Home › Power Systems: Three-Phase, Generation, Grids & Protection › Voltage Control: Tap Changers, Shunt Compensation, SVC and STATCOM

Voltage Control: Tap Changers, Shunt Compensation, SVC and STATCOM

Grid codes and supply standards hold voltages in narrow bands: typically ±10 %\pm 10\ \% at the customer's terminals (EN 50160 for public low-voltage supplies), and about 0.950.95 to 1.05 pu1.05\ \text{pu} on transmission buses. Loads change all day, so the voltage would wander far outside these bands if nothing acted. The previous lesson showed that voltage on an inductive network follows reactive power. This lesson covers the tools operators use to move it: generator excitation, transformer tap changers, switched capacitors and reactors, and the power-electronic compensators SVC and STATCOM.

Safety. Tap changers, capacitor banks and compensators sit in substations at 11 kV11\ \text{kV} and above. A capacitor bank stays charged after it is switched off (banks have discharge resistors, and staff still earth them before touching). Everything here is calculation and simulation only.

The toolbox

Device How it acts Speed Notes
generator AVR raises or lowers the field current, so the generator supplies or absorbs QQ fast (below a second) limited by the capability chart (V-Curves and the Infinite Bus)
on-load tap changer (OLTC) changes the transformer ratio in steps, typically ±10 %\pm 10\ \% in steps of 1.25 %1.25\ \% or 0.625 %0.625\ \% tens of seconds (a deliberate time delay) moves voltage, does not create QQ: it shifts it between the two sides
shunt capacitor bank injects Q=BV2Q = BV^2 switched in seconds to minutes cheap; output falls with the square of voltage
shunt reactor absorbs Q=V2/XQ = V^2/X switched holds voltage down on lightly loaded long lines and cables
SVC (static var compensator) thyristor-controlled reactor plus capacitors: a continuously variable susceptance about one cycle at its limit it is a fixed capacitor, Q∝V2Q \propto V^2
STATCOM voltage-source converter that injects a controlled reactive current under a cycle at its limit it is a current source, Q∝VQ \propto V; small footprint
synchronous condenser an unloaded synchronous machine fast also adds inertia and fault current

Shunt compensation and the fault level

Seen from a bus, the network is a Thevenin source E\mathbf{E} behind an impedance ZthZ_\text{th}, almost a pure reactance XthX_\text{th}. Its size is given by the three-phase short-circuit level of the bus, Ssc=1/xthS_\text{sc} = 1/x_\text{th} in per unit (MVA divided by the base). Changing the reactive injection at the bus by ΔQ\Delta Q changes the voltage by roughly

ΔVV≈ΔQSsc\frac{\Delta V}{V} \approx \frac{\Delta Q}{S_\text{sc}}

A 10 Mvar10\ \text{Mvar} capacitor on a bus with a 500 MVA500\ \text{MVA} fault level raises the voltage by about 2 %2\ \%. Strong buses (high fault level) are stiff; weak buses swing a lot with every switching, which is also why switching a big bank on a weak bus produces a visible voltage step.

Why device type matters at low voltage. When the voltage is already low (after a fault, during a heavy load), you want the most support. A capacitor bank or an SVC at its limit gives Q=BmaxV2Q = B_\text{max}V^2: at 0.8 pu0.8\ \text{pu} only 64 %64\ \% of its rating. A STATCOM at its current limit gives Q=ImaxVQ = I_\text{max}V: 80 %80\ \%. That difference is one reason STATCOMs are chosen for voltage-stability support (Voltage Stability). The converters themselves are covered in Power Electronics & Motor Drives.

Tap changers

132 kV33 kV bus 132/33 kV, OLTC +-10 % VT AVC relaysetpoint, deadband, delay raise / lower

An automatic voltage control (AVC) relay compares the secondary busbar voltage with a setpoint. If the error stays outside a deadband (a little more than half a tap step, so one step cannot overshoot into the opposite band) for longer than a time delay (often 3030 to 120 s120\ \text{s}), it steps the tap. The delay stops the tap changer from chasing short dips, saves wear on its contacts, and lets faster devices act first. Optional line-drop compensation raises the setpoint in proportion to load current, so the voltage is regulated at a remote point down the feeder rather than at the substation.

A tap changer does not produce reactive power. Raising the secondary voltage makes the loads draw more current and more QQ, which the primary side must supply. If the primary network is weak, taps raising the secondary can pull the primary voltage down further: that mechanism is part of many voltage collapses.

Worked example: sizing a capacitor bank

Given: a 33 kV33\ \text{kV} bus whose Thevenin equivalent is E=1.02 puE = 1.02\ \text{pu} behind xth=0.25 pux_\text{th} = 0.25\ \text{pu} on 100 MVA100\ \text{MVA} (a fault level of 400 MVA400\ \text{MVA}), with a constant-power load of 0.6+j0.3 pu0.6 + j0.3\ \text{pu} (60 MW60\ \text{MW}, 30 Mvar30\ \text{Mvar}).

Find: the bus voltage, the capacitor bank (rated at 1.0 pu1.0\ \text{pu} voltage) that brings it to 1.00 pu1.00\ \text{pu}, and compare with the fault-level estimate.

Solve: solve V=E−jxth (S/V)∗\mathbf{V} = \mathbf{E} - jx_\text{th}\,(S/\mathbf{V})^* iteratively (the program below). Without compensation V=0.926 puV = 0.926\ \text{pu} at −9.14∘-9.14^\circ. Adding a susceptance BB that injects BV2BV^2 and solving for V=1.00V = 1.00 gives B=0.264 puB = 0.264\ \text{pu}: a 26.4 Mvar26.4\ \text{Mvar} bank.

Check: the estimate ΔQ≈ΔV⋅Ssc=0.074⋅4.0=0.296 pu\Delta Q \approx \Delta V \cdot S_\text{sc} = 0.074 \cdot 4.0 = 0.296\ \text{pu} is 12 %12\ \% high, good enough for a first sizing. The bank would be built in steps (for example 3×9 Mvar3 \times 9\ \text{Mvar}) so that light-load hours don't push the voltage too high. In amperes, 26.4 Mvar26.4\ \text{Mvar} at 33 kV33\ \text{kV} is 26.4×106/(3⋅33 000)=462 A26.4 \times 10^6/(\sqrt{3} \cdot 33\,000) = 462\ \text{A} of capacitive current.

In Python: capacitor, SVC and STATCOM, and a tap changer

python · try it yourself
import numpy as np

E, x = 1.02, 0.25            # Thevenin source and reactance, pu (fault level 400 MVA on 100 MVA)
P, Q = 0.6, 0.3              # constant-power load, pu

def bus_voltage(q_inj):
    """q_inj(V) = reactive power injected by the device at voltage V. Fixed-point solution."""
    V = 1.0 + 0j
    for _ in range(200):
        S = P + 1j * (Q - q_inj(abs(V)))
        V = E - 1j * x * np.conj(S / V)
    return V

V0 = bus_voltage(lambda v: 0.0)
print(f"no compensation: V = {abs(V0):.4f} pu at {np.degrees(np.angle(V0)):.2f} deg")

# bisection for the capacitor that gives exactly 1.00 pu
lo, hi = 0.0, 1.0
for _ in range(50):
    B = (lo + hi) / 2
    lo, hi = (B, hi) if abs(bus_voltage(lambda v: B * v**2)) < 1.0 else (lo, B)
print(f"capacitor for 1.00 pu: B = {B:.4f} pu = {B*100:.1f} Mvar at 1 pu; estimate {(1-abs(V0))*(1/x)*100:.1f} Mvar")

# a 0.2 pu device of each kind, at depressed voltages
for V in [1.0, 0.9, 0.8, 0.7]:
    print(f"V = {V:.1f} pu: capacitor/SVC at limit {0.2*V*V:.3f} pu, STATCOM at limit {0.2*V:.3f} pu")

# OLTC: 132/33 kV transformer, x = 0.1 pu, taps +-8 x 1.25 % on the HV side, load 0.6 + j0.3 at 33 kV
Vp = 0.97                                # primary voltage, pu
for tap in [0, -2, -4]:                  # negative tap = fewer HV turns = higher LV voltage
    t = 1 + 0.0125 * tap                 # off-nominal ratio
    V = 1.0 + 0j
    for _ in range(200):
        V = Vp / t - 1j * 0.1 * np.conj((P + 1j * Q) / V)
    print(f"tap {tap:+d} (ratio {t:.4f}): LV bus {abs(V):.4f} pu")
no compensation: V = 0.9261 pu at -9.14 deg
capacitor for 1.00 pu: B = 0.2644 pu = 26.4 Mvar at 1 pu; estimate 29.6 Mvar
V = 1.0 pu: capacitor/SVC at limit 0.200 pu, STATCOM at limit 0.200 pu
V = 0.9 pu: capacitor/SVC at limit 0.162 pu, STATCOM at limit 0.180 pu
V = 0.8 pu: capacitor/SVC at limit 0.128 pu, STATCOM at limit 0.160 pu
V = 0.7 pu: capacitor/SVC at limit 0.098 pu, STATCOM at limit 0.140 pu
tap +0 (ratio 1.0000): LV bus 0.9358 pu
tap -2 (ratio 0.9750): LV bus 0.9617 pu
tap -4 (ratio 0.9500): LV bus 0.9889 pu

The last three lines show the tap changer on a 132/33 kV132/33\ \text{kV} transformer (x=0.1 pux = 0.1\ \text{pu}) whose primary sits at 0.97 pu0.97\ \text{pu}: each 1.25 %1.25\ \% step lifts the 33 kV33\ \text{kV} bus by a little more than 1.25 %1.25\ \% (0.9360.936, 0.9620.962, 0.989 pu0.989\ \text{pu}), because the load current also falls slightly as the voltage rises. The primary network has to supply the extra reactive power.

Interactive: switch in the capacitor

The netlist lab is the same bus in per unit at 50 Hz50\ \text{Hz}: source V1 of 1.021.02, the Thevenin reactance as L=0.25/(2π⋅50)=795.8 μHL = 0.25/(2\pi \cdot 50) = 795.8\ \mu\text{H}, and the load as a constant impedance (1.667 Ω1.667\ \Omega in parallel with 10.61 mH10.61\ \text{mH}, which is 0.6+j0.3 pu0.6 + j0.3\ \text{pu} at 1 pu1\ \text{pu}). The capacitor CB has B=ωCB = \omega C (so 636.6 μF636.6\ \mu\text{F} is 0.2 pu0.2\ \text{pu}). The lab sweeps frequency; read only the 50 Hz50\ \text{Hz} values. With the smallest capacitor the bus reads 0.940 pu0.940\ \text{pu}, higher than the 0.9260.926 above because an impedance load draws less power when the voltage sags. At 636.6 μF636.6\ \mu\text{F} it reads 0.985 pu0.985\ \text{pu}, at 841.5 μF841.5\ \mu\text{F} (B=0.264 puB = 0.264\ \text{pu}) 1.000 pu1.000\ \text{pu} (at exactly 1 pu1\ \text{pu} both load models draw the same power), and at the top of the slider 1.053 pu1.053\ \text{pu}: overcompensated.

0.00.51.0100m1101001k10kf (Hz)|V| (V)|V(b)|phasors at f = 50.00 Hz (magnitude @ phase)V(s)1.02 V @ 0.0 degV(b)940 mV @ -7.9 degI(V1)629 mA @ 145.7 degI(LT)629 mA @ -34.3 degI(RL)564 mA @ -7.9 degI(LL)282 mA @ -97.9 degI(CB)2.95 mA @ 82.1 deg

Guided lab: a capacitor on a weak signal-level bus

Hand calculation. Scale to the bench with Zb=100 ΩZ_b = 100\ \Omega at 1 V1\ \text{V}: the Thevenin reactance becomes 25 Ω25\ \Omega (80 mH80\ \text{mH} at 50 Hz50\ \text{Hz}, or 8 mH8\ \text{mH} at 500 Hz500\ \text{Hz} to keep parts small), the load 167 Ω167\ \Omega in parallel with 333 Ω333\ \Omega of inductive reactance, and a 0.264 pu0.264\ \text{pu} capacitor is B=2.64 mSB = 2.64\ \text{mS}. Predict the voltages above for E=1.02 VE = 1.02\ \text{V}.

Simulation. Enter your measured component values in the netlist (keep the frequency you actually use) and note the predicted voltages with and without the capacitor.

What you would measure. With a function generator as the source and a true-rms DMM on the "bus", expect about 0.94 V0.94\ \text{V} without and 1.00 V1.00\ \text{V} with the capacitor, each within about ±3 %\pm 3\ \%, dominated by inductor tolerance and the inductor's own resistance (which also adds an in-phase drop the per-unit model ignores). Use film capacitors; electrolytics are polarised and unsuitable for AC.

Hazards and safe setup. Signal levels only (≤2 V\le 2\ \text{V} rms, a few tens of milliamperes). No mains-powered capacitor banks or power-factor capacitors from equipment: those store dangerous energy.

Pitfalls

  • Expecting a tap changer to create reactive power. It only redistributes voltage; the QQ still comes from somewhere upstream.
  • Rating a capacitor at nominal voltage and forgetting V2V^2. A bank rated 10 Mvar10\ \text{Mvar} at 33 kV33\ \text{kV} gives 8.1 Mvar8.1\ \text{Mvar} at 0.9 pu0.9\ \text{pu}.
  • Overcompensation. At light load, fixed capacitors push voltages high; banks are switched in steps, and reactors are switched in at night on cable-heavy networks.
  • Harmonic resonance. A capacitor bank and the network inductance resonate at f0≈f1Ssc/Qcf_0 \approx f_1\sqrt{S_\text{sc}/Q_c}; with Ssc=400 MVAS_\text{sc} = 400\ \text{MVA} and Qc=25 MvarQ_c = 25\ \text{Mvar} that is the 4th harmonic, close to the 5th that rectifiers produce. Detuning reactors fix it (Power Quality).

Practice

  1. A bus has a fault level of 1200 MVA1200\ \text{MVA}. Roughly how much does switching a 30 Mvar30\ \text{Mvar} reactor change its voltage?
  2. A 50 Mvar50\ \text{Mvar} SVC and a 50 Mvar50\ \text{Mvar} STATCOM are both at their limits with the bus at 0.85 pu0.85\ \text{pu}. How much does each deliver?
  3. The OLTC above has taps of 1.25 %1.25\ \%. Which deadband would you choose, and why not 0.5 %0.5\ \%?
Answer
  1. ΔV/V≈30/1200=2.5 %\Delta V/V \approx 30/1200 = 2.5\ \%, downward (a reactor absorbs QQ).
  2. SVC: 50⋅0.852=36.1 Mvar50 \cdot 0.85^2 = 36.1\ \text{Mvar}; STATCOM: 50⋅0.85=42.5 Mvar50 \cdot 0.85 = 42.5\ \text{Mvar}.
  3. A total band a little wider than one step, e.g. ±0.8 %\pm 0.8\ \% (1.6 %1.6\ \% wide). With ±0.5 %\pm 0.5\ \% one step of 1.25 %1.25\ \% would jump from below the band to above it and the relay would hunt up and down.

Test yourself

A capacitor bank delivers 20 Mvar at 1.0 pu voltage. What does it deliver at 0.9 pu?

  1. 20 Mvar
  2. 18 Mvar
  3. 16.2 Mvar
  4. 22.2 Mvar

Which device keeps the most reactive output when the voltage is depressed?

  1. fixed capacitor
  2. SVC at its limit
  3. STATCOM at its current limit
  4. all the same

A 10 Mvar capacitor is switched on at a bus with a 500 MVA fault level. The voltage rises by about…

  1. 0.2 %
  2. 2 %
  3. 5 %
  4. 20 %

Why does a tap-changer controller wait tens of seconds before stepping?

  1. the motor must warm up
  2. to ignore short dips, reduce contact wear and let faster controls act first
  3. IEC forbids faster operation
  4. to keep the frequency constant