The Ferranti Effect, Voltage Regulation and Line Loadability
In 1890 Sebastian de Ferranti noticed that the far end of a long, lightly loaded cable in his London scheme sat at a higher voltage than the station end. The same thing happens on every long line: energise of line with nothing connected at the far end and the open end rises almost , past what the equipment there is built for. This lesson explains that rise, shows how shunt reactors tame it, checks the result with a real SPICE run, and then asks the planning question that follows: how much power can a line of a given length really carry? Long Lines derived the ABCD parameters used here.
Safety: line energisation and switching are studied here by calculation and simulation only. The bench lab is a signal-level LC ladder.
Why the open end rises
With the receiving end open, , so :
Physically: the line's charging current flows through its series inductance, and a capacitive current through an inductor raises the voltage downstream (the voltage across is in phase opposition to the source's drop it would make for a lagging current). The rise grows with the square of the length and is independent of the voltage level: at it is about for , for and for of overhead line. Cables, with their large , show it at much shorter lengths.
The cure is a shunt reactor at the open end (or both ends) that absorbs the line's charging reactive power. A reactor that compensates fully gives the line the electrical behaviour of a much shorter one at no load; at full load the reactors are switched out, because then the line needs vars rather than produces them.
Voltage regulation
The regulation of a line with sending voltage held constant is the change of the receiving voltage from no load to full load, , with . For long lines this is large in both directions: a voltage above nominal at light load (Ferranti) and below at heavy load. Utilities usually aim to keep transmission voltages within about of nominal in normal operation (the exact band is set by each grid code), which needs tap changers, reactors, capacitors and generator reactive power working together (Voltage Control).
Worked example: energising 400 km at no load
Given: the , line of the previous lesson (); sending end held at ; receiving end open.
Find: the open-end voltage, and the shunt reactor at the open end that brings it back to about .
Solve:
The line's total charging at is . A reactor of about half of that at the open end holds the voltage: the SPICE run below finds that (, ) gives .
Check: the small-angle approximation () is close to the exact ; the difference is the next term of . Typical practice is indeed to install shunt reactors totalling a large fraction of the charging power on long EHV lines.
Cross-check in SPICE: the line as eight sections
The session builds the line from eight sections (, , per section) with a source standing for at the sending end, and solves it at three times: open, with the reactor, and loaded at SIL ().
{
echo "* 400 km, 400 kV line as 8 pi sections of 50 km (1 V = sending-end voltage)"
echo "V1 n0 0 AC 1"
echo "C0 n0 0 263.5n"
for k in 1 2 3 4 5 6 7 8; do
echo "R$k n$((k-1)) m$k 1.5"
echo "L$k m$k n$k 53.84m"
if [ $k -lt 8 ]; then echo "C$k n$k 0 527n"; else echo "C$k n$k 0 263.5n"; fi
done
} > line.inc
for case in open reactor SIL; do
cp line.inc $case.cir
[ $case = reactor ] && echo "LSH n8 0 5.093" >> $case.cir
[ $case = SIL ] && echo "RLD n8 0 320" >> $case.cir
printf '.control\nac lin 1 50 50\nlet r = vm(n8)\nlet mid = vm(n4)\necho "%s: V(end) = amp;r V(middle) = amp;mid"\n.endc\n.end\n' $case >> $case.cir
ngspice -b $case.cir 2>&1 | grep 'V(end)'
doneopen: V(end) = 1.09683 V(middle) = 1.07234
reactor: V(end) = 1.00623 V(middle) = 1.02602
SIL: V(end) = 0.965908 V(middle) = 0.983737
Eight lumped sections reproduce the exact . With the reactor the end is at but the middle of the line still bulges to , which is why long lines sometimes get reactors at intermediate substations too. At SIL the profile droops gently ( at the end) because of the line resistance.
Line loadability
How much a line can carry depends on its length (Long Lines gives SIL as the yardstick):
- Short lines (up to about ): the thermal limit, set by conductor temperature and sag, typically to times SIL.
- Medium lines: the voltage-drop limit, often taken as .
- Long lines: the steady-state stability limit. The power a line can transfer is , and planners keep a margin (a common rule is , so a transfer angle of about at most across the line).
Plotting the minimum against length gives the classic loadability curve (the St. Clair curve, first published in 1953 and extended analytically to EHV and UHV lines in 1979 by Gutman, Marchenko and Dunlop): about 3 SIL at ( miles), about 2 SIL near and 1 SIL at about ( miles), falling below 1 SIL beyond that. The program computes a simplified version for our line, with an assumed thermal rating of per phase.
import numpy as np
import matplotlib.pyplot as plt
z, y = 0.030 + 0.3383j, 3.311e-6j
g, Zc = np.sqrt(z * y), np.sqrt(z / y)
V = 400e3
SIL = V**2 / abs(Zc)
w = 2 * np.pi * 50
# Ferranti rise: exact and approximation
for ell in (100, 250, 400):
exact = 1 / abs(np.cosh(g * ell))
approx = 1 + (g.imag * ell)**2 / 2
print(f"{ell:3d} km: open-end rise exact {100*(exact - 1):5.2f} %, (beta l)^2/2 gives {100*(approx - 1):5.2f} %")
Qch = V**2 * y.imag * 400
print(f"charging of 400 km at 400 kV: {Qch/1e6:.0f} Mvar; a 100 Mvar reactor is L = {V**2/100e6/w:.3f} H")
# Simplified loadability: thermal 2000 A, stability with 30 % margin (Vs = 1.0, VR = 0.95 pu)
lengths = np.linspace(50, 800, 151)
P_th = np.sqrt(3) * V * 2000 * np.ones_like(lengths)
P_st = 0.7 * V * 0.95 * V / np.abs(Zc * np.sinh(g * lengths))
P = np.minimum(P_th, P_st)
for ell in (80, 150, 300, 450, 600, 800):
k = np.argmin(abs(lengths - ell))
print(f"{ell:3d} km: thermal {P_th[k]/SIL:4.2f} SIL, stability {P_st[k]/SIL:4.2f} SIL -> limit {P[k]/SIL:4.2f} SIL ({P[k]/1e6:5.0f} MW)")
fig, ax = plt.subplots(figsize=(7, 3.4))
ax.plot(lengths, P_th / SIL, "--", label="thermal (2000 A)")
ax.plot(lengths, P_st / SIL, ":", label="stability, 30 % margin")
ax.plot(lengths, P / SIL, lw=2.5, label="loadability")
ax.set_xlabel("line length (km)"); ax.set_ylabel("power / SIL"); ax.set_ylim(0, 5)
ax.legend(); ax.grid(alpha=0.3); fig.tight_layout()
plt.show()100 km: open-end rise exact 0.56 %, (beta l)^2/2 gives 0.56 %
250 km: open-end rise exact 3.61 %, (beta l)^2/2 gives 3.51 %
400 km: open-end rise exact 9.68 %, (beta l)^2/2 gives 8.98 %
charging of 400 km at 400 kV: 212 Mvar; a 100 Mvar reactor is L = 5.093 H
80 km: thermal 2.77 SIL, stability 7.85 SIL -> limit 2.77 SIL ( 1386 MW)
150 km: thermal 2.77 SIL, stability 4.20 SIL -> limit 2.77 SIL ( 1386 MW)
300 km: thermal 2.77 SIL, stability 2.13 SIL -> limit 2.13 SIL ( 1062 MW)
450 km: thermal 2.77 SIL, stability 1.45 SIL -> limit 1.45 SIL ( 723 MW)
600 km: thermal 2.77 SIL, stability 1.12 SIL -> limit 1.12 SIL ( 559 MW)
800 km: thermal 2.77 SIL, stability 0.89 SIL -> limit 0.89 SIL ( 443 MW)
This simplified curve leaves out the voltage-drop limit in the middle range, so it is optimistic there; the published curves include it.
Interactive: a shunt reactor at the open end
The netlist lab holds the line as its exact (in per unit of the sending voltage): at each end (), and (), and a shunt reactor LSH at the open end. Read the values at the cursor. At its default (, ) the open end reads , i.e. , as in SPICE. Slide LSH to (only , practically no reactor) and the end rises to ; slide it down to () and the end falls to : over-compensation.
Guided lab: the Ferranti effect in an LC ladder
Hand calculation. A ladder of four sections, each in series and to ground, has a resonance (quarter-wave) near for the equivalent distributed line; the four-section ladder itself resonates lower, at . At , , so a distributed line would rise by about ; the ladder, with a full at its open end, gives (solve it in the netlist lab).
Simulation. Enter the ladder in the netlist lab (four inductors, four capacitors) and sweep f; or copy the SPICE deck above with these values.
What you would measure. With a function generator at rms, , and a DMM on AC volts (check it is accurate at ) at the input and the open end, a rise of about , growing quickly as you raise the frequency toward the ladder's resonance. Inductor resistance reduces the rise; expect agreement after allowing for it.
Hazards and safe setup. Signal levels only. Near resonance the open-end voltage can be several times the input: keep the generator at a few volts.
Pitfalls
- Energising a long line from the wrong end. Energise from the stronger end and with reactors in service, or the open end can exceed its rating.
- Leaving reactors in at full load. They then absorb vars the line needs, depressing the voltage.
- Using the thermal rating for long lines. A line cannot use its conductors' thermal capacity without series compensation or HVDC.
- Forgetting cables. A cable can show a Ferranti rise like that of well over of overhead line, with far more charging current.
Practice
- Estimate the open-end rise of a overhead line at (wave speed ).
- A line draws of charging. What inductance per phase absorbs half of it at ?
- Why does the loadability of a long line fall roughly as ?
Answer
- ; rise (exact ).
- ; .
- The stability limit is and for moderate lengths, so it falls as (and faster as grows).
Test yourself
The Ferranti rise of an open-circuited line grows with length roughly as…
- it does not depend on length
Which device limits the Ferranti rise on a lightly loaded EHV line?
- shunt capacitor
- shunt reactor
- series capacitor
- surge arrester
What usually limits the power of a 600 km line?
- conductor temperature
- steady-state stability (angle)
- corona
- the CTs
With 400 kV at the sending end and , the open-end voltage is about…
- 364 kV
- 400 kV
- 440 kV
- 480 kV