Home › Power Systems: Three-Phase, Generation, Grids & Protection › Distance Protection and Its Zones

Distance Protection and Its Zones

Overcurrent relays struggle on meshed transmission networks: the fault current depends on which generators are running and which lines are in service, and it flows in from both ends. What does not change is the impedance of the line up to the fault. A distance relay divides the voltage at its location by the current and compares the result with the line impedance. A fault at 60 %60\ \% of the line looks like 0.6 ZL0.6\,Z_L, whatever the source strength. This lesson builds the stepped zones that make distance protection selective, and shows the effects that blur the measurement: fault resistance, infeed from the far end, load, and earth return.

Safety: transmission voltages are studied here by calculation and simulation only. Relay testing on real lines uses secondary-injection sets and is done by qualified protection engineers under permit.

What the relay measures

For a solid three-phase fault at a fraction mm of a line with series impedance ZLZ_L, the relay voltage is VR=mZLIR\mathbf{V}_R = m Z_L \mathbf{I}_R, so

Zapp=VRIR=m ZLZ_\text{app} = \frac{\mathbf{V}_R}{\mathbf{I}_R} = m\,Z_L

A real relay has six measuring loops: three phase-to-phase loops (Vab/Iab\mathbf{V}_{ab}/\mathbf{I}_{ab} and so on) and three phase-to-earth loops. For an earth fault the return current flows partly in the ground, whose impedance per km is different, so the phase-to-earth loop uses residual compensation:

Zapp=VaIa+k0 3I0,k0=Z0−Z13Z1Z_\text{app} = \frac{\mathbf{V}_a}{\mathbf{I}_a + k_0\, 3\mathbf{I}_0}, \qquad k_0 = \frac{Z_0 - Z_1}{3 Z_1}

with Z1Z_1 and Z0Z_0 the positive- and zero-sequence line impedances (Sequence Networks). With this correction, every loop measures the positive-sequence impedance to the fault.

The relay's characteristic is a region on the R–X plane; it trips when ZappZ_\text{app} falls inside. A mho circle passes through the origin, which makes it inherently directional. A quadrilateral has independent reactance and resistance reaches, which is useful for fault resistance on short lines.

Stepped zones

The relay cannot tell a fault at 99 %99\ \% of its line from one at 101 %101\ \% (just past the remote busbar): CT and VT errors, line-impedance data and relay tolerance together are worth 1010 to 20 %20\ \%. So it uses several zones:

Zone Typical reach Delay Purpose
Zone 1 8080 to 85 %85\ \% of the protected line instantaneous fast clearance of most of the line, never overreaching the remote bus
Zone 2 about 120 %120\ \% of the line (at least the whole line, at most half of the shortest next line) 0.30.3 to 0.4 s0.4\ \text{s} the last 1515 to 20 %20\ \%, and backup for the remote busbar
Zone 3 protected line plus 120 %120\ \% of the longest next line (load permitting) 0.80.8 to 1.5 s1.5\ \text{s} remote backup for the next lines
reverse zone behind the relay used in schemes blocking and weak-infeed logic
tdistance from A AB (100 km)C (160 km) Z1 80 %, instantaneous Z2 120 %, 0.35 s Z3 to 172 km, 1.0 s 0.351.0 R

Zone 1 at both ends overlaps in the middle 6060 to 70 %70\ \% of the line, where both ends trip instantly. For the end zones, a communication channel (fibre or power-line carrier) lets each end accelerate the other: in a permissive overreach (POTT) scheme an end trips instantly when its own overreaching zone 2 sees the fault and the other end sends a permissive signal. Transmission lines also use line differential protection over fibre (Differential Protection).

Worked example: settings for a 132 kV line

Given: line A–B, 100 km100\ \text{km}, z1=0.08+j0.40 Ω/kmz_1 = 0.08 + j0.40\ \Omega/\text{km}, z0=0.25+j1.20 Ω/kmz_0 = 0.25 + j1.20\ \Omega/\text{km}. Next line B–C, 60 km60\ \text{km}, same conductor. CT 600/1, VT 132 kV/110 V132\ \text{kV}/110\ \text{V}. Maximum load 100 MW100\ \text{MW} at pf 0.950.95.

Find: the zone reaches in primary and secondary ohms, k0k_0, and the load impedance.

Solve:

ZL=100⋅(0.08+j0.40)=8+j40 Ω=40.79 Ω ∠78.7∘Z1=0.8⋅40.79=32.63 Ω,Z2=1.2⋅40.79=48.95 Ω,Z3=(100+1.2⋅60)⋅0.408=70.16 ΩZsecZprim=600/1132 000/110=0.5:16.32, 24.48, 35.08 Ω secondaryk0=(0.25+j1.20)−(0.08+j0.40)3 (0.08+j0.40)=0.668 ∠−0.7∘Zload=V2S=(132 kV)2100 MW/0.95=165.5 Ω ∠18.2∘\begin{aligned} Z_L &= 100 \cdot (0.08 + j0.40) = 8 + j40\ \Omega = 40.79\ \Omega\ \angle 78.7^\circ \\ Z_1 &= 0.8 \cdot 40.79 = 32.63\ \Omega, \quad Z_2 = 1.2 \cdot 40.79 = 48.95\ \Omega, \quad Z_3 = (100 + 1.2 \cdot 60) \cdot 0.408 = 70.16\ \Omega \\ \frac{Z_\text{sec}}{Z_\text{prim}} &= \frac{600/1}{132\,000/110} = 0.5: \quad 16.32,\ 24.48,\ 35.08\ \Omega\ \text{secondary} \\ k_0 &= \frac{(0.25 + j1.20) - (0.08 + j0.40)}{3\,(0.08 + j0.40)} = 0.668\ \angle -0.7^\circ \\ Z_\text{load} &= \frac{V^2}{S} = \frac{(132\ \text{kV})^2}{100\ \text{MW}/0.95} = 165.5\ \Omega\ \angle 18.2^\circ \end{aligned}

Check: zone 3 (70 Ω70\ \Omega at 78.7∘78.7^\circ) is well clear of the load point (165.5 Ω165.5\ \Omega at 18.2∘18.2^\circ): a mho circle of diameter 70 Ω70\ \Omega along 78.7∘78.7^\circ reaches only 70cos⁡(78.7∘−18.2∘)=34.6 Ω70 \cos(78.7^\circ - 18.2^\circ) = 34.6\ \Omega in the load direction. On long, heavily loaded lines this margin vanishes, which is how zone 3 tripped on load during several large blackouts; modern relays add load-encroachment blinders.

In Python: fault resistance and infeed

A fault through resistance RFR_F at the line midpoint, fed from both ends: source A behind j5 Ωj5\ \Omega, source B behind j8 Ωj8\ \Omega with its EMF 10∘10^\circ behind A (power flows from A to B).

python · try it yourself
import numpy as np
import matplotlib.pyplot as plt

ZL = 100 * complex(0.08, 0.40)
VA = 132e3 / np.sqrt(3); VB = VA * np.exp(-1j * np.radians(10))
ZA, ZB = 5j, 8j

def apparent(m, RF):
    # nodal equations for nodes r (relay bus A), f (fault), b (bus B)
    Y = np.zeros((3, 3), complex)
    def branch(i, j, z):
        y = 1 / z
        for k in (i, j):
            if k is not None: Y[k, k] += y
        if i is not None and j is not None: Y[i, j] -= y; Y[j, i] -= y
    branch(0, None, ZA); branch(0, 1, m * ZL); branch(1, 2, (1 - m) * ZL)
    branch(2, None, ZB); branch(1, None, RF)
    V = np.linalg.solve(Y, np.array([VA / ZA, 0, VB / ZB]))
    Ir = (V[0] - V[1]) / (m * ZL)
    return V[0] / Ir

print("RF (Ohm)   Z seen at A (Ohm)        |Z|   inside zone 1 mho?")
D = 0.8 * ZL                                     # mho circle: diameter 0.8 ZL from the origin
for RF in [0.1, 5, 10, 20]:
    Z = apparent(0.5, RF)
    inside = abs(Z - D / 2) <= abs(D) / 2
    print(f"{RF:6.1f}   {Z.real:7.2f} + j{Z.imag:6.2f}   {abs(Z):6.2f}   {inside}")

th = np.linspace(0, 2 * np.pi, 200)
fig, ax = plt.subplots(figsize=(6.4, 3.6))
for k, lab in [(0.8, "Z1"), (1.2, "Z2"), (1.72, "Z3")]:
    c = k * ZL / 2 if k < 1.5 else 172 * complex(0.08, 0.40) / 2
    ax.plot((c + abs(c) * np.exp(1j * th)).real, (c + abs(c) * np.exp(1j * th)).imag, label=lab)
ax.plot([0, ZL.real], [0, ZL.imag], "k", lw=2, label="line A-B")
pts = [apparent(0.5, RF) for RF in np.linspace(0.1, 20, 20)]
ax.plot([p.real for p in pts], [p.imag for p in pts], "r.", label="midpoint fault, RF 0-20")
Zl = 165.5 * np.exp(1j * np.radians(18.2)); ax.plot(Zl.real, Zl.imag, "ks", label="max load")
ax.set_xlabel("R (Ohm, primary)"); ax.set_ylabel("X (Ohm)"); ax.set_aspect("equal")
ax.set_xlim(-40, 170); ax.set_ylim(-20, 80); ax.grid(alpha=0.3); ax.legend(fontsize=7)
fig.tight_layout()
plt.show()
RF (Ohm)   Z seen at A (Ohm)        |Z|   inside zone 1 mho?
   0.1      4.19 + j 19.98    20.42   True
   5.0     13.11 + j 19.16    23.22   True
  10.0     21.69 + j 18.34    28.41   False
  20.0     37.44 + j 16.77    41.02   False

The fault is at 20.4 Ω20.4\ \Omega (half of ZLZ_L) when bolted. With 10 Ω10\ \Omega of fault resistance the relay sees about 17.7 Ω17.7\ \Omega of extra resistance, not 1010: current from B flows through RFR_F too, so the voltage across it is larger than RFR_F times A's current alone. The point also drops slightly in X because B's current is not in phase with A's. The fault leaves the zone 1 mho circle, which is why quadrilateral characteristics with a generous resistive reach are used for earth faults.

Interactive: the two-ended fault

The same circuit as a netlist: sources 76.21 kV76.21\ \text{kV} (phase), A behind 15.92 mH15.92\ \text{mH} (5 Ω5\ \Omega), B behind 25.46 mH25.46\ \text{mH} (8 Ω8\ \Omega) at −10∘-10^\circ, two half-lines of 4 Ω4\ \Omega and 63.66 mH63.66\ \text{mH}, and the fault resistor RF at the midpoint. Read V(r) and I(R1) at the 50 Hz50\ \text{Hz} cursor (the lab also sweeps frequency) and divide them: at RF=10 ΩR_F = 10\ \Omega the lab shows about 67.9 kV67.9\ \text{kV} and 2.39 kA2.39\ \text{kA}, a 28.4 Ω28.4\ \Omega apparent impedance as in the table. Lower RF and watch the current rise and the angle between them approach the line angle.

050000100m1101001k10kf (Hz)|V| (V)|V(r)||V(f)||V(b)|phasors at f = 50.00 Hz (magnitude @ phase)V(sa)76.2 kV @ 0.0 degV(r)67.9 kV @ -6.9 degV(x)60.9 kV @ -1.1 degV(f)42.5 kV @ -52.5 degV(y)50.0 kV @ -53.5 degV(b)65.5 kV @ -18.6 degV(sb)76.2 kV @ -10.0 degI(V1)2.39 kA @ 132.9 degI(LA)2.39 kA @ -47.1 degI(R1)2.39 kA @ -47.1 degI(L1)2.39 kA @ -47.1 degI(R2)1.88 kA @ 120.7 degI(L2)1.88 kA @ 120.7 degI(LB)1.88 kA @ 120.7 degI(V2)1.88 kA @ 120.7 degI(RF)4.25 kA @ -52.5 deg

Guided lab: apparent impedance on a resistor model

Hand calculation. Build a DC analogue of the two-ended line on paper: a 12 V12\ \text{V} source A behind 10 Ω10\ \Omega, two 47 Ω47\ \Omega "half-line" resistors, a 10 V10\ \text{V} source B behind 22 Ω22\ \Omega, and a fault resistor RFR_F from the midpoint to ground. Predict the ratio Vr/IrV_r/I_r at A for RF=10 ΩR_F = 10\ \Omega and RF=100 ΩR_F = 100\ \Omega, and the ratio with source B disconnected.

Simulation. Enter the same network in the netlist lab with analysis set to DC (or in NumPy), and compare.

What you would measure. Two current-limited bench supplies (both outputs floating, negatives joined as "ground"), 0.6 W0.6\ \text{W} resistors, DMMs for VrV_r and IrI_r. Use 2 W2\ \text{W} resistors at least: at RF=10 ΩR_F = 10\ \Omega the A-side 47 Ω47\ \Omega carries 163 mA163\ \text{mA} (1.25 W1.25\ \text{W}), and 179 mA179\ \text{mA} (1.5 W1.5\ \text{W}) with B disconnected. Expect the apparent "impedance" to grow above 47 Ω+RF47\ \Omega + R_F when B feeds in, just as in the AC case (about 63.5 Ω63.5\ \Omega instead of 57 Ω57\ \Omega at RF=10 ΩR_F = 10\ \Omega, 183 Ω183\ \Omega instead of 147 Ω147\ \Omega at 100 Ω100\ \Omega), within the ±1 %\pm 1\ \% resistor tolerance and DMM uncertainty (about ±2 %\pm 2\ \% on the ratio).

Hazards and safe setup. Both supplies ≤12 V\le 12\ \text{V} with current limits of 300 mA300\ \text{mA}; check resistor power (V2/RV^2/R) before switching on; a supply driven backwards by the other one can be damaged, so add a series diode if your supply manual asks for it.

Pitfalls

  • Zone 1 set to 100 %. Any measurement error then makes it overreach and trip for faults on the next line.
  • Forgetting infeed. Zone 2 and 3 underreach when another source feeds the fault beyond the relay; check the reach at minimum infeed (for overreach) and maximum infeed (for coverage).
  • Load encroachment and power swings. Heavy load or a swinging generator can move ZappZ_\text{app} into zone 3; use blinders and power-swing blocking (Swing Equation).
  • Loss of VT voltage. A blown VT fuse makes V=0V = 0, which looks like a fault at the relay: relays supervise the VT and block.

Practice

  1. Convert a zone 1 setting of 32.6 Ω32.6\ \Omega primary for a CT of 800/1 and the same VT.
  2. A line has z1=0.03+j0.32 Ω/kmz_1 = 0.03 + j0.32\ \Omega/\text{km} and z0=0.20+j1.05 Ω/kmz_0 = 0.20 + j1.05\ \Omega/\text{km}. Find k0k_0.
  3. Why is a mho characteristic directional, and why might a quadrilateral be preferred on a short line?
Answer
  1. 32.6⋅(800/1200)=21.7 Ω32.6 \cdot (800/1200) = 21.7\ \Omega secondary.
  2. k0=(0.17+j0.73)/(3(0.03+j0.32))=0.777 ∠−7.8∘k_0 = (0.17 + j0.73)/(3(0.03 + j0.32)) = 0.777\ \angle -7.8^\circ.
  3. The circle passes through the origin and lies on the line side, so reverse faults (negative impedance direction) fall outside. A short line has a small ZLZ_L, so a mho circle sized for it has a tiny resistive reach and would miss earth faults with a few ohms of resistance; a quadrilateral sets the resistive reach independently.

Test yourself

Zone 1 of a distance relay is usually set to…

  1. 50 %
  2. 80–85 %
  3. 100 %
  4. 120 %

Why does a distance relay need residual compensation k0k_0 for earth faults?

  1. to correct for CT saturation
  2. because the earth-return path has a different impedance per km than the phase conductor
  3. to block power swings
  4. to measure the frequency

Current from the remote end flows into a resistive fault. The relay at the local end sees…

  1. less fault resistance than is really there
  2. more resistance than RFR_F, so it tends to underreach
  3. exactly RFR_F
  4. no change

A 0.35 s zone 2 time delay exists mainly to…

  1. let the downstream line's zone 1 and breaker clear faults beyond the remote bus first
  2. wait for the DC offset
  3. allow auto-reclosing
  4. charge the CT