No-Load and Blocked-Rotor Tests
The previous lessons used the example motor's parameters as if they were printed on the nameplate. They never are. A nameplate gives voltage, current, power, speed and power factor; a datasheet adds efficiency and torque ratios. To get , , , and you test the machine, exactly as the open- and short-circuit tests do for a transformer: one test at full voltage with almost no rotor current (no load), one at low voltage with the rotor held still (blocked rotor), and a DC measurement of the stator resistance. This lesson runs the three tests on the example motor's simulated data and recovers its parameters.
Safety: these tests are carried out on machines with locked shafts and high currents by qualified staff on a proper test bed. In this course they are calculation and simulation only: you work from given test data.
The three tests
| Test | How | Circuit seen | Gives |
|---|---|---|---|
| DC resistance | DC current between two terminals, measure | stator windings only | |
| No load | rated voltage and frequency, shaft free | : rotor branch very large, open | and the rotational loss |
| Blocked rotor | rotor locked, voltage raised until rated current flows | : much smaller than , which is ignored | and |
DC test. For a star-connected stator, the resistance between two terminals is , so (for delta, and the star-equivalent is as well). The AC resistance is a little higher (skin effect) and both rise with temperature: copper's resistance rises by about per kelvin, so the test standard corrects resistances to a specified temperature.
No-load test. At no load the slip is tiny, so the rotor branch is practically open. The input power covers only the stator copper loss and the rotational loss (core, friction and windage):
(the power factor at no load is low, typically below 0.2, so the impedance is almost purely reactive).
Blocked-rotor test. With the rotor locked () and rated current flowing, the per-phase circuit is essentially :
A running rotor carries currents of 1–2 Hz, not 50 Hz, and deep bars behave very differently at the two frequencies (Torque–Slip Curve). IEEE 112-2017 (described from memory; check the current text) therefore runs the blocked-rotor test at 25 % of rated frequency (textbooks quote this for motors above about , , and for any rotor whose resistance varies with frequency) and scales the measured reactance up to rated frequency: . The test cannot separate from ; IEEE 112 splits by the NEMA design class:
| Rotor design | ||
|---|---|---|
| wound rotor, NEMA A, NEMA D | 0.5 | 0.5 |
| NEMA B | 0.4 | 0.6 |
| NEMA C | 0.3 | 0.7 |
Finally, the magnetising branch steals a little of the blocked-rotor current. A first-order correction refers the rotor resistance through it:
Worked example: the example motor's test data
Given: a , , , 4-pole star-connected NEMA design B motor:
- DC test: between two terminals.
- No-load test: , , , .
- Blocked-rotor test at : (line), , .
Find: , , , , and .
Solve: . No load: ,
Check: the "true" values behind this data are , , , , and . Every parameter is recovered within 4 %; the largest error is the / split, which the test cannot measure and the design-class rule only estimates. Without the magnetising correction would come out 8 % low.
In Python: parameters from test data, then the predicted rated point
import numpy as np
VL, f = 400.0, 50.0
V = VL / np.sqrt(3)
# measured data
R_dc = 1.10 # ohm, between two terminals (star)
V_nl, I_nl, P_nl = 400.0, 7.00, 301.0 # no-load test at 50 Hz
f_br, V_br, I_br, P_br = 12.5, 28.4, 14.4, 601.0 # blocked rotor at 25 % frequency
x1_share = 0.4 # NEMA design B: X1 = 0.4 X_BR
R1 = R_dc / 2
P_rot = P_nl - 3 * I_nl**2 * R1
X_nl = (V_nl / np.sqrt(3)) / I_nl
R_br = P_br / (3 * I_br**2)
Z_br = (V_br / np.sqrt(3)) / I_br
X_br = np.sqrt(Z_br**2 - R_br**2) * f / f_br
X1, X2 = x1_share * X_br, (1 - x1_share) * X_br
Xm = X_nl - X1
R2 = (R_br - R1) * ((X2 + Xm) / Xm) ** 2
est = dict(R1=R1, X1=X1, Xm=Xm, R2=R2, X2=X2)
true = dict(R1=0.55, X1=1.0, Xm=32.0, R2=0.45, X2=1.4)
print(f"P_rot = {P_rot:.1f} W")
for k in est:
print(f"{k:3s} estimated {est[k]:7.4f} ohm true {true[k]:7.4f} error {100*(est[k]/true[k]-1):+5.1f} %")
def rated(p, s=0.0255):
Z2 = p["R2"] / s + 1j * p["X2"]
I1 = V / (p["R1"] + 1j * p["X1"] + 1j * p["Xm"] * Z2 / (1j * p["Xm"] + Z2))
I2 = abs(I1 * 1j * p["Xm"] / (1j * p["Xm"] + Z2))
P_out = 3 * I2**2 * p["R2"] / s * (1 - s) - 220.0
return abs(I1), np.cos(np.angle(I1)), P_out
for name, p in (("estimated", est), ("true", true)):
I1, pf, P = rated(p)
print(f"{name:9s} model at s = 0.0255: I1 = {I1:.2f} A, pf = {pf:.3f}, P_out = {P:.0f} W")P_rot = 220.1 W
R1 estimated 0.5500 ohm true 0.5500 error +0.0 %
X1 estimated 0.9642 ohm true 1.0000 error -3.6 %
Xm estimated 32.0272 ohm true 32.0000 error +0.1 %
R2 estimated 0.4545 ohm true 0.4500 error +1.0 %
X2 estimated 1.4463 ohm true 1.4000 error +3.3 %
estimated model at s = 0.0255: I1 = 14.35 A, pf = 0.824, P_out = 7432 W
true model at s = 0.0255: I1 = 14.43 A, pf = 0.826, P_out = 7488 W
The fitted model predicts the rated point within a few per cent. That is the normal accuracy of the method; IEEE 112 method F and its variants refine it with tests at several loads.
Interactive: the blocked-rotor test, simulated
The netlist lab holds one phase of the "true" motor with (rotor locked) at . The source is the phase voltage ( line). The lab shows at , so , the test reading. The magnetising branch (I(LM)) takes , under 7 % of the current: small, but the reason for the correction above. Here the frequency plot means something too: with the rotor locked ( at every frequency) it is the locked-rotor current against supply frequency at this voltage, if skin effect is ignored. Raise the voltage slider to see that current scales linearly (no saturation in the model; a real blocked-rotor test at full voltage saturates the leakage paths and the reactance falls).
Guided lab (data analysis)
Hand calculation. Repeat the worked example assuming NEMA design C (). Which parameters change?
Simulation. Change x1_share in the code to 0.3 and compare the predicted rated current and power factor.
What you would measure. In a qualified test lab: a three-phase power analyser (class 0.2 or better) reads , and in all three lines; the blocked-rotor test locks the shaft mechanically, uses a variable-frequency or variable-voltage supply and finishes quickly (seconds) because the stator heats at rated current with no cooling fan running. Expect readings to scatter by about between phases, a no-load power factor near 0.06 ( from ) and a blocked-rotor current that must be held within a few per cent of the target. Measure immediately after the tests, hot, with a four-wire meter (Four-Wire Resistance), because at the test temperature is what the power separation needs.
Pitfalls
- Mixing line and phase values. Test data are line voltages and line currents; the circuit is per phase, star equivalent.
- Forgetting to scale the reduced-frequency reactance back to rated frequency (multiply by ). Resistances are not scaled.
- Using cold resistance. A winding at has about 20 % more resistance than at ; mixing the two shifts losses and .
- Assuming no-load power is all core loss. It includes friction and windage; separating them needs no-load tests at several voltages (extrapolate against to zero voltage).
Practice
- A star-connected motor shows between two terminals. What is ?
- No-load test: , , , with . Find and .
- Blocked-rotor test at rated frequency: line, , . Find and .
Answer
- .
- ; .
- ; ; .
Test yourself
Why can the rotor branch be ignored in the no-load test?
- the rotor is locked
- the slip is nearly zero, so is very large and almost no rotor current flows
- the stator resistance is zero
- the supply frequency is reduced
IEEE 112 runs the blocked-rotor test at 25 % of rated frequency because…
- it is safer
- running rotors carry low-frequency currents, and deep bars behave differently at 50 Hz
- the voltmeter needs it
- the magnetising branch disappears
The blocked-rotor reactance measured at 12.5 Hz is . What is at 50 Hz?
Which split of does IEEE 112 use for a NEMA design B motor?
- ,
- ,