The Ferranti Effect, Voltage Regulation and Line Loadability

In 1890 Sebastian de Ferranti noticed that the far end of a long, lightly loaded cable in his London scheme sat at a higher voltage than the station end. The same thing happens on every long line: energise 400 km400\ \text{km} of 400 kV400\ \text{kV} line with nothing connected at the far end and the open end rises almost 10 %10\ \%, past what the equipment there is built for. This lesson explains that rise, shows how shunt reactors tame it, checks the result with a real SPICE run, and then asks the planning question that follows: how much power can a line of a given length really carry? Long Lines derived the ABCD parameters used here.

Safety: line energisation and switching are studied here by calculation and simulation only. The bench lab is a signal-level LC ladder.

Why the open end rises

With the receiving end open, IR=0\mathbf{I}_R = 0, so Vs=AVR\mathbf{V}_s = A\mathbf{V}_R:

VRVs=1∣cosh⁡γℓ∣≈1cos⁡βℓ≈1+(βℓ)22=1+ω2LC ℓ22\frac{V_R}{V_s} = \frac{1}{\lvert\cosh\gamma\ell\rvert} \approx \frac{1}{\cos\beta\ell} \approx 1 + \frac{(\beta\ell)^2}{2} = 1 + \frac{\omega^2 LC\,\ell^2}{2}

Physically: the line's charging current flows through its series inductance, and a capacitive current through an inductor raises the voltage downstream (the voltage across LL is in phase opposition to the source's drop it would make for a lagging current). The rise grows with the square of the length and is independent of the voltage level: at 50 Hz50\ \text{Hz} it is about 0.6 %0.6\ \% for 100 km100\ \text{km}, 3.6 %3.6\ \% for 250 km250\ \text{km} and 10 %10\ \% for 400 km400\ \text{km} of overhead line. Cables, with their large CC, show it at much shorter lengths.

The cure is a shunt reactor at the open end (or both ends) that absorbs the line's charging reactive power. A reactor that compensates fully gives the line the electrical behaviour of a much shorter one at no load; at full load the reactors are switched out, because then the line needs vars rather than produces them.

Voltage regulation

The regulation of a line with sending voltage held constant is the change of the receiving voltage from no load to full load, VR=(VR,NL−VR,FL)/VR,FL\text{VR} = (V_{R,\text{NL}} - V_{R,\text{FL}})/V_{R,\text{FL}}, with VR,NL=Vs/∣A∣V_{R,\text{NL}} = V_s/\lvert A \rvert. For long lines this is large in both directions: a voltage above nominal at light load (Ferranti) and below at heavy load. Utilities usually aim to keep transmission voltages within about ±5 %\pm 5\ \% of nominal in normal operation (the exact band is set by each grid code), which needs tap changers, reactors, capacitors and generator reactive power working together (Voltage Control).

Worked example: energising 400 km at no load

Given: the 400 kV400\ \text{kV}, 400 km400\ \text{km} line of the previous lesson (A=0.9117+j0.0077A = 0.9117 + j0.0077); sending end held at 400 kV400\ \text{kV}; receiving end open.

Find: the open-end voltage, and the shunt reactor at the open end that brings it back to about 400 kV400\ \text{kV}.

Solve:

VR=400 kV∣0.9117+j0.0077∣=400 kV0.9117=438.7 kV(+9.7 %)approximation: 1+(βℓ)22=1+0.423822=1.090\begin{aligned} V_R &= \frac{400\ \text{kV}}{\lvert 0.9117 + j0.0077 \rvert} = \frac{400\ \text{kV}}{0.9117} = 438.7\ \text{kV} \quad (+9.7\ \%) \\ \text{approximation: } 1 + \frac{(\beta\ell)^2}{2} &= 1 + \frac{0.4238^2}{2} = 1.090 \end{aligned}

The line's total charging at 400 kV400\ \text{kV} is V2ωCℓ=(400 kV)2⋅3.311×10−6⋅400=212 MvarV^2 \omega C\ell = (400\ \text{kV})^2 \cdot 3.311 \times 10^{-6} \cdot 400 = 212\ \text{Mvar}. A reactor of about half of that at the open end holds the voltage: the SPICE run below finds that 100 Mvar100\ \text{Mvar} (X=4002/100=1600 ΩX = 400^2/100 = 1600\ \Omega, L=5.093 HL = 5.093\ \text{H}) gives 1.006 pu1.006\ \text{pu}.

Check: the small-angle approximation (1.0901.090) is close to the exact 1.0971.097; the difference is the next term of 1/cos⁡βℓ1/\cos\beta\ell. Typical practice is indeed to install shunt reactors totalling a large fraction of the charging power on long EHV lines.

Cross-check in SPICE: the line as eight π\pi sections

The session builds the line from eight 50 km50\ \text{km} π\pi sections (R=1.5 ΩR = 1.5\ \Omega, L=53.84 mHL = 53.84\ \text{mH}, C=527 nFC = 527\ \text{nF} per section) with a 1 V1\ \text{V} source standing for 1 pu1\ \text{pu} at the sending end, and solves it at 50 Hz50\ \text{Hz} three times: open, with the 100 Mvar100\ \text{Mvar} reactor, and loaded at SIL (320 Ω320\ \Omega).

bash · try it yourself
{
  echo "* 400 km, 400 kV line as 8 pi sections of 50 km (1 V = sending-end voltage)"
  echo "V1 n0 0 AC 1"
  echo "C0 n0 0 263.5n"
  for k in 1 2 3 4 5 6 7 8; do
    echo "R$k n$((k-1)) m$k 1.5"
    echo "L$k m$k n$k 53.84m"
    if [ $k -lt 8 ]; then echo "C$k n$k 0 527n"; else echo "C$k n$k 0 263.5n"; fi
  done
} > line.inc
for case in open reactor SIL; do
  cp line.inc $case.cir
  [ $case = reactor ] && echo "LSH n8 0 5.093" >> $case.cir
  [ $case = SIL ] && echo "RLD n8 0 320" >> $case.cir
  printf '.control\nac lin 1 50 50\nlet r = vm(n8)\nlet mid = vm(n4)\necho "%s: V(end) = 
amp;r V(middle) =
amp;mid"\n.endc\n.end\n' $case >> $case.cir ngspice -b $case.cir 2>&1 | grep 'V(end)' done
open: V(end) = 1.09683  V(middle) = 1.07234
reactor: V(end) = 1.00623  V(middle) = 1.02602
SIL: V(end) = 0.965908  V(middle) = 0.983737

Eight lumped sections reproduce the exact 1/∣A∣=1.09681/\lvert A \rvert = 1.0968. With the reactor the end is at 1.006 pu1.006\ \text{pu} but the middle of the line still bulges to 1.026 pu1.026\ \text{pu}, which is why long lines sometimes get reactors at intermediate substations too. At SIL the profile droops gently (0.9660.966 at the end) because of the line resistance.

Line loadability

How much a line can carry depends on its length (Long Lines gives SIL as the yardstick):

  • Short lines (up to about 80 km80\ \text{km}): the thermal limit, set by conductor temperature and sag, typically 22 to 33 times SIL.
  • Medium lines: the voltage-drop limit, often taken as 5 %5\ \%.
  • Long lines: the steady-state stability limit. The power a line can transfer is Pmax≈VsVR/∣B∣P_\text{max} \approx V_sV_R/\lvert B \rvert, and planners keep a margin (a common rule is 30 %30\ \%, so a transfer angle of about 44∘44^\circ at most across the line).

Plotting the minimum against length gives the classic loadability curve (the St. Clair curve, first published in 1953 and extended analytically to EHV and UHV lines in 1979 by Gutman, Marchenko and Dunlop): about 3 SIL at 80 km80\ \text{km} (5050 miles), about 2 SIL near 160 km160\ \text{km} and 1 SIL at about 480 km480\ \text{km} (300300 miles), falling below 1 SIL beyond that. The program computes a simplified version for our 400 kV400\ \text{kV} line, with an assumed thermal rating of 2000 A2000\ \text{A} per phase.

python · try it yourself
import numpy as np
import matplotlib.pyplot as plt

z, y = 0.030 + 0.3383j, 3.311e-6j
g, Zc = np.sqrt(z * y), np.sqrt(z / y)
V = 400e3
SIL = V**2 / abs(Zc)
w = 2 * np.pi * 50

# Ferranti rise: exact and approximation
for ell in (100, 250, 400):
    exact = 1 / abs(np.cosh(g * ell))
    approx = 1 + (g.imag * ell)**2 / 2
    print(f"{ell:3d} km: open-end rise exact {100*(exact - 1):5.2f} %, (beta l)^2/2 gives {100*(approx - 1):5.2f} %")
Qch = V**2 * y.imag * 400
print(f"charging of 400 km at 400 kV: {Qch/1e6:.0f} Mvar; a 100 Mvar reactor is L = {V**2/100e6/w:.3f} H")

# Simplified loadability: thermal 2000 A, stability with 30 % margin (Vs = 1.0, VR = 0.95 pu)
lengths = np.linspace(50, 800, 151)
P_th = np.sqrt(3) * V * 2000 * np.ones_like(lengths)
P_st = 0.7 * V * 0.95 * V / np.abs(Zc * np.sinh(g * lengths))
P = np.minimum(P_th, P_st)
for ell in (80, 150, 300, 450, 600, 800):
    k = np.argmin(abs(lengths - ell))
    print(f"{ell:3d} km: thermal {P_th[k]/SIL:4.2f} SIL, stability {P_st[k]/SIL:4.2f} SIL -> limit {P[k]/SIL:4.2f} SIL ({P[k]/1e6:5.0f} MW)")

fig, ax = plt.subplots(figsize=(7, 3.4))
ax.plot(lengths, P_th / SIL, "--", label="thermal (2000 A)")
ax.plot(lengths, P_st / SIL, ":", label="stability, 30 % margin")
ax.plot(lengths, P / SIL, lw=2.5, label="loadability")
ax.set_xlabel("line length (km)"); ax.set_ylabel("power / SIL"); ax.set_ylim(0, 5)
ax.legend(); ax.grid(alpha=0.3); fig.tight_layout()
plt.show()
100 km: open-end rise exact  0.56 %, (beta l)^2/2 gives  0.56 %
250 km: open-end rise exact  3.61 %, (beta l)^2/2 gives  3.51 %
400 km: open-end rise exact  9.68 %, (beta l)^2/2 gives  8.98 %
charging of 400 km at 400 kV: 212 Mvar; a 100 Mvar reactor is L = 5.093 H
 80 km: thermal 2.77 SIL, stability 7.85 SIL -> limit 2.77 SIL ( 1386 MW)
150 km: thermal 2.77 SIL, stability 4.20 SIL -> limit 2.77 SIL ( 1386 MW)
300 km: thermal 2.77 SIL, stability 2.13 SIL -> limit 2.13 SIL ( 1062 MW)
450 km: thermal 2.77 SIL, stability 1.45 SIL -> limit 1.45 SIL (  723 MW)
600 km: thermal 2.77 SIL, stability 1.12 SIL -> limit 1.12 SIL (  559 MW)
800 km: thermal 2.77 SIL, stability 0.89 SIL -> limit 0.89 SIL (  443 MW)

This simplified curve leaves out the voltage-drop limit in the middle range, so it is optimistic there; the published curves include it.

Interactive: a shunt reactor at the open end

The netlist lab holds the line as its exact π\pi (in per unit of the sending voltage): C=2.140 μFC = 2.140\ \mu\text{F} at each end (Y′/2=0.6723 mSY'/2 = 0.6723\ \text{mS}), R=11.29 ΩR = 11.29\ \Omega and L=0.4181 HL = 0.4181\ \text{H} (131.35 Ω131.35\ \Omega), and a shunt reactor LSH at the open end. Read the values at the 50 Hz50\ \text{Hz} cursor. At its default (5.093 H5.093\ \text{H}, 100 Mvar100\ \text{Mvar}) the open end reads 1.006 V1.006\ \text{V}, i.e. 1.006 pu1.006\ \text{pu}, as in SPICE. Slide LSH to 100 H100\ \text{H} (only 5 Mvar5\ \text{Mvar}, practically no reactor) and the end rises to 1.092 pu1.092\ \text{pu}; slide it down to 3 H3\ \text{H} (170 Mvar170\ \text{Mvar}) and the end falls to 0.951 pu0.951\ \text{pu}: over-compensation.

01020100m1101001k10kf (Hz)|V| (V)|V(r)|phasors at f = 50.00 Hz (magnitude @ phase)V(s)1.00 V @ 0.0 degV(m)1.00 V @ 0.0 degV(r)1.01 V @ 0.0 degI(V1)720 uA @ -90.0 degI(C1)672 uA @ 90.0 degI(R1)47.6 uA @ 90.0 degI(L1)47.6 uA @ 90.0 degI(C2)677 uA @ 90.0 degI(LSH)629 uA @ -90.0 deg

Guided lab: the Ferranti effect in an LC ladder

Hand calculation. A ladder of four sections, each 1 mH1\ \text{mH} in series and 100 nF100\ \text{nF} to ground, has a resonance (quarter-wave) near f≈1/(4⋅4LC)≈6 kHzf \approx 1/(4 \cdot 4\sqrt{LC}) \approx 6\ \text{kHz} for the equivalent distributed line; the four-section ladder itself resonates lower, at 5.53 kHz5.53\ \text{kHz}. At 1 kHz1\ \text{kHz}, βℓ=4⋅2π⋅100010−3⋅10−7=0.251 rad\beta\ell = 4 \cdot 2\pi \cdot 1000\sqrt{10^{-3} \cdot 10^{-7}} = 0.251\ \text{rad}, so a distributed line would rise by about 3.2 %3.2\ \%; the ladder, with a full 100 nF100\ \text{nF} at its open end, gives 4.1 %4.1\ \% (solve it in the netlist lab).

Simulation. Enter the ladder in the netlist lab (four inductors, four capacitors) and sweep f; or copy the SPICE deck above with these values.

What you would measure. With a function generator at 5 V5\ \text{V} rms, 1 kHz1\ \text{kHz}, and a DMM on AC volts (check it is accurate at 1 kHz1\ \text{kHz}) at the input and the open end, a rise of about 4 %4\ \%, growing quickly as you raise the frequency toward the ladder's resonance. Inductor resistance reduces the rise; expect ±1 %\pm 1\ \% agreement after allowing for it.

Hazards and safe setup. Signal levels only. Near resonance the open-end voltage can be several times the input: keep the generator at a few volts.

Pitfalls

  • Energising a long line from the wrong end. Energise from the stronger end and with reactors in service, or the open end can exceed its rating.
  • Leaving reactors in at full load. They then absorb vars the line needs, depressing the voltage.
  • Using the thermal rating for long lines. A 600 km600\ \text{km} line cannot use its conductors' thermal capacity without series compensation or HVDC.
  • Forgetting cables. A 50 km50\ \text{km} cable can show a Ferranti rise like that of well over 100 km100\ \text{km} of overhead line, with far more charging current.

Practice

  1. Estimate the open-end rise of a 300 km300\ \text{km} overhead line at 60 Hz60\ \text{Hz} (wave speed 2.95×105 km/s2.95 \times 10^5\ \text{km/s}).
  2. A 220 kV220\ \text{kV} line draws 60 Mvar60\ \text{Mvar} of charging. What inductance per phase absorbs half of it at 50 Hz50\ \text{Hz}?
  3. Why does the loadability of a long line fall roughly as 1/ℓ1/\ell?
Answer
  1. βℓ=2π⋅60⋅300/295 000=0.383 rad\beta\ell = 2\pi \cdot 60 \cdot 300/295\,000 = 0.383\ \text{rad}; rise ≈0.3832/2=7.3 %\approx 0.383^2/2 = 7.3\ \% (exact 1/cos⁡0.383−1=7.8 %1/\cos 0.383 - 1 = 7.8\ \%).
  2. X=2202/30=1613 ΩX = 220^2/30 = 1613\ \Omega; L=1613/314.16=5.14 HL = 1613/314.16 = 5.14\ \text{H}.
  3. The stability limit is V2/∣B∣V^2/\lvert B \rvert and ∣B∣≈Xℓ\lvert B \rvert \approx X\ell for moderate lengths, so it falls as 1/ℓ1/\ell (and faster as sin⁡βℓ\sin\beta\ell grows).

Test yourself

The Ferranti rise of an open-circuited line grows with length roughly as…

  1. ℓ\ell
  2. ℓ2\ell^2
  3. ℓ\sqrt{\ell}
  4. it does not depend on length

Which device limits the Ferranti rise on a lightly loaded EHV line?

  1. shunt capacitor
  2. shunt reactor
  3. series capacitor
  4. surge arrester

What usually limits the power of a 600 km line?

  1. conductor temperature
  2. steady-state stability (angle)
  3. corona
  4. the CTs

With 400 kV at the sending end and ∣A∣=0.91\lvert A \rvert = 0.91, the open-end voltage is about…

  1. 364 kV
  2. 400 kV
  3. 440 kV
  4. 480 kV