Home › Power Systems: Three-Phase, Generation, Grids & Protection › Unbalanced Loads and Three-Phase Power Measurement

Unbalanced Loads and Three-Phase Power Measurement

A small office building on a 230/400 V230/400\ \text{V} supply has its single-phase loads spread badly: 7.05 kW7.05\ \text{kW} on phase a, 3.53 kW3.53\ \text{kW} on b, 2.35 kW2.35\ \text{kW} on c. The neutral carries a large current, the voltages at the loads are no longer equal, and if the neutral conductor ever breaks, some appliances get almost 290 V290\ \text{V}. Per-phase analysis no longer applies. This lesson solves unbalanced networks in full, explains why a broken neutral is dangerous, and shows how three-phase power is metered with two or three wattmeters. Three-Phase Circuits introduced Millman's theorem for an ideal source; here line and neutral impedances are included.

Safety: a broken or high-resistance neutral is a real hazard in buildings: it overvolts appliances and can make exposed metal live. It is studied here by calculation and simulation only. Finding and repairing it is work for a qualified electrician.

Solving an unbalanced four-wire network

With unequal loads the load star point N' is no longer at the source neutral potential. Take the source neutral as reference. Each phase has a line impedance ZℓZ_\ell and a load ZkZ_k in series, and the neutral conductor has impedance ZnZ_n from N' back to the source. One nodal equation at N' gives its voltage (Millman's theorem with the neutral as a fourth branch):

VN′=∑kEk Yk∑kYk+Yn,Yk=1Zℓ+Zk,Yn=1Zn,Ik=(Ek−VN′) Yk\mathbf{V}_{N'} = \frac{\sum_k \mathbf{E}_k\,Y_k}{\sum_k Y_k + Y_n}, \qquad Y_k = \frac{1}{Z_\ell + Z_k}, \quad Y_n = \frac{1}{Z_n}, \qquad \mathbf{I}_k = (\mathbf{E}_k - \mathbf{V}_{N'})\,Y_k

With a solid neutral (Zn→0Z_n \to 0), VN′→0\mathbf{V}_{N'} \to 0 and every load gets its own phase voltage. With a broken neutral (Yn=0Y_n = 0) N' floats to wherever the currents balance, and the lightest-loaded phase (the largest impedance) gets the most voltage.

Worked example: the office building

Given: 230/400 V230/400\ \text{V} source, resistive loads Za=7.5 ΩZ_a = 7.5\ \Omega (7.05 kW7.05\ \text{kW} at 230 V230\ \text{V}), Zb=15 ΩZ_b = 15\ \Omega, Zc=22.5 ΩZ_c = 22.5\ \Omega; line resistance 0.1 Ω0.1\ \Omega per phase, neutral resistance 0.2 Ω0.2\ \Omega. (Calculation only.)

Find: the neutral current and load voltages, then the load voltages with the neutral broken.

Solve: Ya=1/7.6Y_a = 1/7.6, Yb=1/15.1Y_b = 1/15.1, Yc=1/22.6 SY_c = 1/22.6\ \text{S}, Yn=5 SY_n = 5\ \text{S}.

VN′=230(17.6+∠−120∘15.1+∠120∘22.6)17.6+115.1+122.6+5=3.45 V∠−14.0∘Ia=29.82 A,Ib=15.30 A,Ic=10.28 A,IN=VN′0.2 Ω=17.26 AVload=223.7, 229.4, 231.4 V\begin{aligned} \mathbf{V}_{N'} &= \frac{230\left(\frac{1}{7.6} + \frac{\angle -120^\circ}{15.1} + \frac{\angle 120^\circ}{22.6}\right)}{\frac{1}{7.6} + \frac{1}{15.1} + \frac{1}{22.6} + 5} = 3.45\ \text{V}\angle -14.0^\circ \\ I_a &= 29.82\ \text{A}, \quad I_b = 15.30\ \text{A}, \quad I_c = 10.28\ \text{A}, \quad I_N = \frac{V_{N'}}{0.2\ \Omega} = 17.26\ \text{A} \\ V_\text{load} &= 223.7,\ 229.4,\ 231.4\ \text{V} \end{aligned}

Broken neutral (Yn=0Y_n = 0): VN′=74.8 V∠−14.0∘\mathbf{V}_{N'} = 74.8\ \text{V}\angle -14.0^\circ, and the load voltages become 156.4156.4, 259.0259.0 and 285.7 V285.7\ \text{V}.

Check: with the neutral intact the three load currents nearly follow the ratio 3:1.5:13 : 1.5 : 1; the neutral current 17.3 A17.3\ \text{A} is a little below the ideal-source value 18.43 A18.43\ \text{A} (below) because the line and neutral resistances limit it. With the neutral broken, the 2.35 kW2.35\ \text{kW} load on phase c gets 286 V286\ \text{V}, 24 %24\ \% over its rating: electronics on that phase may fail, while phase a's loads brown out at 156 V156\ \text{V}.

Three-phase power measurement

A wattmeter multiplies one voltage by one current and averages: W=Re⁡{VI∗}W = \operatorname{Re}\{\mathbf{V}\mathbf{I}^*\}. Blondel's theorem: a system of nn wires needs n−1n - 1 wattmeter elements, each with its current coil in one wire and its voltage coil between that wire and a common reference wire (Power Measurement).

  • Four-wire: three elements, current in each line, voltage from that line to neutral. P=Wa+Wb+WcP = W_a + W_b + W_c, correct for any unbalance.
  • Three-wire (two-wattmeter or Aron method): current coils in lines a and b, voltage coils from a and b to line c:
P=W1+W2=Re⁡{VacIa∗}+Re⁡{VbcIb∗}P = W_1 + W_2 = \operatorname{Re}\{\mathbf{V}_{ac}\mathbf{I}_a^*\} + \operatorname{Re}\{\mathbf{V}_{bc}\mathbf{I}_b^*\}

This is exact for any three-wire load because Ic=−(Ia+Ib)\mathbf{I}_c = -(\mathbf{I}_a + \mathbf{I}_b). For a balanced load at angle ϕ\phi the two readings are

W1=VLILcos⁡(ϕ−30∘),W2=VLILcos⁡(ϕ+30∘),tan⁡ϕ=3 W1−W2W1+W2W_1 = V_L I_L \cos(\phi - 30^\circ), \qquad W_2 = V_L I_L \cos(\phi + 30^\circ), \qquad \tan\phi = \sqrt{3}\,\frac{W_1 - W_2}{W_1 + W_2}

so the same two readings also give the power factor. At ϕ=60∘\phi = 60^\circ (pf 0.50.5) W2W_2 is zero, and below pf 0.50.5 it goes negative: the meter must be reversed and its reading subtracted.

In Python: the building, the broken neutral and two wattmeters

python · try it yourself
import numpy as np

a = np.exp(2j * np.pi / 3)
E = 230 * np.array([1, a**2, a])              # source phase voltages a, b, c
Z = np.array([7.5, 15.0, 22.5])              # loads (ohm)
Zl = 0.1                                      # line resistance per phase

def solve(Zn):
    y = 1 / (Zl + Z)
    yn = 0 if Zn is None else 1 / Zn
    VN = (E * y).sum() / (y.sum() + yn)       # Millman with the neutral branch
    I = (E - VN) * y
    return VN, I

for label, Zn in (("neutral 0.2 ohm", 0.2), ("neutral broken", None)):
    VN, I = solve(Zn)
    print(f"{label}: VN' = {abs(VN):6.2f} V at {np.degrees(np.angle(VN)):6.1f} deg,"
          f" IN = {abs(I.sum()):5.2f} A")
    print("   line currents (A):", np.round(np.abs(I), 2), " load volts (V):", np.round(np.abs(I * Z), 1))

# Two-wattmeter method on the three-wire (broken-neutral) case, meters at the source
VN, I = solve(None)
W1 = ((E[0] - E[2]) * np.conj(I[0])).real
W2 = ((E[1] - E[2]) * np.conj(I[1])).real
P_true = (np.abs(I)**2 * (Z + Zl)).sum()
print(f"two wattmeters, 3-wire: W1 = {W1:.0f} W, W2 = {W2:.0f} W, sum = {W1 + W2:.0f} W, true P = {P_true:.0f} W")

# The same two meters on the four-wire case are wrong: the neutral current bypasses them
VN, I = solve(0.2)
W1 = ((E[0] - E[2]) * np.conj(I[0])).real
W2 = ((E[1] - E[2]) * np.conj(I[1])).real
P_true = (np.abs(I)**2 * (Z + Zl)).sum() + abs(I.sum())**2 * 0.2
print(f"two wattmeters, 4-wire: sum = {W1 + W2:.0f} W, true P = {P_true:.0f} W")

# Balanced check of tan(phi) = sqrt(3) (W1 - W2)/(W1 + W2) for a 0.8-pf load
VL, IL, phi = 400.0, 10.0, np.arccos(0.8)
w1, w2 = VL * IL * np.cos(phi - np.pi/6), VL * IL * np.cos(phi + np.pi/6)
print(f"balanced pf 0.8: W1 = {w1:.1f} W, W2 = {w2:.1f} W, recovered pf = {np.cos(np.arctan(np.sqrt(3)*(w1-w2)/(w1+w2))):.4f}")
neutral 0.2 ohm: VN' =   3.45 V at  -14.0 deg, IN = 17.26 A
   line currents (A): [29.82 15.3  10.28]  load volts (V): [223.7 229.4 231.4]
neutral broken: VN' =  74.76 V at  -14.0 deg, IN =  0.00 A
   line currents (A): [20.85 17.27 12.7 ]  load volts (V): [156.4 259.  285.7]
two wattmeters, 3-wire: W1 = 6674 W, W2 = 4778 W, sum = 11452 W, true P = 11452 W
two wattmeters, 4-wire: sum = 15500 W, true P = 12742 W
balanced pf 0.8: W1 = 3971.3 W, W2 = 1571.3 W, recovered pf = 0.8000

On the four-wire system two meters read 15.5 kW15.5\ \text{kW} instead of 12.7 kW12.7\ \text{kW}: Blondel's theorem in action. Three-phase energy meters on four-wire supplies therefore have three elements.

Interactive: neutral current and neutral shift

The three-phase lab has no line or neutral impedance, but its load ratios are adjustable: with R=7.5 ΩR = 7.5\ \Omega, X=0X = 0, kb=2k_b = 2, kc=3k_c = 3 it is the building on an ideal source. In 4-wire mode it reads Ia=30.67 AI_a = 30.67\ \text{A}, Ib=15.33 AI_b = 15.33\ \text{A}, Ic=10.22 AI_c = 10.22\ \text{A}, a neutral current of 18.43 A∠−13.9∘18.43\ \text{A}\angle -13.9^\circ and P=12.93 kWP = 12.93\ \text{kW}. Switch to 3-wire (the broken neutral): the neutral shift reads 75.39 V∠−13.9∘75.39\ \text{V}\angle -13.9^\circ, the line currents 21.0521.05, 17.4117.41 and 12.78 A12.78\ \text{A}, and PP drops to 11.54 kW11.54\ \text{kW}. Multiply each current by its load to see phase c's load at 12.78⋅22.5=288 V12.78 \cdot 22.5 = 288\ \text{V}.

VaVbVcIaIbIcINV solid, I thin (own scale)star, 4-wire-pk0+pk0T2Tphase voltages, peak 325 V-pk0+pk0T2Tline currents, peak 43.4 AP = 12.9 kW Q = 114 fvar S = 12.9 kVApf = 1.000 unbalanced IN = 18.4 A

Guided lab: a low-voltage unbalanced star

Hand calculation. Three resistors in star, 100100, 220220 and 470 Ω470\ \Omega, fed from a three-phase source of 5 V5\ \text{V} per phase: predict the neutral shift without a neutral wire, by Millman's theorem.

Simulation. Change Z, E and Zl = 0 in the program to these values.

What you would measure. A safe three-phase source at this level is a three-channel function generator (or a microcontroller board with three DAC outputs and buffers) set to 120∘120^\circ phase steps. With a DMM on AC volts you would measure the three load voltages and the star-point voltage; expect agreement with the calculation within the generators' amplitude and phase accuracy (around 1 %1\ \% and 1∘1^\circ), so within about 2 %2\ \%.

Hazards and safe setup. Signal-level sources only, with a common ground; never use transformers from the mains to build a "small three-phase supply".

Pitfalls

  • Per-phase analysis of an unbalanced load. It is wrong whenever the phases differ; solve the star point.
  • Assuming the neutral current is the sum of magnitudes. It is the phasor sum: 40+20+10=70 A40 + 20 + 10 = 70\ \text{A} in magnitude, but 26.5 A26.5\ \text{A} as phasors (with 4040, 2020 and 10 A10\ \text{A}).
  • Two wattmeters on a four-wire system. Valid only if the neutral current is zero.
  • Ignoring a negative wattmeter reading. Below pf 0.50.5, one of the two readings is negative and must be subtracted.

Practice

  1. Three loads of 10 A10\ \text{A} each at unity pf sit on phases a, b, c of a four-wire supply. Phase c's load is switched off. What is the neutral current?
  2. A balanced load gives two-wattmeter readings of 5 kW5\ \text{kW} and 2 kW2\ \text{kW}. Find PP, the power factor and QQ.
  3. Why do harmonics from single-phase electronic loads raise the neutral current even when the loads are balanced? (Hint: the third harmonic.)
Answer
  1. IN=10∠0∘+10∠−120∘=10 A∠−60∘\mathbf{I}_N = 10\angle 0^\circ + 10\angle -120^\circ = 10\ \text{A}\angle -60^\circ: 10 A10\ \text{A}.
  2. P=7 kWP = 7\ \text{kW}; tan⁡ϕ=3⋅3/7=0.742\tan\phi = \sqrt{3} \cdot 3/7 = 0.742, ϕ=36.6∘\phi = 36.6^\circ, pf 0.8030.803; Q=7tan⁡ϕ=5.20 kvarQ = 7 \tan\phi = 5.20\ \text{kvar} (also 3(W1−W2)\sqrt{3}(W_1 - W_2)).
  3. Third-harmonic currents of the three phases are in phase with each other (3⋅120∘=360∘3 \cdot 120^\circ = 360^\circ), so they add in the neutral instead of cancelling (Power Quality).

Test yourself

When the neutral of an unbalanced star load breaks, the highest voltage appears across…

  1. the most heavily loaded phase
  2. the most lightly loaded phase (largest impedance)
  3. all phases equally
  4. none: the voltages fall

How many wattmeter elements does Blondel's theorem require for a three-phase four-wire system?

  1. 1
  2. 2
  3. 3
  4. 4

For a balanced load measured by two wattmeters, one reading is zero. The power factor is…

  1. 1
  2. 0.866
  3. 0.5
  4. 0

Unity-pf loads of 40, 20 and 10 A on phases a, b, c of an ideal 4-wire supply give a neutral current of about…

  1. 70 A
  2. 26.5 A
  3. 10 A
  4. 0 A