Voltage Control: Tap Changers, Shunt Compensation, SVC and STATCOM
Grid codes and supply standards hold voltages in narrow bands: typically at the customer's terminals (EN 50160 for public low-voltage supplies), and about to on transmission buses. Loads change all day, so the voltage would wander far outside these bands if nothing acted. The previous lesson showed that voltage on an inductive network follows reactive power. This lesson covers the tools operators use to move it: generator excitation, transformer tap changers, switched capacitors and reactors, and the power-electronic compensators SVC and STATCOM.
Safety. Tap changers, capacitor banks and compensators sit in substations at and above. A capacitor bank stays charged after it is switched off (banks have discharge resistors, and staff still earth them before touching). Everything here is calculation and simulation only.
The toolbox
| Device | How it acts | Speed | Notes |
|---|---|---|---|
| generator AVR | raises or lowers the field current, so the generator supplies or absorbs | fast (below a second) | limited by the capability chart (V-Curves and the Infinite Bus) |
| on-load tap changer (OLTC) | changes the transformer ratio in steps, typically in steps of or | tens of seconds (a deliberate time delay) | moves voltage, does not create : it shifts it between the two sides |
| shunt capacitor bank | injects | switched in seconds to minutes | cheap; output falls with the square of voltage |
| shunt reactor | absorbs | switched | holds voltage down on lightly loaded long lines and cables |
| SVC (static var compensator) | thyristor-controlled reactor plus capacitors: a continuously variable susceptance | about one cycle | at its limit it is a fixed capacitor, |
| STATCOM | voltage-source converter that injects a controlled reactive current | under a cycle | at its limit it is a current source, ; small footprint |
| synchronous condenser | an unloaded synchronous machine | fast | also adds inertia and fault current |
Shunt compensation and the fault level
Seen from a bus, the network is a Thevenin source behind an impedance , almost a pure reactance . Its size is given by the three-phase short-circuit level of the bus, in per unit (MVA divided by the base). Changing the reactive injection at the bus by changes the voltage by roughly
A capacitor on a bus with a fault level raises the voltage by about . Strong buses (high fault level) are stiff; weak buses swing a lot with every switching, which is also why switching a big bank on a weak bus produces a visible voltage step.
Why device type matters at low voltage. When the voltage is already low (after a fault, during a heavy load), you want the most support. A capacitor bank or an SVC at its limit gives : at only of its rating. A STATCOM at its current limit gives : . That difference is one reason STATCOMs are chosen for voltage-stability support (Voltage Stability). The converters themselves are covered in Power Electronics & Motor Drives.
Tap changers
An automatic voltage control (AVC) relay compares the secondary busbar voltage with a setpoint. If the error stays outside a deadband (a little more than half a tap step, so one step cannot overshoot into the opposite band) for longer than a time delay (often to ), it steps the tap. The delay stops the tap changer from chasing short dips, saves wear on its contacts, and lets faster devices act first. Optional line-drop compensation raises the setpoint in proportion to load current, so the voltage is regulated at a remote point down the feeder rather than at the substation.
A tap changer does not produce reactive power. Raising the secondary voltage makes the loads draw more current and more , which the primary side must supply. If the primary network is weak, taps raising the secondary can pull the primary voltage down further: that mechanism is part of many voltage collapses.
Worked example: sizing a capacitor bank
Given: a bus whose Thevenin equivalent is behind on (a fault level of ), with a constant-power load of (, ).
Find: the bus voltage, the capacitor bank (rated at voltage) that brings it to , and compare with the fault-level estimate.
Solve: solve iteratively (the program below). Without compensation at . Adding a susceptance that injects and solving for gives : a bank.
Check: the estimate is high, good enough for a first sizing. The bank would be built in steps (for example ) so that light-load hours don't push the voltage too high. In amperes, at is of capacitive current.
In Python: capacitor, SVC and STATCOM, and a tap changer
import numpy as np
E, x = 1.02, 0.25 # Thevenin source and reactance, pu (fault level 400 MVA on 100 MVA)
P, Q = 0.6, 0.3 # constant-power load, pu
def bus_voltage(q_inj):
"""q_inj(V) = reactive power injected by the device at voltage V. Fixed-point solution."""
V = 1.0 + 0j
for _ in range(200):
S = P + 1j * (Q - q_inj(abs(V)))
V = E - 1j * x * np.conj(S / V)
return V
V0 = bus_voltage(lambda v: 0.0)
print(f"no compensation: V = {abs(V0):.4f} pu at {np.degrees(np.angle(V0)):.2f} deg")
# bisection for the capacitor that gives exactly 1.00 pu
lo, hi = 0.0, 1.0
for _ in range(50):
B = (lo + hi) / 2
lo, hi = (B, hi) if abs(bus_voltage(lambda v: B * v**2)) < 1.0 else (lo, B)
print(f"capacitor for 1.00 pu: B = {B:.4f} pu = {B*100:.1f} Mvar at 1 pu; estimate {(1-abs(V0))*(1/x)*100:.1f} Mvar")
# a 0.2 pu device of each kind, at depressed voltages
for V in [1.0, 0.9, 0.8, 0.7]:
print(f"V = {V:.1f} pu: capacitor/SVC at limit {0.2*V*V:.3f} pu, STATCOM at limit {0.2*V:.3f} pu")
# OLTC: 132/33 kV transformer, x = 0.1 pu, taps +-8 x 1.25 % on the HV side, load 0.6 + j0.3 at 33 kV
Vp = 0.97 # primary voltage, pu
for tap in [0, -2, -4]: # negative tap = fewer HV turns = higher LV voltage
t = 1 + 0.0125 * tap # off-nominal ratio
V = 1.0 + 0j
for _ in range(200):
V = Vp / t - 1j * 0.1 * np.conj((P + 1j * Q) / V)
print(f"tap {tap:+d} (ratio {t:.4f}): LV bus {abs(V):.4f} pu")no compensation: V = 0.9261 pu at -9.14 deg
capacitor for 1.00 pu: B = 0.2644 pu = 26.4 Mvar at 1 pu; estimate 29.6 Mvar
V = 1.0 pu: capacitor/SVC at limit 0.200 pu, STATCOM at limit 0.200 pu
V = 0.9 pu: capacitor/SVC at limit 0.162 pu, STATCOM at limit 0.180 pu
V = 0.8 pu: capacitor/SVC at limit 0.128 pu, STATCOM at limit 0.160 pu
V = 0.7 pu: capacitor/SVC at limit 0.098 pu, STATCOM at limit 0.140 pu
tap +0 (ratio 1.0000): LV bus 0.9358 pu
tap -2 (ratio 0.9750): LV bus 0.9617 pu
tap -4 (ratio 0.9500): LV bus 0.9889 pu
The last three lines show the tap changer on a transformer () whose primary sits at : each step lifts the bus by a little more than (, , ), because the load current also falls slightly as the voltage rises. The primary network has to supply the extra reactive power.
Interactive: switch in the capacitor
The netlist lab is the same bus in per unit at : source V1 of , the Thevenin reactance as , and the load as a constant impedance ( in parallel with , which is at ). The capacitor CB has (so is ). The lab sweeps frequency; read only the values. With the smallest capacitor the bus reads , higher than the above because an impedance load draws less power when the voltage sags. At it reads , at () (at exactly both load models draw the same power), and at the top of the slider : overcompensated.
Guided lab: a capacitor on a weak signal-level bus
Hand calculation. Scale to the bench with at : the Thevenin reactance becomes ( at , or at to keep parts small), the load in parallel with of inductive reactance, and a capacitor is . Predict the voltages above for .
Simulation. Enter your measured component values in the netlist (keep the frequency you actually use) and note the predicted voltages with and without the capacitor.
What you would measure. With a function generator as the source and a true-rms DMM on the "bus", expect about without and with the capacitor, each within about , dominated by inductor tolerance and the inductor's own resistance (which also adds an in-phase drop the per-unit model ignores). Use film capacitors; electrolytics are polarised and unsuitable for AC.
Hazards and safe setup. Signal levels only ( rms, a few tens of milliamperes). No mains-powered capacitor banks or power-factor capacitors from equipment: those store dangerous energy.
Pitfalls
- Expecting a tap changer to create reactive power. It only redistributes voltage; the still comes from somewhere upstream.
- Rating a capacitor at nominal voltage and forgetting . A bank rated at gives at .
- Overcompensation. At light load, fixed capacitors push voltages high; banks are switched in steps, and reactors are switched in at night on cable-heavy networks.
- Harmonic resonance. A capacitor bank and the network inductance resonate at ; with and that is the 4th harmonic, close to the 5th that rectifiers produce. Detuning reactors fix it (Power Quality).
Practice
- A bus has a fault level of . Roughly how much does switching a reactor change its voltage?
- A SVC and a STATCOM are both at their limits with the bus at . How much does each deliver?
- The OLTC above has taps of . Which deadband would you choose, and why not ?
Answer
- , downward (a reactor absorbs ).
- SVC: ; STATCOM: .
- A total band a little wider than one step, e.g. ( wide). With one step of would jump from below the band to above it and the relay would hunt up and down.
Test yourself
A capacitor bank delivers 20 Mvar at 1.0 pu voltage. What does it deliver at 0.9 pu?
- 20 Mvar
- 18 Mvar
- 16.2 Mvar
- 22.2 Mvar
Which device keeps the most reactive output when the voltage is depressed?
- fixed capacitor
- SVC at its limit
- STATCOM at its current limit
- all the same
A 10 Mvar capacitor is switched on at a bus with a 500 MVA fault level. The voltage rises by about…
- 0.2 %
- 2 %
- 5 %
- 20 %
Why does a tap-changer controller wait tens of seconds before stepping?
- the motor must warm up
- to ignore short dips, reduce contact wear and let faster controls act first
- IEC forbids faster operation
- to keep the frequency constant