Distance Protection and Its Zones
Overcurrent relays struggle on meshed transmission networks: the fault current depends on which generators are running and which lines are in service, and it flows in from both ends. What does not change is the impedance of the line up to the fault. A distance relay divides the voltage at its location by the current and compares the result with the line impedance. A fault at of the line looks like , whatever the source strength. This lesson builds the stepped zones that make distance protection selective, and shows the effects that blur the measurement: fault resistance, infeed from the far end, load, and earth return.
Safety: transmission voltages are studied here by calculation and simulation only. Relay testing on real lines uses secondary-injection sets and is done by qualified protection engineers under permit.
What the relay measures
For a solid three-phase fault at a fraction of a line with series impedance , the relay voltage is , so
A real relay has six measuring loops: three phase-to-phase loops ( and so on) and three phase-to-earth loops. For an earth fault the return current flows partly in the ground, whose impedance per km is different, so the phase-to-earth loop uses residual compensation:
with and the positive- and zero-sequence line impedances (Sequence Networks). With this correction, every loop measures the positive-sequence impedance to the fault.
The relay's characteristic is a region on the R–X plane; it trips when falls inside. A mho circle passes through the origin, which makes it inherently directional. A quadrilateral has independent reactance and resistance reaches, which is useful for fault resistance on short lines.
Stepped zones
The relay cannot tell a fault at of its line from one at (just past the remote busbar): CT and VT errors, line-impedance data and relay tolerance together are worth to . So it uses several zones:
| Zone | Typical reach | Delay | Purpose |
|---|---|---|---|
| Zone 1 | to of the protected line | instantaneous | fast clearance of most of the line, never overreaching the remote bus |
| Zone 2 | about of the line (at least the whole line, at most half of the shortest next line) | to | the last to , and backup for the remote busbar |
| Zone 3 | protected line plus of the longest next line (load permitting) | to | remote backup for the next lines |
| reverse zone | behind the relay | used in schemes | blocking and weak-infeed logic |
Zone 1 at both ends overlaps in the middle to of the line, where both ends trip instantly. For the end zones, a communication channel (fibre or power-line carrier) lets each end accelerate the other: in a permissive overreach (POTT) scheme an end trips instantly when its own overreaching zone 2 sees the fault and the other end sends a permissive signal. Transmission lines also use line differential protection over fibre (Differential Protection).
Worked example: settings for a 132 kV line
Given: line A–B, , , . Next line B–C, , same conductor. CT 600/1, VT . Maximum load at pf .
Find: the zone reaches in primary and secondary ohms, , and the load impedance.
Solve:
Check: zone 3 ( at ) is well clear of the load point ( at ): a mho circle of diameter along reaches only in the load direction. On long, heavily loaded lines this margin vanishes, which is how zone 3 tripped on load during several large blackouts; modern relays add load-encroachment blinders.
In Python: fault resistance and infeed
A fault through resistance at the line midpoint, fed from both ends: source A behind , source B behind with its EMF behind A (power flows from A to B).
import numpy as np
import matplotlib.pyplot as plt
ZL = 100 * complex(0.08, 0.40)
VA = 132e3 / np.sqrt(3); VB = VA * np.exp(-1j * np.radians(10))
ZA, ZB = 5j, 8j
def apparent(m, RF):
# nodal equations for nodes r (relay bus A), f (fault), b (bus B)
Y = np.zeros((3, 3), complex)
def branch(i, j, z):
y = 1 / z
for k in (i, j):
if k is not None: Y[k, k] += y
if i is not None and j is not None: Y[i, j] -= y; Y[j, i] -= y
branch(0, None, ZA); branch(0, 1, m * ZL); branch(1, 2, (1 - m) * ZL)
branch(2, None, ZB); branch(1, None, RF)
V = np.linalg.solve(Y, np.array([VA / ZA, 0, VB / ZB]))
Ir = (V[0] - V[1]) / (m * ZL)
return V[0] / Ir
print("RF (Ohm) Z seen at A (Ohm) |Z| inside zone 1 mho?")
D = 0.8 * ZL # mho circle: diameter 0.8 ZL from the origin
for RF in [0.1, 5, 10, 20]:
Z = apparent(0.5, RF)
inside = abs(Z - D / 2) <= abs(D) / 2
print(f"{RF:6.1f} {Z.real:7.2f} + j{Z.imag:6.2f} {abs(Z):6.2f} {inside}")
th = np.linspace(0, 2 * np.pi, 200)
fig, ax = plt.subplots(figsize=(6.4, 3.6))
for k, lab in [(0.8, "Z1"), (1.2, "Z2"), (1.72, "Z3")]:
c = k * ZL / 2 if k < 1.5 else 172 * complex(0.08, 0.40) / 2
ax.plot((c + abs(c) * np.exp(1j * th)).real, (c + abs(c) * np.exp(1j * th)).imag, label=lab)
ax.plot([0, ZL.real], [0, ZL.imag], "k", lw=2, label="line A-B")
pts = [apparent(0.5, RF) for RF in np.linspace(0.1, 20, 20)]
ax.plot([p.real for p in pts], [p.imag for p in pts], "r.", label="midpoint fault, RF 0-20")
Zl = 165.5 * np.exp(1j * np.radians(18.2)); ax.plot(Zl.real, Zl.imag, "ks", label="max load")
ax.set_xlabel("R (Ohm, primary)"); ax.set_ylabel("X (Ohm)"); ax.set_aspect("equal")
ax.set_xlim(-40, 170); ax.set_ylim(-20, 80); ax.grid(alpha=0.3); ax.legend(fontsize=7)
fig.tight_layout()
plt.show()RF (Ohm) Z seen at A (Ohm) |Z| inside zone 1 mho?
0.1 4.19 + j 19.98 20.42 True
5.0 13.11 + j 19.16 23.22 True
10.0 21.69 + j 18.34 28.41 False
20.0 37.44 + j 16.77 41.02 False
The fault is at (half of ) when bolted. With of fault resistance the relay sees about of extra resistance, not : current from B flows through too, so the voltage across it is larger than times A's current alone. The point also drops slightly in X because B's current is not in phase with A's. The fault leaves the zone 1 mho circle, which is why quadrilateral characteristics with a generous resistive reach are used for earth faults.
Interactive: the two-ended fault
The same circuit as a netlist: sources (phase), A behind (), B behind () at , two half-lines of and , and the fault resistor RF at the midpoint. Read V(r) and I(R1) at the cursor (the lab also sweeps frequency) and divide them: at the lab shows about and , a apparent impedance as in the table. Lower RF and watch the current rise and the angle between them approach the line angle.
Guided lab: apparent impedance on a resistor model
Hand calculation. Build a DC analogue of the two-ended line on paper: a source A behind , two "half-line" resistors, a source B behind , and a fault resistor from the midpoint to ground. Predict the ratio at A for and , and the ratio with source B disconnected.
Simulation. Enter the same network in the netlist lab with analysis set to DC (or in NumPy), and compare.
What you would measure. Two current-limited bench supplies (both outputs floating, negatives joined as "ground"), resistors, DMMs for and . Use resistors at least: at the A-side carries (), and () with B disconnected. Expect the apparent "impedance" to grow above when B feeds in, just as in the AC case (about instead of at , instead of at ), within the resistor tolerance and DMM uncertainty (about on the ratio).
Hazards and safe setup. Both supplies with current limits of ; check resistor power () before switching on; a supply driven backwards by the other one can be damaged, so add a series diode if your supply manual asks for it.
Pitfalls
- Zone 1 set to 100 %. Any measurement error then makes it overreach and trip for faults on the next line.
- Forgetting infeed. Zone 2 and 3 underreach when another source feeds the fault beyond the relay; check the reach at minimum infeed (for overreach) and maximum infeed (for coverage).
- Load encroachment and power swings. Heavy load or a swinging generator can move into zone 3; use blinders and power-swing blocking (Swing Equation).
- Loss of VT voltage. A blown VT fuse makes , which looks like a fault at the relay: relays supervise the VT and block.
Practice
- Convert a zone 1 setting of primary for a CT of 800/1 and the same VT.
- A line has and . Find .
- Why is a mho characteristic directional, and why might a quadrilateral be preferred on a short line?
Answer
- secondary.
- .
- The circle passes through the origin and lies on the line side, so reverse faults (negative impedance direction) fall outside. A short line has a small , so a mho circle sized for it has a tiny resistive reach and would miss earth faults with a few ohms of resistance; a quadrilateral sets the resistive reach independently.
Test yourself
Zone 1 of a distance relay is usually set to…
- 50 %
- 80–85 %
- 100 %
- 120 %
Why does a distance relay need residual compensation for earth faults?
- to correct for CT saturation
- because the earth-return path has a different impedance per km than the phase conductor
- to block power swings
- to measure the frequency
Current from the remote end flows into a resistive fault. The relay at the local end sees…
- less fault resistance than is really there
- more resistance than , so it tends to underreach
- exactly
- no change
A 0.35 s zone 2 time delay exists mainly to…
- let the downstream line's zone 1 and breaker clear faults beyond the remote bus first
- wait for the DC offset
- allow auto-reclosing
- charge the CT