Synchronous Phasor Diagrams and the Power-Angle Curve
A turbine governor opens the steam valve on a generator connected to the grid. The machine cannot speed up: the grid holds it at . So where does the extra power go, and how much more can the machine take before it falls out of step? The answer is an angle. The rotor moves a few degrees ahead of the grid's voltage phasor, and the electrical power rises as the sine of that load angle . This lesson draws the phasor diagrams of the synchronous machine model, derives the power-angle equation for round and salient rotors, and finds the steady-state stability limit.
Safety: grid-connected synchronous machines are high-voltage plant: this lesson is calculation and simulation only.
Phasor diagrams
Per phase, generator convention, neglected: . Take as the reference. The drop is always ahead of , and closes the triangle. The load angle is the angle from to ; physically it is the angle (in electrical degrees) by which the rotor's field axis leads the rotating reference set by the terminal voltage (close to the resultant air-gap field when the leakage reactance is small).
Three cases appear as the field current changes at constant power:
- Over-excited (): lags ; the generator delivers reactive power (like a capacitor bank seen from the grid).
- Unity power factor: .
- Under-excited (): leads; the generator absorbs reactive power.
For a motor, power flows in, lags and is negative: the rotor is dragged behind the field by the load.
The power-angle equation
Project the triangle onto the direction perpendicular to : . Multiplying by gives the real power, and the component along gives the reactive power (per machine, three phases):
At constant excitation follows a sine. Its peak, the steady-state stability limit (pull-out power), sits at :
Below a small increase of raises the electrical power, which brakes the rotor back: the operation is stable, with a synchronising power . Beyond more angle gives less power, the turbine's surplus accelerates the rotor further and it slips a pole: loss of synchronism, which protection must trip. In practice generators run at of –, leaving margin for faults (transient stability, in Power Systems). The equation also shows why a strong field helps stability: a larger (or a smaller , a high SCR) raises .
Salient poles: reluctance power
A salient-pole rotor has a small air gap along the pole axis (the d-axis) and a large one between poles (the q-axis), so its reactance depends on direction: , typically –. Splitting the armature current into d and q parts (two-reaction theory) gives
The second term needs no field current at all: it is reluctance power, the rotor's iron trying to align with the field. It shifts the peak to below and makes it higher. A rotor with saliency but no field winding is a synchronous reluctance motor (Stepper and Reluctance Motors).
Worked example: rated load and a turbine step
Given: the course's generator (, , 4 poles, ) on a bus ( phase), at rated current and pf 0.85 lagging, which needs , .
Find: , and torque; ; the new load angle when the turbine raises the power to at unchanged excitation.
Solve:
Check: and (to the rounding of and ). The machine is loaded to 46 % of its pull-out power, a comfortable margin; is stable () but exceeds the thermal rating whatever the vars, so it is allowed only briefly, if at all: stability and heating are separate limits.
In Python: power-angle curves
import numpy as np
VL = 6600.0; V = VL / np.sqrt(3) # the 5 MVA, 6.6 kV, 4-pole generator
Xs, Xd, Xq = 8.0, 8.0, 5.0 # round rotor Xs; salient-pole version Xd, Xq (ohm)
ws = 4 * np.pi * 50 / 4 # 157.08 rad/s
Ef = 6388.0 # excitation of the rated 0.85-lagging point
def P_round(d):
return 3 * V * Ef * np.sin(d) / Xs
def P_salient(d):
return 3 * V * Ef * np.sin(d) / Xd + 1.5 * V**2 * (1 / Xq - 1 / Xd) * np.sin(2 * d)
d = np.radians(np.arange(0, 180.01, 0.01))
for name, P in (("round rotor", P_round(d)), ("salient pole", P_salient(d))):
k = np.argmax(P)
print(f"{name:12s}: P_max = {P[k]/1e6:.3f} MW at delta = {np.degrees(d[k]):.1f} deg")
print("delta (deg) P round (MW) Q round (Mvar) P salient (MW) T round (kN m)")
for deg in (0, 15, 27.7, 45, 60, 90, 120):
r = np.radians(deg)
Q = 3 * V * (Ef * np.cos(r) - V) / Xs
print(f"{deg:7.1f} {P_round(r)/1e6:8.3f} {Q/1e6:8.3f} {P_salient(r)/1e6:8.3f} {P_round(r)/ws/1e3:7.2f}")
P_new = 6e6 # the turbine opens up to 6 MW, excitation unchanged
d_new = np.arcsin(P_new / (3 * V * Ef / Xs))
print(f"at 6 MW: delta = {np.degrees(d_new):.1f} deg, synchronising power dP/d(delta) = "
f"{3*V*Ef*np.cos(d_new)/Xs/1e6*np.pi/180:.3f} MW per degree")
import matplotlib.pyplot as plt
plt.plot(np.degrees(d), P_round(d) / 1e6, label="round rotor, Xs = 8 ohm")
plt.plot(np.degrees(d), P_salient(d) / 1e6, "--", label="salient, Xd = 8, Xq = 5 ohm")
plt.axvline(27.7, color="grey", lw=0.8)
plt.xlabel("load angle delta (deg)"); plt.ylabel("P (MW)"); plt.legend(); plt.grid(True)
plt.show()round rotor : P_max = 9.128 MW at delta = 90.0 deg
salient pole: P_max = 9.643 MW at delta = 72.8 deg
delta (deg) P round (MW) Q round (Mvar) P salient (MW) T round (kN m)
0.0 0.000 3.683 0.000 0.00
15.0 2.363 3.372 3.179 15.04
27.7 4.243 2.637 5.588 27.01
45.0 6.455 1.010 8.088 41.09
60.0 7.905 -0.881 9.320 50.33
90.0 9.128 -5.445 9.128 58.11
120.0 7.905 -10.009 6.490 50.33
at 6 MW: delta = 41.1 deg, synchronising power dP/d(delta) = 0.120 MW per degree
The salient-pole curve (same for comparison) peaks higher and earlier, at . Note how falls as grows at constant : pushing more real power through the same excitation uses up the reactive margin, and past (where ) the generator starts absorbing vars.
Guided lab (simulation)
Hand calculation. For (the unity-power-factor excitation at rated current), find at and .
Simulation. Set Ef = 5173.0 in the code and confirm that at and that the margin to pull-out is smaller than at lagging power factor.
What you would measure. At a power station the load angle is measured, not just computed: a tooth wheel or encoder on the shaft gives the rotor position, compared with the zero crossings of the terminal voltage. Operators read , , and on the control system; for this machine at rated lagging load you would expect within a few degrees of (saturation and shift it), and the plant's capability chart (V-Curves and the Infinite Bus) shows the limits. This is not a learner experiment.
Pitfalls
- Mechanical against electrical degrees. is electrical; on a 4-pole machine the rotor shifts mechanically.
- Applying at to salient-pole machines. Their peak comes earlier.
- Forgetting that is set by the prime mover, by the field on an infinite bus. Raising the field does not export more watts.
- Using in line values with in phase values. Keep everything per phase, then multiply by 3.
Practice
- A round-rotor machine has , , . Find .
- The same machine delivers . What is ?
- A 6-pole machine on develops . Find its torque.
Answer
- .
- .
- , .
Test yourself
At constant excitation, a round-rotor synchronous generator reaches its maximum power at a load angle of…
- 0°
- 45°
- 90°
- 180°
A generator on an infinite bus is over-excited. It…
- absorbs reactive power
- delivers reactive power
- delivers more real power
- runs faster
The term in a salient-pole machine's power comes from…
- the field winding
- the difference between and (reluctance)
- armature resistance
- the damper winding
In a synchronous motor, the load angle (from to ) is…
- positive
- negative
- always 90°
- zero