole 7.5 kW7.5\ \text{kW} motor runs at full load for 4000 h/year4000\ \text{h/year}. Find the annual saving in kWh of IE4 over IE2 (table values).
  2. A cycle is 10 kW10\ \text{kW} for 3 min and 4 kW4\ \text{kW} for 7 min. Find PeqP_\text{eq}.
  3. Classify: a crane hoist motor that lifts for 30 s, waits for 90 s, and repeats all day, starting each time.
Answer
  1. 7.5/0.887−7.5/0.926=8.456−8.099=0.356 kW7.5/0.887 - 7.5/0.926 = 8.456 - 8.099 = 0.356\ \text{kW}; times 4000 h4000\ \text{h}: about 1424 kWh1424\ \text{kWh}.
  2. (100⋅3+16⋅7)/10=41.2=6.42 kW\sqrt{(100 \cdot 3 + 16 \cdot 7)/10} = \sqrt{41.2} = 6.42\ \text{kW}.
  3. S4 (intermittent periodic duty with starting), cyclic duration factor 30/120=25 %30/120 = 25\ \%.

Test yourself

The rated output on a motor's nameplate is…

  1. electrical input power
  2. apparent power in kVA
  3. mechanical shaft power
  4. the maximum power for one minute

Duty type S1 means…

  1. short-time duty
  2. continuous running at constant load long enough to reach thermal equilibrium
  3. intermittent duty with starting
  4. non-periodic variable load

Since 1 July 2021, EU Regulation 2019/1781 requires which minimum class for a new 11 kW 4-pole three-phase motor?

  1. IE1
  2. IE2
  3. IE3
  4. IE5

A load cycle is 15 kW for 2 min, 5 kW for 6 min and 0 for 2 min. Its rms-equivalent power is about…

  1. 6.0 kW
  2. 7.75 kW
  3. 10 kW
  4. 15 kW