Unbalanced Loads and Three-Phase Power Measurement
A small office building on a supply has its single-phase loads spread badly: on phase a, on b, on c. The neutral carries a large current, the voltages at the loads are no longer equal, and if the neutral conductor ever breaks, some appliances get almost . Per-phase analysis no longer applies. This lesson solves unbalanced networks in full, explains why a broken neutral is dangerous, and shows how three-phase power is metered with two or three wattmeters. Three-Phase Circuits introduced Millman's theorem for an ideal source; here line and neutral impedances are included.
Safety: a broken or high-resistance neutral is a real hazard in buildings: it overvolts appliances and can make exposed metal live. It is studied here by calculation and simulation only. Finding and repairing it is work for a qualified electrician.
Solving an unbalanced four-wire network
With unequal loads the load star point N' is no longer at the source neutral potential. Take the source neutral as reference. Each phase has a line impedance and a load in series, and the neutral conductor has impedance from N' back to the source. One nodal equation at N' gives its voltage (Millman's theorem with the neutral as a fourth branch):
With a solid neutral (), and every load gets its own phase voltage. With a broken neutral () N' floats to wherever the currents balance, and the lightest-loaded phase (the largest impedance) gets the most voltage.
Worked example: the office building
Given: source, resistive loads ( at ), , ; line resistance per phase, neutral resistance . (Calculation only.)
Find: the neutral current and load voltages, then the load voltages with the neutral broken.
Solve: , , , .
Broken neutral (): , and the load voltages become , and .
Check: with the neutral intact the three load currents nearly follow the ratio ; the neutral current is a little below the ideal-source value (below) because the line and neutral resistances limit it. With the neutral broken, the load on phase c gets , over its rating: electronics on that phase may fail, while phase a's loads brown out at .
Three-phase power measurement
A wattmeter multiplies one voltage by one current and averages: . Blondel's theorem: a system of wires needs wattmeter elements, each with its current coil in one wire and its voltage coil between that wire and a common reference wire (Power Measurement).
- Four-wire: three elements, current in each line, voltage from that line to neutral. , correct for any unbalance.
- Three-wire (two-wattmeter or Aron method): current coils in lines a and b, voltage coils from a and b to line c:
This is exact for any three-wire load because . For a balanced load at angle the two readings are
so the same two readings also give the power factor. At (pf ) is zero, and below pf it goes negative: the meter must be reversed and its reading subtracted.
In Python: the building, the broken neutral and two wattmeters
import numpy as np
a = np.exp(2j * np.pi / 3)
E = 230 * np.array([1, a**2, a]) # source phase voltages a, b, c
Z = np.array([7.5, 15.0, 22.5]) # loads (ohm)
Zl = 0.1 # line resistance per phase
def solve(Zn):
y = 1 / (Zl + Z)
yn = 0 if Zn is None else 1 / Zn
VN = (E * y).sum() / (y.sum() + yn) # Millman with the neutral branch
I = (E - VN) * y
return VN, I
for label, Zn in (("neutral 0.2 ohm", 0.2), ("neutral broken", None)):
VN, I = solve(Zn)
print(f"{label}: VN' = {abs(VN):6.2f} V at {np.degrees(np.angle(VN)):6.1f} deg,"
f" IN = {abs(I.sum()):5.2f} A")
print(" line currents (A):", np.round(np.abs(I), 2), " load volts (V):", np.round(np.abs(I * Z), 1))
# Two-wattmeter method on the three-wire (broken-neutral) case, meters at the source
VN, I = solve(None)
W1 = ((E[0] - E[2]) * np.conj(I[0])).real
W2 = ((E[1] - E[2]) * np.conj(I[1])).real
P_true = (np.abs(I)**2 * (Z + Zl)).sum()
print(f"two wattmeters, 3-wire: W1 = {W1:.0f} W, W2 = {W2:.0f} W, sum = {W1 + W2:.0f} W, true P = {P_true:.0f} W")
# The same two meters on the four-wire case are wrong: the neutral current bypasses them
VN, I = solve(0.2)
W1 = ((E[0] - E[2]) * np.conj(I[0])).real
W2 = ((E[1] - E[2]) * np.conj(I[1])).real
P_true = (np.abs(I)**2 * (Z + Zl)).sum() + abs(I.sum())**2 * 0.2
print(f"two wattmeters, 4-wire: sum = {W1 + W2:.0f} W, true P = {P_true:.0f} W")
# Balanced check of tan(phi) = sqrt(3) (W1 - W2)/(W1 + W2) for a 0.8-pf load
VL, IL, phi = 400.0, 10.0, np.arccos(0.8)
w1, w2 = VL * IL * np.cos(phi - np.pi/6), VL * IL * np.cos(phi + np.pi/6)
print(f"balanced pf 0.8: W1 = {w1:.1f} W, W2 = {w2:.1f} W, recovered pf = {np.cos(np.arctan(np.sqrt(3)*(w1-w2)/(w1+w2))):.4f}")neutral 0.2 ohm: VN' = 3.45 V at -14.0 deg, IN = 17.26 A
line currents (A): [29.82 15.3 10.28] load volts (V): [223.7 229.4 231.4]
neutral broken: VN' = 74.76 V at -14.0 deg, IN = 0.00 A
line currents (A): [20.85 17.27 12.7 ] load volts (V): [156.4 259. 285.7]
two wattmeters, 3-wire: W1 = 6674 W, W2 = 4778 W, sum = 11452 W, true P = 11452 W
two wattmeters, 4-wire: sum = 15500 W, true P = 12742 W
balanced pf 0.8: W1 = 3971.3 W, W2 = 1571.3 W, recovered pf = 0.8000
On the four-wire system two meters read instead of : Blondel's theorem in action. Three-phase energy meters on four-wire supplies therefore have three elements.
Interactive: neutral current and neutral shift
The three-phase lab has no line or neutral impedance, but its load ratios are adjustable: with , , , it is the building on an ideal source. In 4-wire mode it reads , , , a neutral current of and . Switch to 3-wire (the broken neutral): the neutral shift reads , the line currents , and , and drops to . Multiply each current by its load to see phase c's load at .
Guided lab: a low-voltage unbalanced star
Hand calculation. Three resistors in star, , and , fed from a three-phase source of per phase: predict the neutral shift without a neutral wire, by Millman's theorem.
Simulation. Change Z, E and Zl = 0 in the program to these values.
What you would measure. A safe three-phase source at this level is a three-channel function generator (or a microcontroller board with three DAC outputs and buffers) set to phase steps. With a DMM on AC volts you would measure the three load voltages and the star-point voltage; expect agreement with the calculation within the generators' amplitude and phase accuracy (around and ), so within about .
Hazards and safe setup. Signal-level sources only, with a common ground; never use transformers from the mains to build a "small three-phase supply".
Pitfalls
- Per-phase analysis of an unbalanced load. It is wrong whenever the phases differ; solve the star point.
- Assuming the neutral current is the sum of magnitudes. It is the phasor sum: in magnitude, but as phasors (with , and ).
- Two wattmeters on a four-wire system. Valid only if the neutral current is zero.
- Ignoring a negative wattmeter reading. Below pf , one of the two readings is negative and must be subtracted.
Practice
- Three loads of each at unity pf sit on phases a, b, c of a four-wire supply. Phase c's load is switched off. What is the neutral current?
- A balanced load gives two-wattmeter readings of and . Find , the power factor and .
- Why do harmonics from single-phase electronic loads raise the neutral current even when the loads are balanced? (Hint: the third harmonic.)
Answer
- : .
- ; , , pf ; (also ).
- Third-harmonic currents of the three phases are in phase with each other (), so they add in the neutral instead of cancelling (Power Quality).
Test yourself
When the neutral of an unbalanced star load breaks, the highest voltage appears across…
- the most heavily loaded phase
- the most lightly loaded phase (largest impedance)
- all phases equally
- none: the voltages fall
How many wattmeter elements does Blondel's theorem require for a three-phase four-wire system?
- 1
- 2
- 3
- 4
For a balanced load measured by two wattmeters, one reading is zero. The power factor is…
- 1
- 0.866
- 0.5
- 0
Unity-pf loads of 40, 20 and 10 A on phases a, b, c of an ideal 4-wire supply give a neutral current of about…
- 70 A
- 26.5 A
- 10 A
- 0 A