Parallel Operation and Inrush Current
A growing factory adds a second transformer next to the first and connects their LV busbars together. If the two units are well matched they share the load in proportion to their ratings; if not, the smaller one overheats while the larger idles, or a current circulates between them with no load at all. And every time either unit is switched on, its supply breaker may trip for no apparent reason, because a transformer energised at the wrong instant draws an inrush current many times its rating for a fraction of a second. Both effects follow from what you already know: parallel operation from the series impedance (Transformer Phasor Diagrams), inrush from the B–H curve (B–H Curves and Saturation).
Safety: paralleling and energising power transformers is calculation and simulation only in this course; the bench part uses a low-voltage RL circuit.
Conditions for parallel operation
| Condition | If violated |
|---|---|
| same voltage ratio (within about 0.5 %) | a circulating current flows at no load |
| same polarity and the same vector group (clock number) | a huge circulating current: a short circuit through the windings (Vector Groups) |
| same phase sequence (three-phase) | short circuit |
| similar per-unit impedance on their own ratings | load does not share in proportion to rating |
| similar ratio | the currents are out of phase and their sum exceeds the load current |
The first three are mandatory; the last two decide how well the pair performs. IEC 60076-8 (the application guide for power transformers) discusses these conditions in detail.
Load sharing
With the same ratio, the two units are two impedances in parallel between the same buses, so the load divides inversely as their impedances on a common base:
Each unit takes load in proportion to its rating only if the per-unit impedances on their own ratings are equal: a big unit has a small impedance in ohms, so it takes more current. If the smaller unit has the lower per-unit impedance, it reaches its rating first and limits the whole bank.
A ratio mismatch (per unit) drives a circulating current even with no load; with typical impedances of to pu each, every of ratio difference circulates 5 to 10 % of rated current.
Worked example: a 500 kVA and a 1000 kVA unit
Given: TA: , ; TB: , ; same ratio and group, for both; a load.
Find: the share of each unit, and the largest load before either is overloaded.
Solve: on a base, and (same angle, so magnitudes suffice):
Check: . Because TA has the lower per-unit impedance on its own rating, it takes more than its share and the bank can only supply of its , 86 %. Had both been , they would share and , both at 93 %.
import numpy as np
# two transformers in parallel on a 1 MVA base: TA 500 kVA z = 4.75 %, TB 1000 kVA z = 6 % (X/R = 5 for both)
def z(pct, S, xr=5.0):
zpu = pct / 100 * 1e6 / S
return zpu * (1 + 1j * xr) / np.hypot(1, xr)
zA, zB = z(4.75, 500e3), z(6.0, 1000e3)
SA, SB = 500e3, 1000e3
for Sload in (1.0e6, 1.4e6):
s = Sload / 1e6
sA, sB = s * zB / (zA + zB), s * zA / (zA + zB)
print(f"load {Sload/1e6:.1f} MVA: TA {abs(sA)*1e3:5.0f} kVA ({abs(sA)*1e6/SA*100:3.0f} %), "
f"TB {abs(sB)*1e3:5.0f} kVA ({abs(sB)*1e6/SB*100:3.0f} %)")
Smax = SA / 1e6 * abs(zA + zB) / abs(zB)
print(f"largest load before TA reaches its rating: {Smax*1e3:.0f} kVA of {(SA+SB)/1e3:.0f} kVA installed")
# a 1 % ratio mismatch: circulating current with no load
ic = 0.01 / abs(zA + zB)
print(f"1 % ratio difference: circulating {ic:.3f} pu = {ic*1e6/SA*100:.0f} % of TA's rating at no load")
# different vector groups (Dy1 with Dy11): 60 degrees apart
dv = abs(1 - np.exp(1j * np.pi / 3))
print(f"Dy1 with Dy11: voltage difference {dv:.2f} pu, circulating {dv/abs(zA+zB):.1f} pu = {dv/abs(zA+zB)*1e6/SA:.0f} x TA rating")load 1.0 MVA: TA 387 kVA ( 77 %), TB 613 kVA ( 61 %)
load 1.4 MVA: TA 542 kVA (108 %), TB 858 kVA ( 86 %)
largest load before TA reaches its rating: 1292 kVA of 1500 kVA installed
1 % ratio difference: circulating 0.065 pu = 13 % of TA's rating at no load
Dy1 with Dy11: voltage difference 1.00 pu, circulating 6.5 pu = 13 x TA rating
The last line is why the vector group is on the nameplate: a mismatch circulates thirteen times TA's rated current, a fault that the protection must clear at once.
Inrush current
In steady state, a transformer's flux linkage lags its voltage by : it peaks at when the voltage crosses zero. Switch on exactly at a voltage zero and the flux must start from its residual value , not from . Integrating the first half-cycle of voltage then carries it to
the doubling effect. A core designed to run at would need well over , far beyond saturation. Once saturated, the core behaves almost like air: the winding's inductance falls from the magnetising value to the air-core value, tens or hundreds of times smaller, and the current shoots up. The offset in flux then decays only as fast as the winding resistance dissipates it, so the inrush dies away over many cycles, from a fraction of a second in small units to many seconds (in large power transformers sometimes tens of seconds) in large ones. Switching at a voltage peak starts the flux at its natural value and, with no residual flux, gives no inrush at all, which is what controlled (point-on-wave) switching does.
Inrush current is one-sided and rich in second harmonic, unlike a fault current. Transformer differential protection uses that: it restrains tripping while the second harmonic exceeds a set fraction of the fundamental (commonly around 15 to 20 %, a relay setting, not a standard value).
In Python: energising T1
The program integrates for T1's HV winding with the LV open, using a – curve that is linear () up to a knee at and has an air-core slope of beyond it (illustrative values for a unit of this size).
import numpy as np
from scipy.integrate import solve_ivp
# T1 energised on its 2400 V winding with the LV side open; flux linkage lam of the HV winding
V, f, R = 2400.0, 50.0, 0.5
w = 2 * np.pi * f
lam_m = np.sqrt(2) * V / w # rated peak flux linkage (V s)
Lm, Lair, knee = 30.56, 0.05, 1.15 * lam_m # unsaturated L, air-core L of the winding, knee
def i_of_lam(lam): # smooth piecewise-linear lambda-i curve
x = (np.abs(lam) - knee) / (0.02 * lam_m)
excess = 0.02 * lam_m * np.logaddexp(0, x) # ~ max(0, |lam| - knee), smoothed
return np.sign(lam) * (np.abs(lam) / Lm + excess / Lair)
def energise(theta_deg, lam_r, T=1.0):
th = np.radians(theta_deg)
rhs = lambda t, y: [np.sqrt(2) * V * np.sin(w * t + th) - R * i_of_lam(y[0])]
t = np.arange(0, T, 1e-4)
sol = solve_ivp(rhs, (0, T), [lam_r], t_eval=t, max_step=2e-4, rtol=1e-6, atol=1e-6)
return t, i_of_lam(sol.y[0])
Irated_pk = np.sqrt(2) * 50e3 / V
print(f"rated peak current {Irated_pk:.1f} A, rated peak flux linkage {lam_m:.2f} V s")
for th, lr, label in ((0, 0.0, "switched at voltage zero, no residual flux"),
(0, 0.6 * lam_m, "voltage zero, residual flux +0.6 pu"),
(90, 0.0, "switched at voltage peak, no residual flux")):
t, i = energise(th, lr)
cyc = lambda k: np.abs(i[(t >= k / f) & (t < (k + 1) / f)]).max()
print(f"{label}:")
print(" peak in cycle 1, 5, 10, 25, 50 (A):", " ".join(f"{cyc(k):6.1f}" for k in (0, 4, 9, 24, 49)),
f" first peak = {cyc(0)/Irated_pk:.1f} x rated")
seg = i[(t >= 0) & (t < 1 / f)]
c = np.abs(np.fft.rfft(seg))
print(f" first cycle: 2nd harmonic = {c[2]/c[1]*100:.0f} % of fundamental")rated peak current 29.5 A, rated peak flux linkage 10.80 V s
switched at voltage zero, no residual flux:
peak in cycle 1, 5, 10, 25, 50 (A): 179.1 144.2 113.5 63.6 31.6 first peak = 6.1 x rated
first cycle: 2nd harmonic = 52 % of fundamental
voltage zero, residual flux +0.6 pu:
peak in cycle 1, 5, 10, 25, 50 (A): 302.2 227.2 168.1 84.4 38.4 first peak = 10.3 x rated
first cycle: 2nd harmonic = 22 % of fundamental
switched at voltage peak, no residual flux:
peak in cycle 1, 5, 10, 25, 50 (A): 0.4 0.4 0.4 0.4 0.4 first peak = 0.0 x rated
first cycle: 2nd harmonic = 0 % of fundamental
Switched at a voltage zero, T1 draws a first peak of six times its rated peak current, and ten times with residual flux in the same direction, while its normal no-load current peaks at . After a second (50 cycles) the inrush is still about one rated peak. The numbers depend strongly on the assumed air-core inductance and knee, which is why real inrush figures come from the manufacturer or from measurements, but the pattern (worst at voltage zero, worse with residual flux, absent at the voltage peak, slow decay, strong second harmonic) is general.
Interactive: the decay of an offset
The decay of the inrush is the decay of a DC offset in an inductive circuit: the time constant sets it. The RL lab shows the idea at bench scale, , , : , and at the current has reached of its final (). In a saturated transformer the effective inductance changes during the decay (small while saturated, large once out of saturation), so the inrush decays fast at first and slowly at the end, as the program's peaks show.
Guided lab: an RL switch-on at low voltage
Hand calculation. For an inductor of known and winding resistance (measure both), plus a series resistor, predict and the current after and for a step from a bench supply.
Simulation. The RL lab with your values.
What you would measure. Use a small iron-cored choke or a relay coil, a series resistor as a current shunt, and a bench supply with the current limit set above the expected final current. Capture the shunt voltage on an oscilloscope triggered on the rising edge. Expect within about 10 % of the hand value (the inductance of an iron-cored part depends on current). Increase the supply until the final current approaches the choke's rated current: the rise then gets faster near the end as the core starts to saturate, a gentle version of what drives transformer inrush.
Hazards and safe setup. Low voltage, current-limited supply. Put a diode across the inductor before you switch off: the inductive kick at turn-off can exceed hundreds of volts on an open contact. The resistor warms up; keep the duty cycle low.
Pitfalls
- Paralleling by ratings alone. Check the vector group and the per-unit impedance on each unit's own rating.
- Expecting proportional sharing with unequal . The unit with the lower per-unit impedance overloads first.
- Calling inrush a fault. It is one-sided and full of second harmonic; protection is set to ride through it.
- Forgetting residual flux. A transformer de-energised a moment ago can give a worse inrush than a cold one.
Practice
- Two units with and share a load. Find each unit's load.
- Two identical units, each, have ratios differing by . What circulating current flows at no load?
- In the inrush program, why does switching at the voltage peak produce no inrush?
Answer
- On a base, (98 %), (82 %).
- , about 4 % of rated current, flowing all the time.
- At the voltage peak the steady-state flux is zero; starting from zero flux there is no offset, so the flux swings between from the first cycle and never reaches the knee.
Test yourself
Which condition is NOT strictly necessary for two transformers to operate in parallel?
- same vector group
- same phase sequence
- same voltage ratio
- identical kVA ratings
A 500 kVA unit with z = 4.75 % and a 1000 kVA unit with z = 6 % share a load. Which overloads first?
- the 500 kVA unit
- the 1000 kVA unit
- both together
- neither
The worst-case inrush occurs when a transformer is switched on…
- at a voltage peak
- at a voltage zero, with residual flux in the same direction as the flux the first half-cycle builds
- at no load
- at a voltage zero with no residual flux
Which feature of inrush current lets differential protection tell it from a fault?
- it is purely sinusoidal
- a large second-harmonic content
- it has no DC component
- it flows only in the LV winding