Power Systems Exercises
These problems follow the course in order. Work each one by hand first, with units on every quantity, then open the answer. Each section links back to the lessons it draws on. The last section checks several answers in Python. Every system here is at mains or grid voltage, so every problem is a calculation, never a measurement to try.
Unless a problem says otherwise: , system base , low voltage.
Three-phase systems and per unit
Lessons: Balanced Three-Phase, Unbalanced Loads, Power-Factor Correction, Per Unit for Networks.
- A balanced delta load of per phase is fed from a board through a cable of per phase. Find the line current, the line voltage at the load and the load's real power.
- A balanced load measured by two wattmeters reads and . Find , the power factor and .
- A load at pf lagging is corrected to . What bank is needed, and how much does it raise the voltage of a bus with a fault level?
- Express a , transformer with on the base.
- With the neutral of an unbalanced star load broken, which load gets the highest voltage, and why is that dangerous?
Answers 1 to 5
- Star equivalent ; ; load line voltage ; .
- ; , pf ; .
- ; voltage rise .
- .
- The most lightly loaded phase (largest impedance): the floating star point moves toward the heavily loaded phase, so the light load sees up to nearly the line voltage, overvolting and damaging appliances.
Generation
Lessons: Thermal, Hydro and Nuclear, Generators on the Grid, Wind Power, Solar PV, Storage and LCOE.
- A wind turbine with a rotor works at in a wind (). What power does it produce?
- A module has at STC and a coefficient of . How many fit in a string for a inverter if the coldest cell temperature is ?
- Find the LCOE of a plant with CAPEX per kW, O&M per kW-year, capacity factor , life 25 years, discount rate , no fuel.
- A generator on an infinite bus has , total reactance , . What is its steady-state power limit, and its angle at ?
Answers 6 to 9
- ; .
- ; , so modules.
- ; per MWh.
- ; .
Transmission lines
Lessons: Resistance and Inductance, Capacitance and Cables, Short and Medium Lines, Long Lines, Ferranti Effect and Loadability.
- Conductors at the corners of an equilateral triangle of side have a GMR of . Find and per km.
- Estimate the no-load Ferranti rise of a overhead line (wave speed ).
- A line has . Find its SIL. Below SIL, does it supply or absorb reactive power?
- Why does a cable need the model at lengths where an overhead line can use the short-line model?
Answers 10 to 13
- ; .
- ; rise .
- ; below SIL it supplies (generates) reactive power.
- A cable's shunt capacitance is to times larger, so its charging current is significant even over a few kilometres.
Reactive power, load flow and dispatch
Lessons: Reactive Power and Voltage, Voltage Control, Bus Types and Y-Bus, Gauss–Seidel, Newton–Raphson, DC Load Flow, Economic Dispatch, Unit Commitment.
- Two buses at joined by transfer . What is the angle between them?
- Build the Y-bus of three buses joined in a triangle by lines of , and (1–2, 1–3, 2–3), ignoring resistance and charging.
- In that network, bus 1 is the slack, bus 2 injects and bus 3 draws . Solve the DC load flow for the angles and the line flows.
- Two units have incremental costs and (per MWh, P in MW). Dispatch without losses.
- Which bus types does a load flow have, and which two quantities are given at each?
Answers 14 to 18
- , .
- pu (diagonal = sum of the connected susceptances, off-diagonal = minus the branch susceptance).
- With : gives , ; flows , , . Check: bus 3 receives , and the slack supplies .
- per MWh: , .
- Slack (, ), PV or generator (, ), PQ or load (, ).
Faults
Lessons: Symmetrical Faults, Fault Levels and Breaker Duty, Symmetrical Components, Sequence Networks, Unsymmetrical Faults.
- A generator () feeds a step-up transformer (), both on . Find the three-phase fault current at the terminals in pu, kA and MVA (prefault voltage ).
- At a bus with and , compare the bolted single-line-to-ground and three-phase fault currents.
- Why is the first peak of a fault current larger than times its symmetrical rms value, and on what does the extra depend?
- Find the symmetrical components of , , .
Answers 19 to 22
- ; , so ; .
- SLG: ; three-phase: . The earth fault is larger because .
- The DC offset: a fault starting near a voltage zero in an inductive circuit needs a decaying DC component so that the current starts from its prefault value. Its size depends on the switching instant and its decay on ( in IEC 60909-0:2016).
- .
Protection
Lessons: Protection Principles, Overcurrent and IDMT, Coordination and Grading, Distance Protection, Differential Protection, Earthing Systems, Surges, Insulation and Arc Flash.
- An IEC standard-inverse relay (IEC 60255-151) has a pickup of and TMS . How fast does it operate at ?
- A downstream relay operates in at the maximum fault current. With a grading margin of , what operating time must the upstream relay have at that current?
- In a TN system ( to earth) a final circuit has a fault-loop impedance of . What is the earth-fault current, and does a type B circuit breaker (instantaneous trip at 3 to 5 times rated current) disconnect in time?
- A distance relay's zone 1 is set to of the protected line. Why not ?
Answers 23 to 26
- .
- .
- , above , so the breaker trips instantaneously, well within .
- CT and VT errors, line-impedance data and the fault resistance make the measured impedance uncertain by several percent; a reach could overreach into the next line and trip for faults there. The last is covered by zone 2 with a delay (or by a communication scheme).
Stability, distribution, power quality and the modern grid
Lessons: Swing Equation, Equal-Area Criterion, Frequency Control, Voltage Stability, Distribution Systems, Power Quality, HVDC and FACTS, Smart Grid and DER.
- A generator delivers with before and after a fault; during the fault it delivers nothing. With , find the critical clearing angle and time.
- A system with (on the online capacity) loses . What is the initial rate of change of frequency?
- An feeder of carries . Estimate the voltage drop in percent.
- A current has harmonics of , , and of the fundamental. What is its THD?
- Name two reasons why a submarine link is built as HVDC.
Answers 27 to 31
- , ; gives ; .
- .
- , .
- .
- An AC cable of that length would need more charging current than its rating; DC has no charging current in steady state and lower losses over long distances; HVDC can also link asynchronous grids and controls the power flow precisely.
Checking answers in Python
import numpy as np
# 16: DC load flow of the triangle network
B = np.array([[14.0, -4.0], [-4.0, 9.0]])
th2, th3 = np.linalg.solve(B, [0.5, -1.0])
print(f"16: theta2 = {th2:.4f}, theta3 = {th3:.4f} rad; P12 = {(0 - th2)/0.1:.3f}, P13 = {(0 - th3)/0.2:.3f}, P23 = {(th2 - th3)/0.25:.3f} pu")
# 17: equal incremental cost
lam = (600 + 8 / 0.008 + 7 / 0.012) / (1 / 0.008 + 1 / 0.012)
print(f"17: lambda = {lam:.2f}, P1 = {(lam - 8)/0.008:.0f} MW, P2 = {(lam - 7)/0.012:.0f} MW")
# 22: symmetrical components
a = np.exp(2j * np.pi / 3)
A = np.array([[1, 1, 1], [1, a, a**2], [1, a**2, a]]) / 3
print("22: I0, I1, I2 =", np.round(np.abs(A @ np.array([10, 0, 0])), 3))
# 23: IEC standard inverse
print(f"23: t = {0.1 * 0.14 / (10**0.02 - 1):.3f} s")
# 27: critical clearing angle and time
Pm, Pmax, H, f = 0.8, 2.0, 5.0, 50.0
d0 = np.arcsin(Pm / Pmax); dmax = np.pi - d0
dcr = np.arccos((Pm * (dmax - d0) + Pmax * np.cos(dmax)) / Pmax)
tcr = np.sqrt(4 * H * (dcr - d0) / (2 * np.pi * f * Pm))
print(f"27: delta0 = {np.degrees(d0):.2f} deg, delta_cr = {np.degrees(dcr):.1f} deg, t_cr = {tcr:.3f} s")
# 30: THD
print(f"30: THD = {100 * np.sqrt(np.sum(np.array([0.20, 0.12, 0.07, 0.05])**2)):.1f} %")16: theta2 = 0.0045, theta3 = -0.1091 rad; P12 = -0.045, P13 = 0.545, P23 = 0.455 pu
17: lambda = 10.48, P1 = 310 MW, P2 = 290 MW
22: I0, I1, I2 = [3.333 3.333 3.333]
23: t = 0.297 s
27: delta0 = 23.58 deg, delta_cr = 89.4 deg, t_cr = 0.302 s
30: THD = 24.9 %
Test yourself
A balanced load gives two-wattmeter readings of 6 kW and 6 kW. Its power factor is…
- 0.5
- 0.866
- 1
- 0
In a DC load flow, the flow on a line is…
Which fault usually gives the largest current near a solidly earthed transformer?
- three-phase
- line-to-line
- single line-to-ground (when )
- open conductor
Doubling a system's inertia H for the same loss of generation changes the initial RoCoF by a factor of…
- 2
- 1/2
- 4
- 1