No-Load and Blocked-Rotor Tests

The previous lessons used the example motor's parameters as if they were printed on the nameplate. They never are. A nameplate gives voltage, current, power, speed and power factor; a datasheet adds efficiency and torque ratios. To get R1R_1, X1X_1, XmX_m, R2′R_2' and X2′X_2' you test the machine, exactly as the open- and short-circuit tests do for a transformer: one test at full voltage with almost no rotor current (no load), one at low voltage with the rotor held still (blocked rotor), and a DC measurement of the stator resistance. This lesson runs the three tests on the example motor's simulated data and recovers its parameters.

Safety: these tests are carried out on 400 V400\ \text{V} machines with locked shafts and high currents by qualified staff on a proper test bed. In this course they are calculation and simulation only: you work from given test data.

The three tests

Test How Circuit seen Gives
DC resistance DC current between two terminals, measure V/IV/I stator windings only R1R_1
No load rated voltage and frequency, shaft free s≈0s \approx 0: rotor branch R2′/s→R_2'/s \to very large, open X1+XmX_1 + X_m and the rotational loss
Blocked rotor rotor locked, voltage raised until rated current flows s=1s = 1: R2′+jX2′R_2' + jX_2' much smaller than jXmjX_m, which is ignored R1+R2′R_1 + R_2' and X1+X2′X_1 + X_2'

DC test. For a star-connected stator, the resistance between two terminals is 2R12R_1, so R1=Rdc/2R_1 = R_{dc}/2 (for delta, Rphase=1.5RdcR_\text{phase} = 1.5R_{dc} and the star-equivalent is Rdc/2R_{dc}/2 as well). The AC resistance is a little higher (skin effect) and both rise with temperature: copper's resistance rises by about 0.39 %0.39\ \% per kelvin, so the test standard corrects resistances to a specified temperature.

No-load test. At no load the slip is tiny, so the rotor branch is practically open. The input power covers only the stator copper loss and the rotational loss (core, friction and windage):

Prot=Pnl−3Inl2R1,X1+Xm≈V1InlP_\text{rot} = P_\text{nl} - 3I_\text{nl}^2R_1, \qquad X_1 + X_m \approx \frac{V_1}{I_\text{nl}}

(the power factor at no load is low, typically below 0.2, so the impedance is almost purely reactive).

Blocked-rotor test. With the rotor locked (s=1s = 1) and rated current flowing, the per-phase circuit is essentially R1+R2′+j(X1+X2′)R_1 + R_2' + j(X_1 + X_2'):

RBR=PBR3IBR2,XBR=(VBRIBR)2−RBR2,R2′≈RBR−R1R_\text{BR} = \frac{P_\text{BR}}{3I_\text{BR}^2}, \qquad X_\text{BR} = \sqrt{\left(\frac{V_\text{BR}}{I_\text{BR}}\right)^2 - R_\text{BR}^2}, \qquad R_2' \approx R_\text{BR} - R_1

A running rotor carries currents of 1–2 Hz, not 50 Hz, and deep bars behave very differently at the two frequencies (Torque–Slip Curve). IEEE 112-2017 (described from memory; check the current text) therefore runs the blocked-rotor test at 25 % of rated frequency (textbooks quote this for motors above about 20 hp20\ \text{hp}, 15 kW15\ \text{kW}, and for any rotor whose resistance varies with frequency) and scales the measured reactance up to rated frequency: XBR(50 Hz)=4 XBR(12.5 Hz)X_\text{BR}(50\ \text{Hz}) = 4\,X_\text{BR}(12.5\ \text{Hz}). The test cannot separate X1X_1 from X2′X_2'; IEEE 112 splits XBRX_\text{BR} by the NEMA design class:

Rotor design X1/XBRX_1/X_\text{BR} X2′/XBRX_2'/X_\text{BR}
wound rotor, NEMA A, NEMA D 0.5 0.5
NEMA B 0.4 0.6
NEMA C 0.3 0.7

Finally, the magnetising branch steals a little of the blocked-rotor current. A first-order correction refers the rotor resistance through it:

R2′≈(RBR−R1)(X2′+XmXm)2R_2' \approx (R_\text{BR} - R_1)\left(\frac{X_2' + X_m}{X_m}\right)^2

Worked example: the example motor's test data

Given: a 7.5 kW7.5\ \text{kW}, 400 V400\ \text{V}, 50 Hz50\ \text{Hz}, 4-pole star-connected NEMA design B motor:

  • DC test: 1.10 Ω1.10\ \Omega between two terminals.
  • No-load test: 400 V400\ \text{V}, 7.00 A7.00\ \text{A}, 301 W301\ \text{W}, 50 Hz50\ \text{Hz}.
  • Blocked-rotor test at 12.5 Hz12.5\ \text{Hz}: 28.4 V28.4\ \text{V} (line), 14.4 A14.4\ \text{A}, 601 W601\ \text{W}.

Find: R1R_1, ProtP_\text{rot}, X1X_1, X2′X_2', XmX_m and R2′R_2'.

Solve: R1=1.10/2=0.550 ΩR_1 = 1.10/2 = 0.550\ \Omega. No load: V1=400/3=230.9 VV_1 = 400/\sqrt{3} = 230.9\ \text{V},

Prot=301 W−3⋅(7.00 A)2⋅0.550 Ω=220 W,X1+Xm=230.9 V7.00 A=32.99 ΩRBR=601 W3⋅(14.4 A)2=0.966 Ω,∣ZBR∣=28.4 V/314.4 A=1.139 ΩXBR(12.5 Hz)=1.1392−0.9662 Ω=0.603 Ω,XBR(50 Hz)=4⋅0.603 Ω=2.41 ΩX1=0.4⋅2.41 Ω=0.964 Ω,X2′=0.6⋅2.41 Ω=1.447 Ω,Xm=32.99−0.964=32.03 ΩR2′≈(0.966−0.550) Ω⋅(1.447+32.0332.03)2=0.416 Ω⋅1.093=0.455 Ω\begin{aligned} P_\text{rot} &= 301\ \text{W} - 3 \cdot (7.00\ \text{A})^2 \cdot 0.550\ \Omega = 220\ \text{W}, \qquad X_1 + X_m = \frac{230.9\ \text{V}}{7.00\ \text{A}} = 32.99\ \Omega \\ R_\text{BR} &= \frac{601\ \text{W}}{3 \cdot (14.4\ \text{A})^2} = 0.966\ \Omega, \qquad \lvert Z_\text{BR} \rvert = \frac{28.4\ \text{V}/\sqrt{3}}{14.4\ \text{A}} = 1.139\ \Omega \\ X_\text{BR}(12.5\ \text{Hz}) &= \sqrt{1.139^2 - 0.966^2}\ \Omega = 0.603\ \Omega, \qquad X_\text{BR}(50\ \text{Hz}) = 4 \cdot 0.603\ \Omega = 2.41\ \Omega \\ X_1 &= 0.4 \cdot 2.41\ \Omega = 0.964\ \Omega, \quad X_2' = 0.6 \cdot 2.41\ \Omega = 1.447\ \Omega, \quad X_m = 32.99 - 0.964 = 32.03\ \Omega \\ R_2' &\approx (0.966 - 0.550)\ \Omega \cdot \left(\frac{1.447 + 32.03}{32.03}\right)^2 = 0.416\ \Omega \cdot 1.093 = 0.455\ \Omega \end{aligned}

Check: the "true" values behind this data are R1=0.55R_1 = 0.55, X1=1.0X_1 = 1.0, Xm=32X_m = 32, R2′=0.45R_2' = 0.45, X2′=1.4 ΩX_2' = 1.4\ \Omega and Prot=220 WP_\text{rot} = 220\ \text{W}. Every parameter is recovered within 4 %; the largest error is the X1X_1/X2′X_2' split, which the test cannot measure and the design-class rule only estimates. Without the magnetising correction R2′R_2' would come out 8 % low.

In Python: parameters from test data, then the predicted rated point

python · try it yourself
import numpy as np
VL, f = 400.0, 50.0
V = VL / np.sqrt(3)

# measured data
R_dc = 1.10                                   # ohm, between two terminals (star)
V_nl, I_nl, P_nl = 400.0, 7.00, 301.0         # no-load test at 50 Hz
f_br, V_br, I_br, P_br = 12.5, 28.4, 14.4, 601.0   # blocked rotor at 25 % frequency
x1_share = 0.4                                # NEMA design B: X1 = 0.4 X_BR

R1 = R_dc / 2
P_rot = P_nl - 3 * I_nl**2 * R1
X_nl = (V_nl / np.sqrt(3)) / I_nl
R_br = P_br / (3 * I_br**2)
Z_br = (V_br / np.sqrt(3)) / I_br
X_br = np.sqrt(Z_br**2 - R_br**2) * f / f_br
X1, X2 = x1_share * X_br, (1 - x1_share) * X_br
Xm = X_nl - X1
R2 = (R_br - R1) * ((X2 + Xm) / Xm) ** 2
est = dict(R1=R1, X1=X1, Xm=Xm, R2=R2, X2=X2)
true = dict(R1=0.55, X1=1.0, Xm=32.0, R2=0.45, X2=1.4)
print(f"P_rot = {P_rot:.1f} W")
for k in est:
    print(f"{k:3s} estimated {est[k]:7.4f} ohm   true {true[k]:7.4f}   error {100*(est[k]/true[k]-1):+5.1f} %")

def rated(p, s=0.0255):
    Z2 = p["R2"] / s + 1j * p["X2"]
    I1 = V / (p["R1"] + 1j * p["X1"] + 1j * p["Xm"] * Z2 / (1j * p["Xm"] + Z2))
    I2 = abs(I1 * 1j * p["Xm"] / (1j * p["Xm"] + Z2))
    P_out = 3 * I2**2 * p["R2"] / s * (1 - s) - 220.0
    return abs(I1), np.cos(np.angle(I1)), P_out
for name, p in (("estimated", est), ("true", true)):
    I1, pf, P = rated(p)
    print(f"{name:9s} model at s = 0.0255: I1 = {I1:.2f} A, pf = {pf:.3f}, P_out = {P:.0f} W")
P_rot = 220.1 W
R1  estimated  0.5500 ohm   true  0.5500   error  +0.0 %
X1  estimated  0.9642 ohm   true  1.0000   error  -3.6 %
Xm  estimated 32.0272 ohm   true 32.0000   error  +0.1 %
R2  estimated  0.4545 ohm   true  0.4500   error  +1.0 %
X2  estimated  1.4463 ohm   true  1.4000   error  +3.3 %
estimated model at s = 0.0255: I1 = 14.35 A, pf = 0.824, P_out = 7432 W
true      model at s = 0.0255: I1 = 14.43 A, pf = 0.826, P_out = 7488 W

The fitted model predicts the rated point within a few per cent. That is the normal accuracy of the method; IEEE 112 method F and its variants refine it with tests at several loads.

Interactive: the blocked-rotor test, simulated

The netlist lab holds one phase of the "true" motor with R2′/s=R2′=0.45 ΩR_2'/s = R_2' = 0.45\ \Omega (rotor locked) at 12.5 Hz12.5\ \text{Hz}. The source is the phase voltage 16.42 V16.42\ \text{V} (28.4 V28.4\ \text{V} line). The lab shows I1=14.43 AI_1 = 14.43\ \text{A} at −32.3∘-32.3^\circ, so P=3⋅16.42⋅14.43⋅cos⁡32.3∘=601 WP = 3 \cdot 16.42 \cdot 14.43 \cdot \cos 32.3^\circ = 601\ \text{W}, the test reading. The magnetising branch (I(LM)) takes 0.98 A0.98\ \text{A}, under 7 % of the current: small, but the reason for the correction above. Here the frequency plot means something too: with the rotor locked (s=1s = 1 at every frequency) it is the locked-rotor current against supply frequency at this voltage, if skin effect is ignored. Raise the voltage slider to see that current scales linearly (no saturation in the model; a real blocked-rotor test at full voltage saturates the leakage paths and the reactance falls).

051015100m1101001k10kf (Hz)|V| (V)0 A10 A20 A30 A|I| (A)|V(a)||I(R1)|phasors at f = 12.50 Hz (magnitude @ phase)V(a)16.4 V @ 0.0 degV(b)10.6 V @ 23.6 degV(c)7.87 V @ 8.7 degV(d)6.21 V @ -29.2 degI(V1)14.4 A @ 147.7 degI(R1)14.4 A @ -32.3 degI(L1)14.4 A @ -32.3 degI(LM)984 mA @ -81.3 degI(L2)13.8 A @ -29.2 degI(RR)13.8 A @ -29.2 deg

Guided lab (data analysis)

Hand calculation. Repeat the worked example assuming NEMA design C (X1=0.3XBRX_1 = 0.3X_\text{BR}). Which parameters change?

Simulation. Change x1_share in the code to 0.3 and compare the predicted rated current and power factor.

What you would measure. In a qualified test lab: a three-phase power analyser (class 0.2 or better) reads VV, II and PP in all three lines; the blocked-rotor test locks the shaft mechanically, uses a variable-frequency or variable-voltage supply and finishes quickly (seconds) because the stator heats at rated current with no cooling fan running. Expect readings to scatter by about ±1 %\pm 1\ \% between phases, a no-load power factor near 0.06 (301 W301\ \text{W} from 4.85 kVA4.85\ \text{kVA}) and a blocked-rotor current that must be held within a few per cent of the target. Measure RdcR_{dc} immediately after the tests, hot, with a four-wire meter (Four-Wire Resistance), because R1R_1 at the test temperature is what the power separation needs.

Pitfalls

  • Mixing line and phase values. Test data are line voltages and line currents; the circuit is per phase, star equivalent.
  • Forgetting to scale the reduced-frequency reactance back to rated frequency (multiply by f/ftestf/f_\text{test}). Resistances are not scaled.
  • Using cold resistance. A winding at 75 ∘C75\,^\circ\text{C} has about 20 % more resistance than at 25 ∘C25\,^\circ\text{C}; mixing the two shifts losses and R2′R_2'.
  • Assuming no-load power is all core loss. It includes friction and windage; separating them needs no-load tests at several voltages (extrapolate PP against V2V^2 to zero voltage).

Practice

  1. A star-connected motor shows 0.84 Ω0.84\ \Omega between two terminals. What is R1R_1?
  2. No-load test: 400 V400\ \text{V}, 5.5 A5.5\ \text{A}, 380 W380\ \text{W}, with R1=0.42 ΩR_1 = 0.42\ \Omega. Find ProtP_\text{rot} and X1+XmX_1 + X_m.
  3. Blocked-rotor test at rated frequency: 60 V60\ \text{V} line, 12 A12\ \text{A}, 500 W500\ \text{W}. Find RBRR_\text{BR} and XBRX_\text{BR}.
Answer
  1. 0.42 Ω0.42\ \Omega.
  2. Prot=380−3⋅5.52⋅0.42=341.9 WP_\text{rot} = 380 - 3 \cdot 5.5^2 \cdot 0.42 = 341.9\ \text{W}; X1+Xm≈230.9/5.5=42.0 ΩX_1 + X_m \approx 230.9/5.5 = 42.0\ \Omega.
  3. RBR=500/(3⋅144)=1.157 ΩR_\text{BR} = 500/(3 \cdot 144) = 1.157\ \Omega; ∣Z∣=34.64/12=2.887 Ω\lvert Z \rvert = 34.64/12 = 2.887\ \Omega; XBR=2.8872−1.1572=2.645 ΩX_\text{BR} = \sqrt{2.887^2 - 1.157^2} = 2.645\ \Omega.

Test yourself

Why can the rotor branch be ignored in the no-load test?

  1. the rotor is locked
  2. the slip is nearly zero, so R2′/sR_2'/s is very large and almost no rotor current flows
  3. the stator resistance is zero
  4. the supply frequency is reduced

IEEE 112 runs the blocked-rotor test at 25 % of rated frequency because…

  1. it is safer
  2. running rotors carry low-frequency currents, and deep bars behave differently at 50 Hz
  3. the voltmeter needs it
  4. the magnetising branch disappears

The blocked-rotor reactance measured at 12.5 Hz is 0.6 Ω0.6\ \Omega. What is X1+X2′X_1 + X_2' at 50 Hz?

  1. 0.15 Ω0.15\ \Omega
  2. 0.6 Ω0.6\ \Omega
  3. 1.2 Ω1.2\ \Omega
  4. 2.4 Ω2.4\ \Omega

Which split of XBRX_\text{BR} does IEEE 112 use for a NEMA design B motor?

  1. X1=X2′X_1 = X_2'
  2. X1=0.4XBRX_1 = 0.4X_\text{BR}, X2′=0.6XBRX_2' = 0.6X_\text{BR}
  3. X1=0.3XBRX_1 = 0.3X_\text{BR}, X2′=0.7XBRX_2' = 0.7X_\text{BR}
  4. X2′=0X_2' = 0