Wind Turbines and Power Curves
A wind turbine is called "4 MW", but over a year it delivers on average perhaps to , and at any moment anything from zero to its rating, depending on the wind. To plan a grid with wind farms an engineer needs three things: how power depends on wind speed (the power curve), how often each wind speed occurs (the wind distribution), and how the turbine's generator and converter behave electrically. This lesson builds all three from first principles and turns them into an annual energy estimate.
Safety: wind turbines are tall machines with large stored rotational energy and medium-voltage electrics; this lesson is calculation and simulation only. The bench analogue uses a small DC fan motor in front of a desk fan.
Power in the wind
Air of density moving at speed through an area carries kinetic energy at the rate . A rotor can only capture a fraction of it, the power coefficient:
The Betz limit follows from momentum: a rotor that stopped the air completely would block the flow, one that let it through unslowed would extract nothing; the optimum slows the wind to one third of its upstream speed far behind the rotor. Large modern rotors reach to at their best operating point.
Three consequences dominate wind engineering:
- The cube. Twice the wind speed gives eight times the power, so a site with more mean wind gives roughly to more energy. Turbines are put on hills, out at sea and on tall towers (wind speed grows with height).
- The area. Power grows with the rotor diameter squared, which is why rotors have grown past onshore and to to offshore, with prototypes larger still (mid-2020s figures).
- The tip-speed ratio sets . Each rotor has an optimum (often around to ), so in light winds the controller varies the rotor speed to stay at it.
The power curve
A real turbine follows four regions:
| Region | Wind speed (typical) | What the control does |
|---|---|---|
| below cut-in | parked or idling, no output | |
| partial load | to about | variable speed at optimum , near its maximum: |
| full load | rated to | blades pitched to spill power, output held at rating |
| above cut-out | shut down and feathered to protect the structure (many newer turbines ramp down gradually instead) |
The numbers vary by model; the manufacturer publishes a measured power curve to IEC 61400-12-1 (power performance measurements; edition 3.0, 2022, current as of 2026).
Wind distribution and annual energy
Wind speeds at a site follow, approximately, a Weibull distribution; with shape parameter it is the Rayleigh distribution, fixed by the mean speed alone:
The capacity factor is . Onshore wind farms typically achieve about to and offshore farms to (2020s fleet averages; individual sites vary widely). Wake losses inside a farm, availability and electrical losses take a further to off a single-turbine estimate.
Worked example: a 4 MW turbine
Given: rotor diameter , , in partial load, rated power , cut-in , cut-out ; a site with a Rayleigh distribution and mean wind at hub height.
Find: the power at , the rated wind speed, the mean power, the AEP and the capacity factor.
Solve:
The mean power needs the integral, done numerically below: , , .
Check: the Betz limit would give at , so is of the theoretical maximum, plausible. A capacity factor of is high for onshore: this simple model holds constant right up to rating and ignores wake and electrical losses, so treat it as an upper bound.
In Python: power curve, distribution and AEP
import numpy as np
import matplotlib.pyplot as plt
rho, D, Cp, Prated = 1.225, 130.0, 0.45, 4e6
A = np.pi * D**2 / 4
v_in, v_out = 3.0, 25.0
def power(v):
p = np.minimum(0.5 * rho * A * v**3 * Cp, Prated)
return np.where((v < v_in) | (v > v_out), 0.0, p)
def rayleigh(v, vmean):
return np.pi * v / (2 * vmean**2) * np.exp(-np.pi / 4 * (v / vmean)**2)
v = np.linspace(0, 30, 3001)
print(f"A = {A:.0f} m2, P(10 m/s) = {float(power(np.array(10.0)))/1e6:.2f} MW,"
f" Betz limit at 10 m/s = {0.5*rho*A*1000*16/27/1e6:.2f} MW")
print(f"rated wind speed = {(Prated / (0.5*rho*A*Cp))**(1/3):.1f} m/s")
for vm in (6.0, 7.5, 9.0):
Pbar = np.trapezoid(power(v) * rayleigh(v, vm), v)
print(f"mean wind {vm:.1f} m/s: mean power {Pbar/1e6:.2f} MW, AEP {Pbar*8760/1e9:5.1f} GWh, CF {100*Pbar/Prated:4.1f} %")
fig, ax = plt.subplots(figsize=(7, 3.5))
ax.plot(v, power(v) / 1e6, label="power curve (MW)")
ax.bar(np.arange(0.5, 30), [np.trapezoid(rayleigh(v[(v >= k) & (v <= k + 1)], 7.5), v[(v >= k) & (v <= k + 1)]) * 20 for k in range(30)],
width=0.9, alpha=0.3, label="hours share x 20 (mean 7.5 m/s)")
ax.set_xlabel("wind speed (m/s)"); ax.set_ylabel("MW"); ax.legend(); ax.grid(alpha=0.3)
fig.tight_layout()
plt.show()A = 13273 m2, P(10 m/s) = 3.66 MW, Betz limit at 10 m/s = 4.82 MW
rated wind speed = 10.3 m/s
mean wind 6.0 m/s: mean power 1.20 MW, AEP 10.5 GWh, CF 30.0 %
mean wind 7.5 m/s: mean power 1.77 MW, AEP 15.5 GWh, CF 44.3 %
mean wind 9.0 m/s: mean power 2.23 MW, AEP 19.5 GWh, CF 55.7 %
Raising the mean wind from to (25 % more) adds more energy; the power cap at rating keeps it from being the full cube.
The electrical side: four turbine types
| Type | Generator and converter | Grid behaviour |
|---|---|---|
| 1 | squirrel-cage induction generator, direct on line, fixed speed | absorbs reactive power, needs capacitors; speed fixed, so is optimal at one wind speed only |
| 2 | wound-rotor induction generator with variable rotor resistance | a few percent of speed range |
| 3 | doubly-fed induction generator (DFIG): stator on the grid, rotor fed by a converter rated about | variable speed (), reactive control; common in the 2000s and 2010s |
| 4 | synchronous (often permanent-magnet) or induction generator behind a full-power converter | any speed, full reactive control and fault ride-through; dominant in new large and offshore turbines |
Types 3 and 4 connect through power electronics (Power Electronics & Motor Drives), so the grid does not see the rotor's kinetic energy as natural inertia, and they give only a limited fault current set by the converter rating. Grid codes therefore demand fault ride-through, reactive current during faults and, increasingly, synthetic inertia and grid-forming control (Smart Grid and DER, Frequency Control).
Guided lab: a desk-fan "wind turbine"
Hand calculation. A desk fan blows air at perhaps through the of a small propeller: in the wind, and at (small rotors are poor) about .
Simulation. Change D, Cp, Prated, v_in and v_out in the program to the toy's values and plot its power curve.
What you would measure. A small DC motor with a propeller, loaded by a resistor (try to ), at several distances from the fan; an anemometer (or a phone app with an anemometer accessory) for wind speed; a DMM for voltage. Expect tens of milliwatts and a power that falls steeply with distance, roughly as the cube of the measured wind speed, with scatter from the turbulent fan flow. You will also find an optimum load resistance, the bench version of optimum tip-speed ratio.
Hazards and safe setup. Keep fingers clear of both propellers, use a fan with a guard, and keep the motor's output below (it is a few volts here).
Pitfalls
- Mean wind cubed is not mean power. (by a factor of about for a Rayleigh distribution), so use the distribution.
- Rated power is not typical power. Plan energy with the capacity factor, and firm capacity with even less.
- Hub height. Wind data measured at must be extrapolated to hub height (power law or log law), with large uncertainty.
- Air density. It falls with altitude and temperature; a site at has about less power at the same speed.
Practice
- What power is in a wind through a rotor (), and what could the Betz limit capture?
- A turbine produces in a year. What is its capacity factor?
- Why do pitch-regulated turbines keep output flat above rated speed rather than letting it rise?
Answer
- ; wind power ; Betz .
- .
- The generator, converter, gearbox and structure would otherwise have to be sized for winds that occur only a few hours a year; capping at rating gives the most energy per unit cost.
Test yourself
If the wind speed doubles (below rated), the power of a turbine…
- doubles
- quadruples
- rises 8 times
- stays the same
The Betz limit on the power coefficient is…
- 0.25
- 0.5
- 16/27, about 0.593
- 1
Which turbine type connects its generator to the grid only through a full-power converter?
- Type 1
- Type 2
- Type 3 (DFIG)
- Type 4
A 4 MW turbine has a mean output of 1.6 MW. Its capacity factor and annual energy are…
- 40 % and 14.0 GWh
- 40 % and 35 GWh
- 25 % and 14.0 GWh
- 60 % and 21 GWh