Most faults in low-voltage installations are earth faults: a damaged cable or a failed appliance connects a live conductor to a metal enclosure. Whether that enclosure becomes lethal, and for how long, depends on how the system is earthed. IEC 60364 classifies low-voltage earthing arrangements with two or three letters, and for each one prescribes how protection must disconnect a fault before the voltage on exposed metal can harm anyone. This lesson computes fault loops, touch voltages and disconnection conditions for LV board B1 and its final circuits.

Safety: this lesson is about installations at 230/400 V230/400\ \text{V}, which can kill. Everything here is calculation and simulation only. Earth-loop impedance and RCD testing on real installations is done by qualified electricians with rated test instruments. Step and touch voltages around substations are described as concepts; never approach a fallen conductor or a substation fence during a fault.

The letters

The first letter is the source's relation to earth: T (terre), one point (usually the star point) directly earthed; I, isolated from earth or earthed through a high impedance. The second letter is the installation's exposed conductive parts: T, connected to a local earth electrode independent of the source earth; N, connected to the source's earthed point through a protective conductor. Further letters for TN: S, separate neutral (N) and protective (PE) conductors; C, combined in one PEN conductor; C-S, combined in the supply and separated at the origin of the installation.

TN-C-STT L1L2L3PEN NPE load fault returns in PE (metal) N RB load RA fault returns via soil (RA + RB)
System Earth-fault current Protection that disconnects Typical use
TN-S, TN-C-S large (metal loop), hundreds of A to kA fuses and circuit breakers (overcurrent devices), RCDs as additional protection public supplies in much of Europe (TN-C-S, also called PME), industry
TN-C as TN-S overcurrent devices; RCDs cannot work on a PEN conductor fixed installations with large conductors only
TT small (through soil), a few A RCDs rural overhead supplies, France, many countries' houses
IT first fault: tiny (capacitive) insulation monitoring device alarms; second fault disconnected like TN or TT hospitals' operating theatres, mines, process plants needing continuity

Automatic disconnection: the conditions

IEC 60364-4-41:2005 with amendment 1 of 2017 requires, for TN systems, that the protective device disconnect within a maximum time, which holds if

Zs⋅Ia≤U0Z_s \cdot I_a \le U_0

where ZsZ_s is the earth-fault loop impedance (source, phase conductor up to the fault, protective conductor back to the source), IaI_a the current that makes the device operate within the required time, and U0U_0 the nominal line-to-earth voltage (230 V230\ \text{V}). Maximum disconnection times for final circuits up to 32 A32\ \text{A} at U0=230 VU_0 = 230\ \text{V}: 0.4 s0.4\ \text{s} in TN, 0.2 s0.2\ \text{s} in TT; distribution circuits: 5 s5\ \text{s} (TN) and 1 s1\ \text{s} (TT). For an MCB, IaI_a is the top of its instantaneous band (IEC 60898-1): type B 5In5 I_n, type C 10In10 I_n, type D 20In20 I_n.

For TT systems, with an RCD of rated residual current IΔnI_{\Delta n} and installation electrode plus protective-conductor resistance RAR_A:

RA⋅IΔn≤50 VR_A \cdot I_{\Delta n} \le 50\ \text{V}

50 V50\ \text{V} AC is the conventional touch-voltage limit for normal dry conditions. RCDs of 30 mA30\ \text{mA} are also required as additional protection for socket outlets and many final circuits in both TN and TT systems.

Worked example: a final circuit fed from B1

Given: B1 (TN-C-S, Dyn11 transformer). The phase-to-earth loop at the B1 busbar, from the symmetrical-component impedances (Unsymmetrical Faults), is Ze=∣2Z1+Z0∣/3=10.0 mΩZ_e = \lvert 2Z_1 + Z_0 \rvert/3 = 10.0\ \text{m}\Omega (the transformer's Z0≈Z1,tZ_0 \approx Z_{1,t}; the delta blocks the grid's zero sequence). Feeder to DB1: 100 m100\ \text{m}, 95 mm295\ \text{mm}^2 phase (0.193 Ω/km0.193\ \Omega/\text{km}), 50 mm250\ \text{mm}^2 PE (0.387 Ω/km0.387\ \Omega/\text{km}). Final circuit: 30 m30\ \text{m} of 2.5 mm22.5\ \text{mm}^2 phase (7.41 mΩ/m7.41\ \text{m}\Omega/\text{m}) with a 1.5 mm21.5\ \text{mm}^2 protective conductor (12.1 mΩ/m12.1\ \text{m}\Omega/\text{m}), protected by a type B 16 A16\ \text{A} MCB. Conductor resistances are multiplied by 1.21.2 for operating temperature (a common design allowance).

Find: ZsZ_s, the earth-fault current, whether the MCB disconnects in 0.4 s0.4\ \text{s}, and the prospective touch voltage on the faulty appliance.

Solve:

Rfeeder=1.2⋅0.1 km⋅(0.193+0.387) Ω/km=0.0696 ΩRfinal=1.2⋅30 m⋅(7.41+12.1) mΩ/m=0.702 ΩZs≈0.010+0.0696+0.702=0.782 ΩIf=230 V0.782 Ω=294 A ≥ Ia=5⋅16 A=80 AUt≈If RPE=294 A⋅1.2 (0.1⋅0.387+30⋅0.0121) Ω=142 V\begin{aligned} R_\text{feeder} &= 1.2 \cdot 0.1\ \text{km} \cdot (0.193 + 0.387)\ \Omega/\text{km} = 0.0696\ \Omega \\ R_\text{final} &= 1.2 \cdot 30\ \text{m} \cdot (7.41 + 12.1)\ \text{m}\Omega/\text{m} = 0.702\ \Omega \\ Z_s &\approx 0.010 + 0.0696 + 0.702 = 0.782\ \Omega \\ I_f &= \frac{230\ \text{V}}{0.782\ \Omega} = 294\ \text{A} \ \ge\ I_a = 5 \cdot 16\ \text{A} = 80\ \text{A} \\ U_t &\approx I_f\,R_{PE} = 294\ \text{A} \cdot 1.2\,(0.1 \cdot 0.387 + 30 \cdot 0.0121)\ \Omega = 142\ \text{V} \end{aligned}

Check: the condition holds with margin: Zs=0.78 ΩZ_s = 0.78\ \Omega against the maximum 230/80=2.875 Ω230/80 = 2.875\ \Omega for a B16. The same circuit with a C32 breaker would need Zs≤230/320=0.72 ΩZ_s \le 230/320 = 0.72\ \Omega and fails. The prospective touch voltage of 142 V142\ \text{V} is far above 50 V50\ \text{V}: it is the fast disconnection (an MCB's magnetic trip at 294 A294\ \text{A} acts in about 10 ms10\ \text{ms}), plus the main equipotential bonding that raises nearby metalwork to a similar potential, that keeps it from being dangerous. Adding the impedances arithmetically, as here, slightly overestimates ZsZ_s and is the conservative direction.

In Python: loop impedances for TN, TT and IT

python · try it yourself
import numpy as np

U0 = 230.0
k = 1.2                                     # operating-temperature factor
Z1 = complex(1.642, 10.106) * 1e-3          # B1 positive sequence at 400 V (Ohm)
Z0 = complex(1.578, 9.469) * 1e-3           # transformer zero sequence (Dyn: delta blocks the grid)
Ze = abs(2 * Z1 + Z0) / 3
R_feed = k * 0.1 * (0.193 + 0.387)
R_final = k * 30 * (7.41 + 12.1) * 1e-3
Zs = Ze + R_feed + R_final
If = U0 / Zs
print(f"TN: Ze = {Ze*1e3:.1f} mOhm, Zs = {Zs:.3f} Ohm, If = {If:.0f} A")
for mcb, Ia in [("B16", 80), ("C16", 160), ("B32", 160), ("C32", 320)]:
    print(f"  {mcb}: Zs max = {U0/Ia:.3f} Ohm ->", "OK" if Zs * Ia <= U0 else "FAILS")
Rpe = k * (0.1 * 0.387 + 30 * 12.1e-3)
print(f"  prospective touch voltage = {If * Rpe:.0f} V")

# TT: supply earth RB = 10 Ohm, installation electrode RA = 100 Ohm, phase conductor 0.5 Ohm
RA, RB = 100.0, 10.0
I_tt = U0 / (RA + RB + 0.5)
print(f"TT: If = {I_tt:.2f} A (an MCB never sees this), touch voltage = {I_tt * RA:.0f} V")
print(f"    30 mA RCD: RA x IdN = {RA * 0.030:.1f} V <= 50 V; RA may be up to {50 / 0.030:.0f} Ohm")

# IT: first fault, leakage capacitance 1 uF per phase to earth
C = 1e-6
I_it = 3 * 2 * np.pi * 50 * C * U0
print(f"IT: first-fault current = {I_it * 1e3:.0f} mA (capacitive), alarm only")
TN: Ze = 10.0 mOhm, Zs = 0.782 Ohm, If = 294 A
  B16: Zs max = 2.875 Ohm -> OK
  C16: Zs max = 1.438 Ohm -> OK
  B32: Zs max = 1.438 Ohm -> OK
  C32: Zs max = 0.719 Ohm -> FAILS
  prospective touch voltage = 142 V
TT: If = 2.08 A (an MCB never sees this), touch voltage = 208 V
    30 mA RCD: RA x IdN = 3.0 V <= 50 V; RA may be up to 1667 Ohm
IT: first-fault current = 217 mA (capacitive), alarm only

The TT result explains why TT installations rely on RCDs: 2 A2\ \text{A} will never trip a 16 A16\ \text{A} breaker, while the enclosure sits at about 208 V208\ \text{V} until the RCD opens (within 40 ms40\ \text{ms} at 5IΔn5 I_{\Delta n} for a general-type RCD). In IT the first fault draws only the charging current of the healthy phases (3ωCU03\omega C U_0), so the system keeps running; the insulation monitor must be acted on before a second fault on another phase creates a line-to-line short through two enclosures.

Interactive: the TT fault loop

Simulation only. A 230 V230\ \text{V} source with its star point earthed through RB =10 Ω= 10\ \Omega, a 0.5 Ω0.5\ \Omega phase conductor, a solid fault to the enclosure, and the installation electrode RA to true earth (node 0). Node e is the enclosure's voltage to remote earth, the prospective touch voltage. At RA=100 ΩR_A = 100\ \Omega the lab shows 2.08 A2.08\ \text{A} and 208 V208\ \text{V}; slide RAR_A down to 5 Ω5\ \Omega and the touch voltage falls to about 74 V74\ \text{V} while the current rises to 14.8 A14.8\ \text{A}: still not enough to trip an MCB quickly, so even a good electrode does not replace the RCD.

node voltages (to ground 0)l209.2 Vn-20.81 Vc208.1 Ve208.1 VnetlistV1 l n 230RB n 0 10RL l c 0.5RF c e 0.01RA e 0 100element currents (node 1 to node 2 through it)V1l>n-2.08 ARBn>0-2.08 ARLl>c2.08 ARFc>e2.08 ARAe>02.08 A

Step and touch voltage near substations (concepts)

When a fault current flows into a substation's earth grid, the grid rises above remote earth (the earth potential rise, EPR), and the soil surface around it carries a potential gradient. A person touching a structure while standing a metre away bridges part of that gradient (touch voltage); a person walking bridges the gradient between their feet (step voltage). Substation earthing (designed to IEEE 80-2013, still the reference although IEEE lists it as inactive-reserved since 2024 while a revision is prepared, or to EN 50522) keeps these within body-current limits that depend on fault duration, using a meshed grid, a gravel surface layer and fast clearance. This is design-office work with soil-resistivity surveys; nobody tests it by touching anything.

Guided lab: an electrode-resistance model

Hand calculation. A single vertical rod of length LL and diameter dd in uniform soil of resistivity ρ\rho has R≈ρ2πL[ln⁡8Ld−1]R \approx \frac{\rho}{2\pi L}\left[\ln\frac{8L}{d} - 1\right]. For ρ=100 Ω⋅m\rho = 100\ \Omega \cdot \text{m}, L=2.4 mL = 2.4\ \text{m}, d=16 mmd = 16\ \text{mm}: R≈6.63⋅(7.09−1)=40.4 ΩR \approx 6.63 \cdot (7.09 - 1) = 40.4\ \Omega.

Simulation. Change RA in the lab to your result and read the touch voltage and fault current.

What you would measure. On a small scale, in a plastic tray of damp sand, push two short stainless rods and an auxiliary probe and drive a function generator at 1 kHz1\ \text{kHz}, 5 V5\ \text{V} through a 1 kΩ1\ \text{k}\Omega series resistor; measure the voltage between rod and probe as you move the probe away (the "fall-of-potential" method that earth testers use with an injected AC test current). Expect the reading to level off at about 60 %60\ \% of the rod-to-current-electrode distance, and resistances of hundreds of ohms to kilohms that vary ±20 %\pm 20\ \% with moisture.

Hazards and safe setup. Function generator only, ≤5 V\le 5\ \text{V}; never use a real installation's earth or a mains-powered earth tester for this; wash hands after handling sand and metal.

Pitfalls

  • RCDs on a PEN conductor. In TN-C the neutral and protective currents share one conductor, so an RCD cannot see the fault.
  • Broken PEN in TN-C-S. Loss of the combined conductor raises every bonded part toward line voltage; supply rules require multiple earthing of the PEN and bonding.
  • Using cold resistances for the minimum fault current gives too optimistic a ZsZ_s.
  • Ignoring the second fault in IT. It behaves like a TN or TT fault and needs its own disconnection check.

Practice

  1. What maximum ZsZ_s does a type C 20 A20\ \text{A} MCB need in a 230 V230\ \text{V} TN system?
  2. A TT installation has RA=200 ΩR_A = 200\ \Omega. Which RCD sensitivities satisfy the 50 V50\ \text{V} condition: 30 mA30\ \text{mA}, 100 mA100\ \text{mA}, 300 mA300\ \text{mA}?
  3. Why is an IT system allowed to keep running after the first earth fault?
Answer
  1. Ia=10⋅20=200 AI_a = 10 \cdot 20 = 200\ \text{A}; Zs≤230/200=1.15 ΩZ_s \le 230/200 = 1.15\ \Omega.
  2. 200⋅0.03=6 V200 \cdot 0.03 = 6\ \text{V} and 200⋅0.1=20 V200 \cdot 0.1 = 20\ \text{V} pass; 200⋅0.3=60 V200 \cdot 0.3 = 60\ \text{V} fails.
  3. With the source isolated from earth, the only return path is the small leakage capacitance, so the fault current and touch voltage are tiny. The fault must be found and removed before a second one appears.

Test yourself

In the code TN-C-S, what does "C-S" mean?

  1. capacitive and series earthing
  2. neutral and protective functions combined (PEN) in the supply, separate in the installation
  3. copper and steel conductors
  4. earthed at the consumer only

A 230 V TN final circuit of 16 A must disconnect an earth fault within…

  1. 0.04 s
  2. 0.2 s
  3. 0.4 s
  4. 5 s

Why do TT installations depend on RCDs?

  1. their fault currents are too small to operate overcurrent devices quickly
  2. RCDs are cheaper than MCBs
  3. TT has no neutral
  4. the electrode resistance is zero

For a type B 16 A MCB in a 230 V TN system, the maximum earth-fault loop impedance is about…

  1. 0.72 Ω0.72\ \Omega
  2. 1.44 Ω1.44\ \Omega
  3. 2.88 Ω2.88\ \Omega
  4. 14.4 Ω14.4\ \Omega