Home › Electrical Machines & Transformers › Open-Circuit and Short-Circuit Tests

Open-Circuit and Short-Circuit Tests

Nobody gives you R1R_1, X1X_1, RcR_c or XmX_m for a transformer on a pole. What you get is a nameplate and, from the factory, a test report. Two simple tests produce the whole equivalent circuit, without loading the transformer at all: an open-circuit test at rated voltage with one winding open, which shows the shunt branch, and a short-circuit test at rated current with one winding shorted, which shows the series branch. The same two ideas reappear for induction motors as the no-load and blocked-rotor tests (No-Load and Blocked-Rotor Tests).

Safety: calculation and simulation only. Both tests on a real power transformer involve mains or higher voltages and, in the short-circuit test, rated current with a deliberately shorted winding. They are done by qualified staff in test bays with interlocked enclosures. In this lesson the "readings" come from an ngspice model of transformer T1, and the hands-on part uses a small signal transformer.

The two tests

open circuit (LV side, rated V) A V W HV openLVHV short circuit (HV side, rated I) A V W LV shortedHVLV

Open-circuit (OC) test. Apply rated voltage to the LV winding (rated voltage is easier to source there and the current is larger, so easier to read) with the HV winding open. The series impedance carries only the tiny no-load current, so its drop is negligible and the readings VocV_\text{oc}, IocI_\text{oc}, PocP_\text{oc} describe the shunt branch at rated flux:

Gc=PocVoc2,∣Y∣=IocVoc,Bm=∣Y∣2−Gc2,Rc=1Gc, Xm=1BmG_c = \frac{P_\text{oc}}{V_\text{oc}^2}, \qquad \lvert Y \rvert = \frac{I_\text{oc}}{V_\text{oc}}, \qquad B_m = \sqrt{\lvert Y \rvert^2 - G_c^2}, \qquad R_c = \frac{1}{G_c},\ X_m = \frac{1}{B_m}

PocP_\text{oc} is the core loss (no-load loss), valid at this voltage and frequency.

Short-circuit (SC) test. Short the LV winding and raise the voltage on the HV winding until rated current flows. That takes only a few percent of rated voltage, so the core flux is a few percent of normal, the shunt branch draws almost nothing, and the readings describe the series branch:

Req=PscIsc2,∣Zeq∣=VscIsc,Xeq=∣Zeq∣2−Req2R_\text{eq} = \frac{P_\text{sc}}{I_\text{sc}^2}, \qquad \lvert Z_\text{eq} \rvert = \frac{V_\text{sc}}{I_\text{sc}}, \qquad X_\text{eq} = \sqrt{\lvert Z_\text{eq} \rvert^2 - R_\text{eq}^2}

PscP_\text{sc} is the full-load copper loss (load loss). VscV_\text{sc} as a percentage of rated voltage is the impedance voltage, printed on the nameplate as uku_k or %Z.

Each test gives its parameters referred to the side on which it was measured. The split of ReqR_\text{eq} between the windings can be found from their DC resistances, measured separately; the split of XeqX_\text{eq} is usually taken as half and half.

The readings: a virtual test bench

The deck below runs both tests on T1's exact equivalent circuit (the equivalent circuit lesson): 240 V240\ \text{V} on the LV winding with the HV open (the circuit referred to LV, so every impedance divided by a2=100a^2 = 100), and 70 V70\ \text{V} on the HV winding with the LV shorted.

bash · try it yourself
cat > tests.cir <<'EOF'
* virtual test bench for T1 (exact T circuit, values in ohms and henries at 50 Hz)
* open-circuit test: 240 V on the LV winding, HV open (circuit referred to LV)
VOC a 0 AC 240
R2 a b 0.0052
L2 b c 50.93u
RC c 0 480
LM c 0 0.30558
R1 c d 0.005
L1 d e 50.93u
ROPEN e 0 1e9
* short-circuit test: 70 V on the HV winding, LV shorted (circuit referred to HV)
VSC p 0 AC 70
R1H p q 0.5
L1H q r 5.093m
RCH r 0 48k
LMH r 0 30.558
R2H r s 0.52
L2H s 0 5.093m
.control
ac lin 1 50 50
let ioc = -i(voc)
let isc = -i(vsc)
let poc = 240*real(ioc)
let psc = 70*real(isc)
print mag(ioc) poc mag(isc) psc
.endc
.end
EOF
ngspice -b tests.cir 2>&1 | grep -E '^(mag|poc|psc)'
mag(ioc) = 2.549037e+00
poc = 1.199913e+02
mag(isc) = 2.084352e+01
psc = 4.430870e+02

Rounded the way a test report prints them: OC 240 V240\ \text{V}, 2.55 A2.55\ \text{A}, 120 W120\ \text{W}; SC 70.0 V70.0\ \text{V}, 20.84 A20.84\ \text{A}, 443 W443\ \text{W}.

Worked example: T1's parameters from its test report

Given: the readings above for the 50 kVA50\ \text{kVA}, 2400/240 V2400/240\ \text{V} transformer T1.

Find: RcR_c, XmX_m, ReqR_\text{eq} and XeqX_\text{eq} referred to the HV side, and the percentage impedance.

Solve:

Gc=120 W(240 V)2=2.083 mS,∣Y∣=2.55 A240 V=10.63 mS,Bm=10.42 mSRc=a2Gc=1002.083×10−3 S=48.0 kΩ,Xm=10010.42×10−3 S=9.60 kΩReq=443 W(20.84 A)2=1.020 Ω,∣Zeq∣=70.0 V20.84 A=3.359 Ω,Xeq=3.200 Ω\begin{aligned} G_c &= \frac{120\ \text{W}}{(240\ \text{V})^2} = 2.083\ \text{mS}, \quad \lvert Y \rvert = \frac{2.55\ \text{A}}{240\ \text{V}} = 10.63\ \text{mS}, \quad B_m = 10.42\ \text{mS} \\ R_c &= \frac{a^2}{G_c} = \frac{100}{2.083 \times 10^{-3}\ \text{S}} = 48.0\ \text{k}\Omega, \qquad X_m = \frac{100}{10.42 \times 10^{-3}\ \text{S}} = 9.60\ \text{k}\Omega \\ R_\text{eq} &= \frac{443\ \text{W}}{(20.84\ \text{A})^2} = 1.020\ \Omega, \quad \lvert Z_\text{eq} \rvert = \frac{70.0\ \text{V}}{20.84\ \text{A}} = 3.359\ \Omega, \quad X_\text{eq} = 3.200\ \Omega \end{aligned}

The impedance voltage is 70/2400=2.92 %70/2400 = 2.92\ \%.

Check: these are the values the model was built from, so the method recovers them. The no-load power factor is 120/(240⋅2.55)=0.196120/(240 \cdot 2.55) = 0.196, low as expected: the shunt branch is mainly inductive. In the SC test the core flux is 70/2400=2.9 %70/2400 = 2.9\ \% of normal, so the core loss in it is about 0.0292⋅120 W=0.1 W0.029^2 \cdot 120\ \text{W} = 0.1\ \text{W}, invisible next to 443 W443\ \text{W}; the netlist lab below shows only 3.65 mA3.65\ \text{mA} in the magnetising branch during the SC test.

In Python: parameters and their uncertainty

The OC test is a low-power-factor measurement, where wattmeter errors matter. A Monte Carlo run draws meter errors of ±0.5 %\pm 0.5\ \% (V, I) and ±1 %\pm 1\ \% (P) of reading and shows how far the results move (Error Propagation and Monte Carlo).

python · try it yourself
import numpy as np
a = 10.0                                         # 2400/240 V
# open-circuit test on the LV side (HV open), short-circuit test on the HV side (LV shorted)
Voc, Ioc, Poc = 240.0, 2.55, 120.0
Vsc, Isc, Psc = 70.0, 20.84, 443.0

def params(Voc, Ioc, Poc, Vsc, Isc, Psc):
    Gc = Poc / Voc**2                            # shunt branch from the OC test (LV side)
    Y = Ioc / Voc
    Bm = np.sqrt(Y**2 - Gc**2)
    Rc, Xm = a**2 / Gc, a**2 / Bm                # referred to HV
    Req = Psc / Isc**2                           # series branch from the SC test (HV side)
    Zeq = Vsc / Isc
    Xeq = np.sqrt(Zeq**2 - Req**2)
    return Rc, Xm, Req, Xeq

Rc, Xm, Req, Xeq = params(Voc, Ioc, Poc, Vsc, Isc, Psc)
print(f"OC test: pf = {Poc/(Voc*Ioc):.3f}, Rc = {Rc/1e3:.2f} kOhm, Xm = {Xm/1e3:.2f} kOhm (HV side)")
print(f"SC test: pf = {Psc/(Vsc*Isc):.3f}, Req = {Req:.3f} Ohm, Xeq = {Xeq:.3f} Ohm (HV side)")
print(f"Zbase = {2400**2/50e3:.1f} Ohm: Req = {Req/115.2*100:.2f} %, Xeq = {Xeq/115.2*100:.2f} %, "
      f"impedance voltage = {Vsc/2400*100:.2f} %")

# how far can meter errors move the answers? V and I +-0.5 %, P +-1 % of reading, uniform, 20000 draws
rng = np.random.default_rng(1)
u = lambda x, e: x * (1 + rng.uniform(-e, e, 20000))
out = np.array(params(u(Voc, .005), u(Ioc, .005), u(Poc, .01), u(Vsc, .005), u(Isc, .005), u(Psc, .01)))
for name, col, unit in (("Rc", 0, "kOhm"), ("Xm", 1, "kOhm"), ("Req", 2, "Ohm"), ("Xeq", 3, "Ohm")):
    s = out[col] / (1e3 if unit == "kOhm" else 1)
    print(f"{name:3s}: {np.mean(s):7.3f} {unit}, spread (2 sd) +-{2 * np.std(s) / np.mean(s) * 100:.1f} %")
OC test: pf = 0.196, Rc = 48.00 kOhm, Xm = 9.60 kOhm (HV side)
SC test: pf = 0.304, Req = 1.020 Ohm, Xeq = 3.200 Ohm (HV side)
Zbase = 115.2 Ohm: Req = 0.89 %, Xeq = 2.78 %, impedance voltage = 2.92 %
Rc :  47.999 kOhm, spread (2 sd) +-1.6 %
Xm :   9.598 kOhm, spread (2 sd) +-0.8 %
Req:   1.020 Ohm, spread (2 sd) +-1.6 %
Xeq:   3.200 Ohm, spread (2 sd) +-0.8 %

The resistances inherit the wattmeter's error (and twice the voltmeter's or ammeter's, because they enter squared); the reactances are less sensitive. In real tests the wattmeter's own phase error at power factors near 0.20.2 is often the largest term, which is why test standards specify low-power-factor wattmeters or power analysers. Load losses measured at the test temperature are also corrected to a reference temperature, 75 ∘C75\,^\circ\text{C} for many transformer classes (IEC 60076-1:2011 as of 2026), because copper resistance rises about 0.4 %0.4\ \% per kelvin.

Interactive: the short-circuit test

The SC test on T1 in the netlist lab (calculation only: the real test uses a high-current source). At the default 70 V70\ \text{V} the lab shows I(VSC)=20.84 AI(VSC) = 20.84\ \text{A}, rated current, and only 3.652 mA3.652\ \text{mA} in LM. Slide the test voltage: the current scales linearly, because the series branch is linear; the shunt branch stays negligible. The lab also sweeps frequency on its plot; only the readouts at the 50 Hz50\ \text{Hz} cursor matter here.

0102030100m1101001k10kf (Hz)|V| (V)|V(r)|phasors at f = 50.00 Hz (magnitude @ phase)V(p)70.0 V @ 0.0 degV(q)67.6 V @ 8.5 degV(r)35.1 V @ -0.3 degV(s)33.3 V @ 17.7 degI(VSC)20.8 A @ 107.7 degI(R1)20.8 A @ -72.3 degI(L1)20.8 A @ -72.3 degI(RC)730 uA @ -0.3 degI(LM)3.65 mA @ -90.3 degI(R2)20.8 A @ -72.3 degI(L2)20.8 A @ -72.3 deg

Guided lab: OC and SC tests on a signal transformer

Hand calculation. For a small 1 ⁣: ⁣11\!:\!1 line or audio transformer rated for a few volts, plan an OC test at its rated signal level (say 1 V1\ \text{V} rms at 1 kHz1\ \text{kHz}) and an SC test at a current that warms nothing (say 20 mA20\ \text{mA}). Estimate VscV_\text{sc} from the winding resistances and the shorted inductance you measured in the equivalent-circuit lab.

Simulation. Put your readings into the Python function (with a=1a = 1) and run the Monte Carlo with your meters' accuracy.

What you would measure. Drive the winding from a function generator, read current with a series 10 Ω10\ \Omega resistor and the oscilloscope, voltage directly, and power as the cycle average of the product (scope math). Expect a very low OC power factor (below 0.10.1) and an SC power factor that is mostly resistive at low frequency. The OC power, a few milliwatts, is the hardest number: treat it as ±20 %\pm 20\ \% after deskewing the probes.

Hazards and safe setup. Signal levels only. Never perform these tests on a mains transformer or motor: the OC test would need mains voltage on a winding and the SC test needs a deliberately shorted winding at rated current.

Pitfalls

  • Swapping the sides. OC on LV and SC on HV is the convention for convenience; the parameters come out referred to the side measured.
  • Using the SC power as the core loss (or the OC power as the copper loss). Each test isolates one branch.
  • Forgetting temperature. Copper loss must be corrected to the reference temperature before it is compared with a guarantee.
  • Running the OC test away from rated voltage. The shunt branch is nonlinear; it must be measured at the voltage it will see.

Practice

  1. A 10 kVA10\ \text{kVA}, 400/230 V400/230\ \text{V} transformer gives OC (LV side): 230 V230\ \text{V}, 1.2 A1.2\ \text{A}, 70 W70\ \text{W}; SC (HV side): 16 V16\ \text{V}, 25 A25\ \text{A}, 180 W180\ \text{W}. Find all parameters referred to HV.
  2. What is its impedance voltage and the full-load copper loss?
  3. Why does the SC test need only a few percent of rated voltage?
Answer
  1. a=400/230=1.739a = 400/230 = 1.739, a2=3.025a^2 = 3.025. OC: Gc=70/2302=1.323 mSG_c = 70/230^2 = 1.323\ \text{mS}, ∣Y∣=5.217 mS\lvert Y \rvert = 5.217\ \text{mS}, Bm=5.047 mSB_m = 5.047\ \text{mS}; LV side Rc=756 ΩR_c = 756\ \Omega, Xm=198 ΩX_m = 198\ \Omega; HV side Rc=2.29 kΩR_c = 2.29\ \text{k}\Omega, Xm=599 ΩX_m = 599\ \Omega. SC: Req=180/625=0.288 ΩR_\text{eq} = 180/625 = 0.288\ \Omega, ∣Zeq∣=0.640 Ω\lvert Z_\text{eq} \rvert = 0.640\ \Omega, Xeq=0.572 ΩX_\text{eq} = 0.572\ \Omega.
  2. Rated HV current is 10 000/400=25 A10\,000/400 = 25\ \text{A}, so the test was at rated current: impedance voltage 16/400=4 %16/400 = 4\ \%, full-load copper loss 180 W180\ \text{W}.
  3. The series impedance is only a few percent of the base impedance, so a few percent of rated voltage drives rated current through it.

Test yourself

The power measured in the open-circuit test is mainly…

  1. copper loss
  2. core loss
  3. stray load loss
  4. mechanical loss

In the short-circuit test the shunt branch can be neglected because…

  1. it is disconnected
  2. the applied voltage, and so the core flux, is only a few percent of rated
  3. the current is too small
  4. the test is at DC

SC test readings: 70 V, 20.84 A, 443 W. The equivalent series resistance is…

  1. 3.36 Ω3.36\ \Omega
  2. 1.02 Ω1.02\ \Omega
  3. 0.29 Ω0.29\ \Omega
  4. 21.3 Ω21.3\ \Omega

Why is the open-circuit test usually done on the low-voltage winding?

  1. the core loss is smaller there
  2. rated voltage is lower and easier to supply, and the current is larger and easier to read
  3. the HV winding would saturate
  4. the standard forbids the HV side