Complex Power Flow and Power-Factor Correction at System Scale
A factory takes at with a power factor of . Its supplier bills reactive energy above a threshold, its incoming cable runs warm, and the voltage at its busbar sags whenever the big compressors start. A capacitor bank of about fixes all three. This lesson sizes that bank and shows what it does to the current, the voltage, the losses and, if you are careless, the harmonics. Complex power , the power triangle and correction of a single load are in Complex Power, Power Factor and Correction; here they are applied to a supply network.
Safety: medium-voltage capacitor banks store lethal energy and stay charged after disconnection (they have discharge resistors that take minutes). This lesson is calculation and simulation only.
Conservation of complex power
In any network, the complex power delivered by the sources equals the sum of the complex powers absorbed by all elements (Tellegen's theorem). For each element:
| Element | ||
|---|---|---|
| resistor | ||
| inductor | (absorbs) | |
| capacitor | (supplies) | |
| induction motor, transformer magnetising | load | absorbs |
| over-excited synchronous machine | either | supplies |
So reactive power can be "booked" like real power: a bus whose loads absorb and whose capacitor supplies imports only the difference, (the factory below, with its bank in service). The supply network itself absorbs in its reactance, which grows with the square of the current: reactive power does not travel well, and the best place to produce it is close to where it is used.
Why correct the power factor
For the same real power, a lower pf means more current: . More current means
- losses in every cable and transformer upstream, which scale as ;
- capacity used up: a transformer or cable is rated in kVA or amperes, not in kW;
- voltage drop ; in networks where , reactive power dominates the drop;
- charges: many tariffs bill reactive energy (kvarh) beyond a limit, often set somewhere between pf and (tariff details vary by country and change; check the current rules).
The bank size for a target power factor follows from the power triangle:
Installing it raises the bus voltage by roughly , where is the short-circuit power (fault level) at the bus, a handy rule because the fault level is the one number every network operator can give you.
Worked example: the factory bank
Given: a factory at an bus, , pf lagging; the supply has a three-phase fault level of at the bus (treat it as a pure reactance behind ). Target pf . (Calculation only.)
Find: the bank rating, its capacitance, the current and voltage before and after, and the parallel-resonance harmonic order.
Solve:
Modelling the factory as a constant impedance (the R and L that draw at ), the program below finds the line current falling from to and the bus voltage rising from to ; the pf seen from the supply rises to .
Check: the voltage rise is , matching . Upstream losses scale with : , a reduction. The resonance check is the warning: with the bank in service, the supply inductance and the capacitors resonate near the 8.7th harmonic, between the 7th and the 11th that rectifier loads produce. Practical banks with harmonic-producing loads nearby are detuned: a series reactor (for example of the capacitor reactance) moves the resonance down to about , below the 5th harmonic (Power Quality).
In Python: sizing and checking the bank
import numpy as np
w, VL, Ssc = 2 * np.pi * 50, 11e3, 150e6
P, pf1, pf2 = 4e6, 0.78, 0.95
Q1, Q2 = P * np.tan(np.arccos(pf1)), P * np.tan(np.arccos(pf2))
print(f"Q1 = {Q1/1e6:.3f} Mvar, Q2 = {Q2/1e6:.3f} Mvar, needed Qc = {(Q1 - Q2)/1e6:.3f} Mvar")
Qc = 2.0e6 # next standard size: 4 x 0.5 Mvar
C = Qc / (w * VL**2)
print(f"bank {Qc/1e6:.1f} Mvar -> C = {C*1e6:.1f} uF per phase (star)")
# per-phase circuit: source behind Xs, factory as constant R || jX, bank in parallel
V = VL / np.sqrt(3)
Xs = VL**2 / Ssc
R, X = V**2 / (P / 3), V**2 / (Q1 / 3)
for label, Cb in (("without bank", 0.0), ("with bank", C)):
Yload = 1 / R + 1 / (1j * X) + 1j * w * Cb
I = V / (1j * Xs + 1 / Yload)
Vb = I / Yload
S = 3 * Vb * np.conj(I)
print(f"{label:12s}: I = {abs(I):6.1f} A, V_bus = {abs(Vb)*np.sqrt(3)/1e3:6.3f} kV,"
f" P = {S.real/1e6:.3f} MW, Q = {S.imag/1e6:.3f} Mvar, pf = {S.real/abs(S):.3f}")
print(f"voltage-rise rule Qc/Ssc = {100*Qc/Ssc:.2f} %")
print(f"parallel resonance at harmonic {np.sqrt(Ssc/Qc):.2f} ({50*np.sqrt(Ssc/Qc):.0f} Hz)")
print(f"detuned with a 7 % reactor: series resonance at harmonic {1/np.sqrt(0.07):.2f}")Q1 = 3.209 Mvar, Q2 = 1.315 Mvar, needed Qc = 1.894 Mvar
bank 2.0 Mvar -> C = 52.6 uF per phase (star)
without bank: I = 263.4 A, V_bus = 10.766 kV, P = 3.832 MW, Q = 3.074 Mvar, pf = 0.780
with bank : I = 217.5 A, V_bus = 10.908 kV, P = 3.934 MW, Q = 1.189 Mvar, pf = 0.957
voltage-rise rule Qc/Ssc = 1.33 %
parallel resonance at harmonic 8.66 (433 Hz)
detuned with a 7 % reactor: series resonance at harmonic 3.78
A constant-impedance load takes less than its nominal when the voltage sags, so the "without bank" power is ; with the bank the voltage recovers and so does the power. Real loads lie between constant impedance and constant power (motors hold their power), which is why load models matter in Voltage Stability.
Interactive: switch the bank in
The netlist lab is the per-phase circuit: behind the supply inductance ( is ), the factory as in parallel with , and the bank C1. Its plot sweeps frequency; read the values at the cursor. With C1 at (practically no bank) it shows the supply current I(LS) at and the bus b at ( line). Slide C1 to and the current falls to and the bus rises to . Keep going: the current reaches its minimum, about , near (unity pf at the supply), and beyond that the factory over-compensates. At the current leads (, larger again), the bus climbs to , and the factory exports reactive power. On the frequency plot, notice the bus-voltage peak that moves down in frequency as C1 grows: that is the parallel resonance.
Guided lab: power-factor correction at signal level
Hand calculation. A function generator at rms, drives a resistor in parallel with a inductor (or, more practically at this frequency, scale everything to : in parallel with ). Compute the pf and the capacitor for unity pf: .
Simulation. Reproduce the circuit in the netlist lab (change the values) and sweep the capacitor.
What you would measure. With a sense resistor in the supply lead and a two-channel oscilloscope (a common ground at the generator, so both channels are referenced correctly), measure the phase between voltage and current and the supply-current amplitude. Expect the current to fall to the resistor's at the optimal capacitor, within the components' tolerances ( to for typical capacitors and inductors, so the minimum may be at a capacitor value off the calculated one).
Hazards and safe setup. Function generator only. Do not use a mains-frequency power transformer to get "more volts".
Pitfalls
- Sizing on the wrong voltage. : a bank rated at gives only at and at .
- Over-compensation at light load. A fixed bank sized for full load drives the pf leading and the voltage up at night; use automatic stepped banks.
- Ignoring resonance. Check against the harmonics present; detune where needed.
- Switching transients. Energising a bank draws a large inrush, especially back-to-back with another energised bank; banks use current-limiting reactors or controlled switching.
Practice
- A transformer supplies at pf . Is it overloaded? What bank brings the pf to , and what is the transformer loading then?
- Where does a bus with a fault level of and a bank resonate?
- Why does cause most of the voltage drop on a transmission line but less on a low-voltage cable?
Answer
- : , overloaded. ; then , .
- : right on the 5th harmonic, a bad choice without detuning.
- . Overhead lines have of about to or more, so dominates; LV cables have well below 1, so dominates.
Test yourself
A load of 1 MW at pf 0.8 lagging is corrected to unity pf. The capacitor bank supplies…
- 0.6 Mvar
- 0.75 Mvar
- 0.8 Mvar
- 1.25 Mvar
Installing a 3 Mvar bank on a bus with a 200 MVA fault level raises its voltage by about…
- 0.15 %
- 1.5 %
- 6.7 %
- 15 %
Raising a load's power factor from 0.7 to 1.0 at the same real power reduces upstream losses to…
- 70 %
- 49 %
- 30 %
- 100 %
Why are capacitor banks near rectifier loads often fitted with series reactors?
- to raise their kvar
- to detune the resonance below the 5th harmonic
- to limit the 50 Hz current to zero
- to make the pf leading