Open-Circuit and Short-Circuit Tests
Nobody gives you , , or for a transformer on a pole. What you get is a nameplate and, from the factory, a test report. Two simple tests produce the whole equivalent circuit, without loading the transformer at all: an open-circuit test at rated voltage with one winding open, which shows the shunt branch, and a short-circuit test at rated current with one winding shorted, which shows the series branch. The same two ideas reappear for induction motors as the no-load and blocked-rotor tests (No-Load and Blocked-Rotor Tests).
Safety: calculation and simulation only. Both tests on a real power transformer involve mains or higher voltages and, in the short-circuit test, rated current with a deliberately shorted winding. They are done by qualified staff in test bays with interlocked enclosures. In this lesson the "readings" come from an ngspice model of transformer T1, and the hands-on part uses a small signal transformer.
The two tests
Open-circuit (OC) test. Apply rated voltage to the LV winding (rated voltage is easier to source there and the current is larger, so easier to read) with the HV winding open. The series impedance carries only the tiny no-load current, so its drop is negligible and the readings , , describe the shunt branch at rated flux:
is the core loss (no-load loss), valid at this voltage and frequency.
Short-circuit (SC) test. Short the LV winding and raise the voltage on the HV winding until rated current flows. That takes only a few percent of rated voltage, so the core flux is a few percent of normal, the shunt branch draws almost nothing, and the readings describe the series branch:
is the full-load copper loss (load loss). as a percentage of rated voltage is the impedance voltage, printed on the nameplate as or %Z.
Each test gives its parameters referred to the side on which it was measured. The split of between the windings can be found from their DC resistances, measured separately; the split of is usually taken as half and half.
The readings: a virtual test bench
The deck below runs both tests on T1's exact equivalent circuit (the equivalent circuit lesson): on the LV winding with the HV open (the circuit referred to LV, so every impedance divided by ), and on the HV winding with the LV shorted.
cat > tests.cir <<'EOF'
* virtual test bench for T1 (exact T circuit, values in ohms and henries at 50 Hz)
* open-circuit test: 240 V on the LV winding, HV open (circuit referred to LV)
VOC a 0 AC 240
R2 a b 0.0052
L2 b c 50.93u
RC c 0 480
LM c 0 0.30558
R1 c d 0.005
L1 d e 50.93u
ROPEN e 0 1e9
* short-circuit test: 70 V on the HV winding, LV shorted (circuit referred to HV)
VSC p 0 AC 70
R1H p q 0.5
L1H q r 5.093m
RCH r 0 48k
LMH r 0 30.558
R2H r s 0.52
L2H s 0 5.093m
.control
ac lin 1 50 50
let ioc = -i(voc)
let isc = -i(vsc)
let poc = 240*real(ioc)
let psc = 70*real(isc)
print mag(ioc) poc mag(isc) psc
.endc
.end
EOF
ngspice -b tests.cir 2>&1 | grep -E '^(mag|poc|psc)'mag(ioc) = 2.549037e+00
poc = 1.199913e+02
mag(isc) = 2.084352e+01
psc = 4.430870e+02
Rounded the way a test report prints them: OC , , ; SC , , .
Worked example: T1's parameters from its test report
Given: the readings above for the , transformer T1.
Find: , , and referred to the HV side, and the percentage impedance.
Solve:
The impedance voltage is .
Check: these are the values the model was built from, so the method recovers them. The no-load power factor is , low as expected: the shunt branch is mainly inductive. In the SC test the core flux is of normal, so the core loss in it is about , invisible next to ; the netlist lab below shows only in the magnetising branch during the SC test.
In Python: parameters and their uncertainty
The OC test is a low-power-factor measurement, where wattmeter errors matter. A Monte Carlo run draws meter errors of (V, I) and (P) of reading and shows how far the results move (Error Propagation and Monte Carlo).
import numpy as np
a = 10.0 # 2400/240 V
# open-circuit test on the LV side (HV open), short-circuit test on the HV side (LV shorted)
Voc, Ioc, Poc = 240.0, 2.55, 120.0
Vsc, Isc, Psc = 70.0, 20.84, 443.0
def params(Voc, Ioc, Poc, Vsc, Isc, Psc):
Gc = Poc / Voc**2 # shunt branch from the OC test (LV side)
Y = Ioc / Voc
Bm = np.sqrt(Y**2 - Gc**2)
Rc, Xm = a**2 / Gc, a**2 / Bm # referred to HV
Req = Psc / Isc**2 # series branch from the SC test (HV side)
Zeq = Vsc / Isc
Xeq = np.sqrt(Zeq**2 - Req**2)
return Rc, Xm, Req, Xeq
Rc, Xm, Req, Xeq = params(Voc, Ioc, Poc, Vsc, Isc, Psc)
print(f"OC test: pf = {Poc/(Voc*Ioc):.3f}, Rc = {Rc/1e3:.2f} kOhm, Xm = {Xm/1e3:.2f} kOhm (HV side)")
print(f"SC test: pf = {Psc/(Vsc*Isc):.3f}, Req = {Req:.3f} Ohm, Xeq = {Xeq:.3f} Ohm (HV side)")
print(f"Zbase = {2400**2/50e3:.1f} Ohm: Req = {Req/115.2*100:.2f} %, Xeq = {Xeq/115.2*100:.2f} %, "
f"impedance voltage = {Vsc/2400*100:.2f} %")
# how far can meter errors move the answers? V and I +-0.5 %, P +-1 % of reading, uniform, 20000 draws
rng = np.random.default_rng(1)
u = lambda x, e: x * (1 + rng.uniform(-e, e, 20000))
out = np.array(params(u(Voc, .005), u(Ioc, .005), u(Poc, .01), u(Vsc, .005), u(Isc, .005), u(Psc, .01)))
for name, col, unit in (("Rc", 0, "kOhm"), ("Xm", 1, "kOhm"), ("Req", 2, "Ohm"), ("Xeq", 3, "Ohm")):
s = out[col] / (1e3 if unit == "kOhm" else 1)
print(f"{name:3s}: {np.mean(s):7.3f} {unit}, spread (2 sd) +-{2 * np.std(s) / np.mean(s) * 100:.1f} %")OC test: pf = 0.196, Rc = 48.00 kOhm, Xm = 9.60 kOhm (HV side)
SC test: pf = 0.304, Req = 1.020 Ohm, Xeq = 3.200 Ohm (HV side)
Zbase = 115.2 Ohm: Req = 0.89 %, Xeq = 2.78 %, impedance voltage = 2.92 %
Rc : 47.999 kOhm, spread (2 sd) +-1.6 %
Xm : 9.598 kOhm, spread (2 sd) +-0.8 %
Req: 1.020 Ohm, spread (2 sd) +-1.6 %
Xeq: 3.200 Ohm, spread (2 sd) +-0.8 %
The resistances inherit the wattmeter's error (and twice the voltmeter's or ammeter's, because they enter squared); the reactances are less sensitive. In real tests the wattmeter's own phase error at power factors near is often the largest term, which is why test standards specify low-power-factor wattmeters or power analysers. Load losses measured at the test temperature are also corrected to a reference temperature, for many transformer classes (IEC 60076-1:2011 as of 2026), because copper resistance rises about per kelvin.
Interactive: the short-circuit test
The SC test on T1 in the netlist lab (calculation only: the real test uses a high-current source). At the default the lab shows , rated current, and only in LM. Slide the test voltage: the current scales linearly, because the series branch is linear; the shunt branch stays negligible. The lab also sweeps frequency on its plot; only the readouts at the cursor matter here.
Guided lab: OC and SC tests on a signal transformer
Hand calculation. For a small line or audio transformer rated for a few volts, plan an OC test at its rated signal level (say rms at ) and an SC test at a current that warms nothing (say ). Estimate from the winding resistances and the shorted inductance you measured in the equivalent-circuit lab.
Simulation. Put your readings into the Python function (with ) and run the Monte Carlo with your meters' accuracy.
What you would measure. Drive the winding from a function generator, read current with a series resistor and the oscilloscope, voltage directly, and power as the cycle average of the product (scope math). Expect a very low OC power factor (below ) and an SC power factor that is mostly resistive at low frequency. The OC power, a few milliwatts, is the hardest number: treat it as after deskewing the probes.
Hazards and safe setup. Signal levels only. Never perform these tests on a mains transformer or motor: the OC test would need mains voltage on a winding and the SC test needs a deliberately shorted winding at rated current.
Pitfalls
- Swapping the sides. OC on LV and SC on HV is the convention for convenience; the parameters come out referred to the side measured.
- Using the SC power as the core loss (or the OC power as the copper loss). Each test isolates one branch.
- Forgetting temperature. Copper loss must be corrected to the reference temperature before it is compared with a guarantee.
- Running the OC test away from rated voltage. The shunt branch is nonlinear; it must be measured at the voltage it will see.
Practice
- A , transformer gives OC (LV side): , , ; SC (HV side): , , . Find all parameters referred to HV.
- What is its impedance voltage and the full-load copper loss?
- Why does the SC test need only a few percent of rated voltage?
Answer
- , . OC: , , ; LV side , ; HV side , . SC: , , .
- Rated HV current is , so the test was at rated current: impedance voltage , full-load copper loss .
- The series impedance is only a few percent of the base impedance, so a few percent of rated voltage drives rated current through it.
Test yourself
The power measured in the open-circuit test is mainly…
- copper loss
- core loss
- stray load loss
- mechanical loss
In the short-circuit test the shunt branch can be neglected because…
- it is disconnected
- the applied voltage, and so the core flux, is only a few percent of rated
- the current is too small
- the test is at DC
SC test readings: 70 V, 20.84 A, 443 W. The equivalent series resistance is…
Why is the open-circuit test usually done on the low-voltage winding?
- the core loss is smaller there
- rated voltage is lower and easier to supply, and the current is larger and easier to read
- the HV winding would saturate
- the standard forbids the HV side