Fault Levels, the Z-Bus and Breaker Duty (IEC 60909)

The previous lesson found the fault current at one bus by reducing the network by hand. A protection engineer needs it at every bus, plus the voltages elsewhere during each fault (which relays see), and the numbers must follow a standard so that the switchgear supplier, the utility and the consultant all get the same answer. This lesson builds the bus impedance matrix Zbus\mathbf{Z}_\text{bus}, which gives all of that at once, and introduces the calculation rules of IEC 60909-0 (Short-circuit currents in three-phase AC systems, Part 0: Calculation of currents) and how its results choose a circuit breaker. The factors quoted here are those of edition 2.0 (2016); edition 3.0 was published on 23 July 2026 and replaces it, so check cc, κ\kappa and the motor rules against the 2026 text before a real study.

Safety. Fault currents of kiloamperes at 1111 to 132 kV132\ \text{kV}: calculation and simulation only.

The Z-bus

Invert the bus admittance matrix of the network with every generator and source represented by its internal impedance to the reference: Zbus=Ybus−1\mathbf{Z}_\text{bus} = \mathbf{Y}_\text{bus}^{-1}. Then:

  • the diagonal element ZkkZ_{kk} is the Thevenin impedance at bus kk, so a bolted fault there draws IF=Vk0/ZkkI_F = V_k^0/Z_{kk};
  • the off-diagonal ZikZ_{ik} gives the voltage change at bus ii caused by that fault current: Vi=Vi0−ZikIF\mathbf{V}_i = \mathbf{V}_i^0 - Z_{ik}\mathbf{I}_F;
  • branch currents during the fault follow from those voltages.

One factorisation answers every fault location. Large programs never form the full (dense) inverse; they factorise the sparse Ybus\mathbf{Y}_\text{bus} and solve for the columns they need. The Z-bus can also be built step by step, branch by branch, a method classic textbooks spend chapters on; with a linear-algebra library, inverting is simpler (Matrix Inverse and LU).

IEC 60909 in brief

The standard does not use a load-flow prefault state. It places an equivalent voltage source cUn/3cU_n/\sqrt{3} at the fault, with all other sources shorted, and uses rated (positive-sequence) impedances:

Ik′′=c Un3 ∣Zk∣,ip=κ2 Ik′′,κ=1.02+0.98 e−3R/XI_k'' = \frac{c\,U_n}{\sqrt{3}\,\lvert Z_k \rvert}, \qquad i_p = \kappa\sqrt{2}\,I_k'', \qquad \kappa = 1.02 + 0.98\,e^{-3R/X}
Quantity Meaning
voltage factor cc cmaxc_\text{max} for the largest currents (equipment ratings): 1.101.10 for medium and high voltage; 1.051.05 for low-voltage systems with +6 %+6\ \% tolerance, 1.101.10 for +10 %+10\ \%. cminc_\text{min} for the smallest (protection sensitivity): 0.950.95 LV, 1.001.00 MV/HV
Ik′′I_k'' initial symmetrical short-circuit current (rms)
ipi_p peak short-circuit current, including the DC offset; sets making capacity and mechanical forces
IbI_b symmetrical breaking current at the moment the contacts part; equals Ik′′I_k'' far from generators, smaller (μIk′′\mu I_k'') near them
IthI_\text{th} thermal equivalent current over the fault duration, for cable and busbar heating
Sk′′=3 UnIk′′S_k'' = \sqrt{3}\,U_nI_k'' short-circuit power ("fault level"), a convenient size measure

The standard also applies impedance correction factors to generators, power-station units and network transformers (KGK_G, KSK_S, KTK_T), and gives methods for κ\kappa in meshed networks (where the R/XR/X of branches differs). This lesson leaves the correction factors out, so its numbers illustrate the method; a compliant study uses them (and usually a commercial program). Remember too that κ\kappa from the Thevenin R/XR/X at the fault is an approximation in a meshed network; the standard's methods B and C are more careful.

Choosing a breaker

A high-voltage circuit breaker (IEC 62271-100:2021) is rated by, among others:

  • rated short-circuit breaking current, from the series 2020, 2525, 31.531.5, 4040, 5050, 63 kA63\ \text{kA}: must exceed IbI_b (with its DC component, which the rating covers for a standard 45 ms45\ \text{ms} time constant);
  • rated short-circuit making current: 2.52.5 times the breaking current (peak) for 50 Hz50\ \text{Hz}: must exceed ipi_p;
  • rated short-time withstand current and duration (often 11 or 3 s3\ \text{s}): must exceed IthI_\text{th} for the protection's clearing time.

Plan for growth: fault levels rise as generation and interconnection are added, and replacing switchgear because it is "overstressed" is expensive. Generator circuit breakers are a separate class (IEC/IEEE 62271-37-013) because of the very large DC offsets near generators.

Worked example: the 132 kV bus

Given: Plant P1 (Symmetrical Faults) with resistances added through typical X/RX/R ratios (G1 40, T1 30, lines 8), plus a 50 MVA50\ \text{MVA}, 132/33 kV132/33\ \text{kV} transformer T2 with x=10 %x = 10\ \% on its own rating (0.20 pu0.20\ \text{pu} on 100 MVA100\ \text{MVA}, X/R=20X/R = 20) feeding a 33 kV33\ \text{kV} bus D. From the Z-bus below, ZHH=0.0098+j0.1169 puZ_{HH} = 0.0098 + j0.1169\ \text{pu}.

Find: Ik′′I_k'', κ\kappa, ipi_p and Sk′′S_k'' at bus H with c=1.10c = 1.10, and check a 31.5 kA31.5\ \text{kA} breaker.

Solve:

∣ZHH∣=0.1173 pu,Ik′′=1.100.1173⋅437.4 A=9.38⋅437.4 A=4.10 kAκ=1.02+0.98 e−3⋅0.084=1.78,ip=1.78⋅2⋅4.10 kA=10.3 kASk′′=3⋅132 kV⋅4.10 kA=937 MVA\begin{aligned} \lvert Z_{HH} \rvert &= 0.1173\ \text{pu}, \qquad I_k'' = \frac{1.10}{0.1173} \cdot 437.4\ \text{A} = 9.38 \cdot 437.4\ \text{A} = 4.10\ \text{kA} \\ \kappa &= 1.02 + 0.98\,e^{-3 \cdot 0.084} = 1.78, \qquad i_p = 1.78 \cdot \sqrt{2} \cdot 4.10\ \text{kA} = 10.3\ \text{kA} \\ S_k'' &= \sqrt{3} \cdot 132\ \text{kV} \cdot 4.10\ \text{kA} = 937\ \text{MVA} \end{aligned}

Check: a 31.5 kA31.5\ \text{kA} breaker (making 78.75 kA78.75\ \text{kA} peak) has a large margin; 132 kV132\ \text{kV} switchgear is commonly 31.531.5 or 40 kA40\ \text{kA} because real substations have far higher fault levels than this small example. Compared with the reactance-only answer of the last lesson (8.57 pu8.57\ \text{pu} at 1.0 pu1.0\ \text{pu} voltage), the factor c=1.1c = 1.1 raises the current by 10 %10\ \% and the resistances lower it slightly.

In Python: Z-bus, fault levels at every bus, and voltages during a fault

python · try it yourself
import numpy as np

# Plant P1 plus a 33 kV substation, 100 MVA base. Nodes: G (11 kV), H (132 kV), D (33 kV); the infinite
# bus is the reference node (zero impedance to it). Each branch: (from, to, x, X/R); to = None means reference.
def z(x, xr):
    return complex(x / xr, x)
branches = [("G", None, z(0.18, 40), "G1 (X''d)"),
            ("G", "H", z(0.10, 30), "T1"),
            ("H", None, z(0.40, 8), "line 1"),
            ("H", None, z(0.40, 8), "line 2"),
            ("H", "D", z(0.20, 20), "T2 132/33 kV, 50 MVA, x = 10 %")]
nodes = ["G", "H", "D"]
idx = {b: i for i, b in enumerate(nodes)}
Y = np.zeros((3, 3), dtype=complex)
for a, b, zz, _ in branches:
    y = 1 / zz
    Y[idx[a], idx[a]] += y
    if b is not None:
        Y[idx[b], idx[b]] += y
        Y[idx[a], idx[b]] -= y
        Y[idx[b], idx[a]] -= y
Z = np.linalg.inv(Y)                         # Z-bus: Z[k, k] is the Thevenin impedance at bus k
np.set_printoptions(precision=4, suppress=True)
print("Z-bus (pu):")
print(Z)

kV = {"G": 11.0, "H": 132.0, "D": 33.0}
c = 1.10                                     # IEC 60909-0 voltage factor c_max for MV and HV
for k in nodes:
    Zk = Z[idx[k], idx[k]]
    Ik = c / abs(Zk)                         # pu, prefault voltage c times nominal
    Ib = 100e6 / (np.sqrt(3) * kV[k] * 1e3)
    RX = Zk.real / Zk.imag
    kappa = 1.02 + 0.98 * np.exp(-3 * RX)
    print(f"bus {k} ({kV[k]:5.1f} kV): Zth = {Zk.real:.4f}+j{Zk.imag:.4f} pu, R/X = {RX:.3f}, "
          f"Ik'' = {Ik*Ib/1e3:6.2f} kA ({np.sqrt(3)*kV[k]*Ik*Ib/1e3:5.0f} MVA), "
          f"kappa = {kappa:.3f}, ip = {kappa*np.sqrt(2)*Ik*Ib/1e3:6.2f} kA")

# Voltages everywhere during a bolted fault at H: V_i = c - Z_iH * I_F (prefault c everywhere)
IF = c / Z[idx["H"], idx["H"]]
for i in nodes:
    print(f"fault at H: |V_{i}| = {abs(c - Z[idx[i], idx['H']] * IF):.3f} pu")
Z-bus (pu):
[[0.0057+0.1126j 0.0061+0.0752j 0.0061+0.0752j]
 [0.0061+0.0752j 0.0098+0.1169j 0.0098+0.1169j]
 [0.0061+0.0752j 0.0098+0.1169j 0.0198+0.3169j]]
bus G ( 11.0 kV): Zth = 0.0057+j0.1126 pu, R/X = 0.051, Ik'' =  51.20 kA (  975 MVA), kappa = 1.861, ip = 134.75 kA
bus H (132.0 kV): Zth = 0.0098+j0.1169 pu, R/X = 0.084, Ik'' =   4.10 kA (  937 MVA), kappa = 1.781, ip =  10.33 kA
bus D ( 33.0 kV): Zth = 0.0198+j0.3169 pu, R/X = 0.063, Ik'' =   6.06 kA (  346 MVA), kappa = 1.832, ip =  15.70 kA
fault at H: |V_G| = 0.393 pu
fault at H: |V_H| = 0.000 pu
fault at H: |V_D| = 0.000 pu

The generator terminal bus G has by far the largest current (51 kA51\ \text{kA} at 11 kV11\ \text{kV}, ipi_p near 135 kA135\ \text{kA}): that is a generator-breaker duty. The 33 kV33\ \text{kV} bus D sees 6.06 kA6.06\ \text{kA}, so a 25 kA25\ \text{kA} breaker (making 62.5 kA62.5\ \text{kA} peak, against ip=15.7 kAi_p = 15.7\ \text{kA}) is ample. During a fault at H, the generator terminals hold 0.39 pu0.39\ \text{pu} (of the 1.11.1 source): the off-diagonal ZGHZ_{GH} at work. Bus D, beyond the fault and with no source of its own, collapses to zero.

Interactive: a fault on the 33 kV bus

The same network in the netlist lab, in per unit at 50 Hz50\ \text{Hz}: both sources at 1.11.1 (the generator behind Xd′′X_d'', and the infinite bus), each branch as RR in series with L=x/(2π⋅50)L = x/(2\pi \cdot 50) (the two lines combined), and a fault resistor RF at bus d. The lab sweeps frequency; read only the 50 Hz50\ \text{Hz} values. With RF at 1 mΩ1\ \text{m}\Omega the fault current is 3.463 pu3.463\ \text{pu} at −86.2∘-86.2^\circ, i.e. 3.463⋅1749.5 A=6.06 kA3.463 \cdot 1749.5\ \text{A} = 6.06\ \text{kA}, and the 132 kV132\ \text{kV} bus h sags to 0.6940.694 (0.630.63 of its prefault 1.11.1). Raise RF to model an arcing or high-resistance fault and watch the current fall and the voltages recover.

0.00.5100m1101001k10kf (Hz)|V| (V)|V(d)||V(h)||V(g)|phasors at f = 50.00 Hz (magnitude @ phase)V(e)1.10 V @ 0.0 degV(g1)1.10 V @ 0.3 degV(g)839 mV @ 0.3 degV(t1)839 mV @ 0.6 degV(h)694 mV @ 0.6 degV(l1)700 mV @ -3.5 degV(i)1.10 V @ 0.0 degV(d1)693 mV @ 3.5 degV(d)3.46 mV @ -86.2 degI(V1)1.45 A @ 90.6 degI(RG)1.45 A @ -89.4 degI(LG)1.45 A @ -89.4 degI(RT)1.45 A @ -89.4 degI(LT)1.45 A @ -89.4 degI(RL)2.02 A @ 96.1 degI(LL)2.02 A @ 96.1 degI(V2)2.02 A @ 96.1 degI(RT2)3.46 A @ -86.2 degI(LT2)3.46 A @ -86.2 degI(RF)3.46 A @ -86.2 deg

Guided lab: a fault-level study from data

Hand calculation. Take a real-looking case: a 20 kV20\ \text{kV} bus fed by a 40 MVA40\ \text{MVA}, 110/20 kV110/20\ \text{kV} transformer with uk=12 %u_k = 12\ \%, upstream fault level 3000 MVA3000\ \text{MVA}. Compute Ik′′I_k'' (c=1.1c = 1.1) on a 100 MVA100\ \text{MVA} base by hand: zs=0.0333z_s = 0.0333, zt=0.30z_t = 0.30, Ik′′=1.1/0.3333=3.30 pu=9.5 kAI_k'' = 1.1/0.3333 = 3.30\ \text{pu} = 9.5\ \text{kA}.

Simulation. Add the bus to the program as an extra node and recompute, with X/R=15X/R = 15 for the transformer and 1010 for the grid.

What you would measure. Nobody measures a bolted fault on purpose. Utilities validate fault-level models with network impedance measurements (small, controlled disturbances) and with disturbance recorder data from real faults: relays record currents with errors of a few percent, and the comparison typically agrees within 55 to 10 %10\ \%. At the bench, the equivalent is measuring a low-voltage source's internal impedance: load a current-limited supply set to 12 V12\ \text{V} in two steps and compute ΔV/ΔI\Delta V/\Delta I, a "fault level" without a fault.

Hazards and safe setup. Bench: 12 V12\ \text{V}, current-limited, power resistors rated for the current. Never short-circuit a battery or an unlimited supply to "measure" its short-circuit current.

Pitfalls

  • Inverting Ybus\mathbf{Y}_\text{bus} without source impedances. Without a path to the reference the matrix is singular; generators and grid infeeds must be in it.
  • Using cmaxc_\text{max} for protection sensitivity. Minimum fault currents (relay pick-up checks) use cminc_\text{min} and the weakest source configuration.
  • Ignoring motor contributions. Running induction and synchronous motors feed a fault for a few cycles; IEC 60909 includes them.
  • Forgetting future growth. Size switchgear for the fault level expected over its life, not today's.

Practice

  1. At bus D, what are Ik′′I_k'' and Sk′′S_k'' with cmin=1.0c_\text{min} = 1.0?
  2. A breaker rated 25 kA25\ \text{kA} at 33 kV33\ \text{kV}: what is its rated making current, and its "MVA rating" 3UnI\sqrt{3}U_nI?
  3. Why is ZHD=ZHHZ_{HD} = Z_{HH} in the printed Z-bus?
Answer
  1. 6.06/1.1=5.51 kA6.06/1.1 = 5.51\ \text{kA}, 3⋅33⋅5.51=315 MVA\sqrt{3} \cdot 33 \cdot 5.51 = 315\ \text{MVA}.
  2. 2.5⋅25=62.5 kA2.5 \cdot 25 = 62.5\ \text{kA} peak; 3⋅33⋅25=1429 MVA\sqrt{3} \cdot 33 \cdot 25 = 1429\ \text{MVA}.
  3. Bus D hangs radially from H with no source behind it: a current injected at D flows entirely through H, so it changes H's voltage exactly as an injection at H would.

Test yourself

The diagonal element ZkkZ_{kk} of the bus impedance matrix is…

  1. the impedance of the line to bus kk
  2. the Thevenin impedance seen at bus kk
  3. the load impedance at bus kk
  4. always zero

IEC 60909-0 uses cmax=1.10c_\text{max} = 1.10 in a 33 kV system to calculate…

  1. the smallest fault currents for relay sensitivity
  2. the largest fault currents for equipment ratings
  3. the load current
  4. the earth-fault current only

A 50 Hz circuit breaker rated 40 kA breaking has a rated making current of…

  1. 40 kA
  2. 56.6 kA
  3. 100 kA peak
  4. 160 kA peak

Which quantity sets the mechanical forces on busbars during a fault?

  1. Ik′′I_k'' rms
  2. the peak current ipi_p
  3. the breaking current IbI_b
  4. the load current