Home › Electrical Machines & Transformers › Parallel Operation and Inrush Current

Parallel Operation and Inrush Current

A growing factory adds a second transformer next to the first and connects their LV busbars together. If the two units are well matched they share the load in proportion to their ratings; if not, the smaller one overheats while the larger idles, or a current circulates between them with no load at all. And every time either unit is switched on, its supply breaker may trip for no apparent reason, because a transformer energised at the wrong instant draws an inrush current many times its rating for a fraction of a second. Both effects follow from what you already know: parallel operation from the series impedance (Transformer Phasor Diagrams), inrush from the B–H curve (B–H Curves and Saturation).

Safety: paralleling and energising power transformers is calculation and simulation only in this course; the bench part uses a low-voltage RL circuit.

Conditions for parallel operation

Condition If violated
same voltage ratio (within about 0.5 %) a circulating current flows at no load
same polarity and the same vector group (clock number) a huge circulating current: a short circuit through the windings (Vector Groups)
same phase sequence (three-phase) short circuit
similar per-unit impedance on their own ratings load does not share in proportion to rating
similar X/RX/R ratio the currents are out of phase and their sum exceeds the load current

The first three are mandatory; the last two decide how well the pair performs. IEC 60076-8 (the application guide for power transformers) discusses these conditions in detail.

Load sharing

With the same ratio, the two units are two impedances in parallel between the same buses, so the load divides inversely as their impedances on a common base:

SA=Sload zBzA+zB,SB=Sload zAzA+zB\mathbf{S}_A = \mathbf{S}_\text{load}\,\frac{\mathbf{z}_B}{\mathbf{z}_A + \mathbf{z}_B}, \qquad \mathbf{S}_B = \mathbf{S}_\text{load}\,\frac{\mathbf{z}_A}{\mathbf{z}_A + \mathbf{z}_B}

Each unit takes load in proportion to its rating only if the per-unit impedances on their own ratings are equal: a big unit has a small impedance in ohms, so it takes more current. If the smaller unit has the lower per-unit impedance, it reaches its rating first and limits the whole bank.

A ratio mismatch Δv\Delta v (per unit) drives a circulating current Δv/(zA+zB)\Delta v/(z_A + z_B) even with no load; with typical impedances of 0.050.05 to 0.10.1 pu each, every 1 %1\ \% of ratio difference circulates 5 to 10 % of rated current.

Worked example: a 500 kVA and a 1000 kVA unit

Given: TA: 500 kVA500\ \text{kVA}, z=4.75 %z = 4.75\ \%; TB: 1000 kVA1000\ \text{kVA}, z=6 %z = 6\ \%; same ratio and group, X/R=5X/R = 5 for both; a 1.4 MVA1.4\ \text{MVA} load.

Find: the share of each unit, and the largest load before either is overloaded.

Solve: on a 1 MVA1\ \text{MVA} base, zA=0.0475⋅2=0.095 puz_A = 0.0475 \cdot 2 = 0.095\ \text{pu} and zB=0.060 puz_B = 0.060\ \text{pu} (same angle, so magnitudes suffice):

SA=1.4 MVA⋅0.0600.095+0.060=542 kVA (108 %),SB=1.4⋅0.0950.155=858 kVA (86 %)Smax=500 kVA⋅0.1550.060=1292 kVA\begin{aligned} S_A &= 1.4\ \text{MVA} \cdot \frac{0.060}{0.095 + 0.060} = 542\ \text{kVA}\ (108\ \%), \qquad S_B = 1.4 \cdot \frac{0.095}{0.155} = 858\ \text{kVA}\ (86\ \%) \\ S_\text{max} &= 500\ \text{kVA} \cdot \frac{0.155}{0.060} = 1292\ \text{kVA} \end{aligned}

Check: 542+858=1400 kVA542 + 858 = 1400\ \text{kVA}. Because TA has the lower per-unit impedance on its own rating, it takes more than its share and the bank can only supply 12921292 of its 1500 kVA1500\ \text{kVA}, 86 %. Had both been 6 %6\ \%, they would share 467467 and 933 kVA933\ \text{kVA}, both at 93 %.

python · try it yourself
import numpy as np
# two transformers in parallel on a 1 MVA base: TA 500 kVA z = 4.75 %, TB 1000 kVA z = 6 % (X/R = 5 for both)
def z(pct, S, xr=5.0):
    zpu = pct / 100 * 1e6 / S
    return zpu * (1 + 1j * xr) / np.hypot(1, xr)
zA, zB = z(4.75, 500e3), z(6.0, 1000e3)
SA, SB = 500e3, 1000e3
for Sload in (1.0e6, 1.4e6):
    s = Sload / 1e6
    sA, sB = s * zB / (zA + zB), s * zA / (zA + zB)
    print(f"load {Sload/1e6:.1f} MVA: TA {abs(sA)*1e3:5.0f} kVA ({abs(sA)*1e6/SA*100:3.0f} %), "
          f"TB {abs(sB)*1e3:5.0f} kVA ({abs(sB)*1e6/SB*100:3.0f} %)")
Smax = SA / 1e6 * abs(zA + zB) / abs(zB)
print(f"largest load before TA reaches its rating: {Smax*1e3:.0f} kVA of {(SA+SB)/1e3:.0f} kVA installed")
# a 1 % ratio mismatch: circulating current with no load
ic = 0.01 / abs(zA + zB)
print(f"1 % ratio difference: circulating {ic:.3f} pu = {ic*1e6/SA*100:.0f} % of TA's rating at no load")
# different vector groups (Dy1 with Dy11): 60 degrees apart
dv = abs(1 - np.exp(1j * np.pi / 3))
print(f"Dy1 with Dy11: voltage difference {dv:.2f} pu, circulating {dv/abs(zA+zB):.1f} pu = {dv/abs(zA+zB)*1e6/SA:.0f} x TA rating")
load 1.0 MVA: TA   387 kVA ( 77 %), TB   613 kVA ( 61 %)
load 1.4 MVA: TA   542 kVA (108 %), TB   858 kVA ( 86 %)
largest load before TA reaches its rating: 1292 kVA of 1500 kVA installed
1 % ratio difference: circulating 0.065 pu = 13 % of TA's rating at no load
Dy1 with Dy11: voltage difference 1.00 pu, circulating 6.5 pu = 13 x TA rating

The last line is why the vector group is on the nameplate: a 60∘60^\circ mismatch circulates thirteen times TA's rated current, a fault that the protection must clear at once.

Inrush current

In steady state, a transformer's flux linkage lags its voltage by 90∘90^\circ: it peaks at λm\lambda_m when the voltage crosses zero. Switch on exactly at a voltage zero and the flux must start from its residual value λr\lambda_r, not from −λm-\lambda_m. Integrating the first half-cycle of voltage then carries it to

λpeak=λr+2λm\lambda_\text{peak} = \lambda_r + 2\lambda_m

the doubling effect. A core designed to run at 1.6 T1.6\ \text{T} would need well over 3 T3\ \text{T}, far beyond saturation. Once saturated, the core behaves almost like air: the winding's inductance falls from the magnetising value to the air-core value, tens or hundreds of times smaller, and the current shoots up. The offset in flux then decays only as fast as the winding resistance dissipates it, so the inrush dies away over many cycles, from a fraction of a second in small units to many seconds (in large power transformers sometimes tens of seconds) in large ones. Switching at a voltage peak starts the flux at its natural value and, with no residual flux, gives no inrush at all, which is what controlled (point-on-wave) switching does.

Inrush current is one-sided and rich in second harmonic, unlike a fault current. Transformer differential protection uses that: it restrains tripping while the second harmonic exceeds a set fraction of the fundamental (commonly around 15 to 20 %, a relay setting, not a standard value).

In Python: energising T1

The program integrates dλ/dt=v−R1i(λ)d\lambda/dt = v - R_1 i(\lambda) for T1's HV winding with the LV open, using a λ\lambda–ii curve that is linear (Lm=30.56 HL_m = 30.56\ \text{H}) up to a knee at 1.15λm1.15\lambda_m and has an air-core slope of 50 mH50\ \text{mH} beyond it (illustrative values for a unit of this size).

python · try it yourself
import numpy as np
from scipy.integrate import solve_ivp
# T1 energised on its 2400 V winding with the LV side open; flux linkage lam of the HV winding
V, f, R = 2400.0, 50.0, 0.5
w = 2 * np.pi * f
lam_m = np.sqrt(2) * V / w                        # rated peak flux linkage (V s)
Lm, Lair, knee = 30.56, 0.05, 1.15 * lam_m        # unsaturated L, air-core L of the winding, knee

def i_of_lam(lam):                                # smooth piecewise-linear lambda-i curve
    x = (np.abs(lam) - knee) / (0.02 * lam_m)
    excess = 0.02 * lam_m * np.logaddexp(0, x)    # ~ max(0, |lam| - knee), smoothed
    return np.sign(lam) * (np.abs(lam) / Lm + excess / Lair)

def energise(theta_deg, lam_r, T=1.0):
    th = np.radians(theta_deg)
    rhs = lambda t, y: [np.sqrt(2) * V * np.sin(w * t + th) - R * i_of_lam(y[0])]
    t = np.arange(0, T, 1e-4)
    sol = solve_ivp(rhs, (0, T), [lam_r], t_eval=t, max_step=2e-4, rtol=1e-6, atol=1e-6)
    return t, i_of_lam(sol.y[0])

Irated_pk = np.sqrt(2) * 50e3 / V
print(f"rated peak current {Irated_pk:.1f} A, rated peak flux linkage {lam_m:.2f} V s")
for th, lr, label in ((0, 0.0, "switched at voltage zero, no residual flux"),
                      (0, 0.6 * lam_m, "voltage zero, residual flux +0.6 pu"),
                      (90, 0.0, "switched at voltage peak, no residual flux")):
    t, i = energise(th, lr)
    cyc = lambda k: np.abs(i[(t >= k / f) & (t < (k + 1) / f)]).max()
    print(f"{label}:")
    print("   peak in cycle 1, 5, 10, 25, 50 (A):", "  ".join(f"{cyc(k):6.1f}" for k in (0, 4, 9, 24, 49)),
          f"  first peak = {cyc(0)/Irated_pk:.1f} x rated")
    seg = i[(t >= 0) & (t < 1 / f)]
    c = np.abs(np.fft.rfft(seg))
    print(f"   first cycle: 2nd harmonic = {c[2]/c[1]*100:.0f} % of fundamental")
rated peak current 29.5 A, rated peak flux linkage 10.80 V s
switched at voltage zero, no residual flux:
   peak in cycle 1, 5, 10, 25, 50 (A):  179.1   144.2   113.5    63.6    31.6   first peak = 6.1 x rated
   first cycle: 2nd harmonic = 52 % of fundamental
voltage zero, residual flux +0.6 pu:
   peak in cycle 1, 5, 10, 25, 50 (A):  302.2   227.2   168.1    84.4    38.4   first peak = 10.3 x rated
   first cycle: 2nd harmonic = 22 % of fundamental
switched at voltage peak, no residual flux:
   peak in cycle 1, 5, 10, 25, 50 (A):    0.4     0.4     0.4     0.4     0.4   first peak = 0.0 x rated
   first cycle: 2nd harmonic = 0 % of fundamental

Switched at a voltage zero, T1 draws a first peak of six times its rated peak current, and ten times with residual flux in the same direction, while its normal no-load current peaks at 0.4 A0.4\ \text{A}. After a second (50 cycles) the inrush is still about one rated peak. The numbers depend strongly on the assumed air-core inductance and knee, which is why real inrush figures come from the manufacturer or from measurements, but the pattern (worst at voltage zero, worse with residual flux, absent at the voltage peak, slow decay, strong second harmonic) is general.

Interactive: the decay of an offset

The decay of the inrush is the decay of a DC offset in an inductive circuit: the time constant L/RL/R sets it. The RL lab shows the idea at bench scale, 12 V12\ \text{V}, 10 Ω10\ \Omega, 100 mH100\ \text{mH}: τ=10.0 ms\tau = 10.0\ \text{ms}, and at t=1τt = 1\tau the current has reached 63.2 %63.2\ \% of its final 1.2 A1.2\ \text{A} (759 mA759\ \text{mA}). In a saturated transformer the effective inductance changes during the decay (small while saturated, large once out of saturation), so the inrush decays fast at first and slowly at the end, as the program's peaks show.

+-R = 10.0 Ohmswitch closed at t = 0V = 12.0 V, L = 100 mHtau = L/R = 10.0 mst10.0 mst/tau1.00vL4.41 Vi759 mAvR7.59 V0.03.06.09.012.001 tau2 tau3 tau4 tau5 tau6 tautv (V)0 A600 mA1.2 Ai63.2 %5 tau: 99.3 %vL(t), inductor voltagei(t)

Guided lab: an RL switch-on at low voltage

Hand calculation. For an inductor of known LL and winding resistance RR (measure both), plus a series resistor, predict τ=L/Rtotal\tau = L/R_\text{total} and the current after 1τ1\tau and 5τ5\tau for a step from a bench supply.

Simulation. The RL lab with your values.

What you would measure. Use a small iron-cored choke or a relay coil, a series 10 Ω10\ \Omega resistor as a current shunt, and a 12 V12\ \text{V} bench supply with the current limit set above the expected final current. Capture the shunt voltage on an oscilloscope triggered on the rising edge. Expect τ\tau within about 10 % of the hand value (the inductance of an iron-cored part depends on current). Increase the supply until the final current approaches the choke's rated current: the rise then gets faster near the end as the core starts to saturate, a gentle version of what drives transformer inrush.

Hazards and safe setup. Low voltage, current-limited supply. Put a diode across the inductor before you switch off: the inductive kick at turn-off can exceed hundreds of volts on an open contact. The resistor warms up; keep the duty cycle low.

Pitfalls

  • Paralleling by ratings alone. Check the vector group and the per-unit impedance on each unit's own rating.
  • Expecting proportional sharing with unequal zz. The unit with the lower per-unit impedance overloads first.
  • Calling inrush a fault. It is one-sided and full of second harmonic; protection is set to ride through it.
  • Forgetting residual flux. A transformer de-energised a moment ago can give a worse inrush than a cold one.

Practice

  1. Two 1 MVA1\ \text{MVA} units with z=5 %z = 5\ \% and 6 %6\ \% share a 1.8 MVA1.8\ \text{MVA} load. Find each unit's load.
  2. Two identical units, z=6 %z = 6\ \% each, have ratios differing by 0.5 %0.5\ \%. What circulating current flows at no load?
  3. In the inrush program, why does switching at the voltage peak produce no inrush?
Answer
  1. On a 1 MVA1\ \text{MVA} base, S1=1.8⋅0.06/0.11=0.982 MVAS_1 = 1.8 \cdot 0.06/0.11 = 0.982\ \text{MVA} (98 %), S2=1.8⋅0.05/0.11=0.818 MVAS_2 = 1.8 \cdot 0.05/0.11 = 0.818\ \text{MVA} (82 %).
  2. 0.005/(0.06+0.06)=0.042 pu0.005/(0.06 + 0.06) = 0.042\ \text{pu}, about 4 % of rated current, flowing all the time.
  3. At the voltage peak the steady-state flux is zero; starting from zero flux there is no offset, so the flux swings between ±λm\pm\lambda_m from the first cycle and never reaches the knee.

Test yourself

Which condition is NOT strictly necessary for two transformers to operate in parallel?

  1. same vector group
  2. same phase sequence
  3. same voltage ratio
  4. identical kVA ratings

A 500 kVA unit with z = 4.75 % and a 1000 kVA unit with z = 6 % share a load. Which overloads first?

  1. the 500 kVA unit
  2. the 1000 kVA unit
  3. both together
  4. neither

The worst-case inrush occurs when a transformer is switched on…

  1. at a voltage peak
  2. at a voltage zero, with residual flux in the same direction as the flux the first half-cycle builds
  3. at no load
  4. at a voltage zero with no residual flux

Which feature of inrush current lets differential protection tell it from a fault?

  1. it is purely sinusoidal
  2. a large second-harmonic content
  3. it has no DC component
  4. it flows only in the LV winding