Power Systems Exercises

These problems follow the course in order. Work each one by hand first, with units on every quantity, then open the answer. Each section links back to the lessons it draws on. The last section checks several answers in Python. Every system here is at mains or grid voltage, so every problem is a calculation, never a measurement to try.

Unless a problem says otherwise: 50 Hz50\ \text{Hz}, system base 100 MVA100\ \text{MVA}, 230/400 V230/400\ \text{V} low voltage.

Three-phase systems and per unit

Lessons: Balanced Three-Phase, Unbalanced Loads, Power-Factor Correction, Per Unit for Networks.

  1. A balanced delta load of 24+j18 Ω24 + j18\ \Omega per phase is fed from a 400 V400\ \text{V} board through a cable of 0.1+j0.1 Ω0.1 + j0.1\ \Omega per phase. Find the line current, the line voltage at the load and the load's real power.
  2. A balanced load measured by two wattmeters reads 8 kW8\ \text{kW} and 3 kW3\ \text{kW}. Find PP, the power factor and QQ.
  3. A 1.5 MW1.5\ \text{MW} load at pf 0.750.75 lagging is corrected to 0.950.95. What bank is needed, and how much does it raise the voltage of a bus with a 50 MVA50\ \text{MVA} fault level?
  4. Express a 40 MVA40\ \text{MVA}, 132/33 kV132/33\ \text{kV} transformer with x=8 %x = 8\ \% on the 100 MVA100\ \text{MVA} base.
  5. With the neutral of an unbalanced star load broken, which load gets the highest voltage, and why is that dangerous?
Answers 1 to 5
  1. Star equivalent 8+j6 Ω8 + j6\ \Omega; I=230.9/∣8.1+j6.1∣=22.78 AI = 230.9/\lvert 8.1 + j6.1 \rvert = 22.78\ \text{A}; load line voltage 3⋅22.78⋅10=394.5 V\sqrt{3} \cdot 22.78 \cdot 10 = 394.5\ \text{V}; P=3⋅22.782⋅8=12.45 kWP = 3 \cdot 22.78^2 \cdot 8 = 12.45\ \text{kW}.
  2. P=11 kWP = 11\ \text{kW}; tan⁡ϕ=3⋅5/11=0.787\tan\phi = \sqrt{3} \cdot 5/11 = 0.787, pf =0.786= 0.786; Q=3(W1−W2)=8.66 kvarQ = \sqrt{3}(W_1 - W_2) = 8.66\ \text{kvar}.
  3. QC=1.5(tan⁡41.41∘−tan⁡18.19∘)=0.830 MvarQ_C = 1.5(\tan 41.41^\circ - \tan 18.19^\circ) = 0.830\ \text{Mvar}; voltage rise ≈0.83/50=1.7 %\approx 0.83/50 = 1.7\ \%.
  4. 0.08⋅100/40=0.20 pu0.08 \cdot 100/40 = 0.20\ \text{pu}.
  5. The most lightly loaded phase (largest impedance): the floating star point moves toward the heavily loaded phase, so the light load sees up to nearly the line voltage, overvolting and damaging appliances.

Generation

Lessons: Thermal, Hydro and Nuclear, Generators on the Grid, Wind Power, Solar PV, Storage and LCOE.

  1. A wind turbine with a 120 m120\ \text{m} rotor works at Cp=0.42C_p = 0.42 in a 9 m/s9\ \text{m/s} wind (ρ=1.225 kg/m3\rho = 1.225\ \text{kg/m}^3). What power does it produce?
  2. A module has Voc=45 VV_\text{oc} = 45\ \text{V} at STC and a coefficient of −0.30 %/K-0.30\ \%/\text{K}. How many fit in a string for a 1000 V1000\ \text{V} inverter if the coldest cell temperature is −10 ∘C-10\,^\circ\text{C}?
  3. Find the LCOE of a plant with CAPEX 10001000 per kW, O&M 2020 per kW-year, capacity factor 20 %20\ \%, life 25 years, discount rate 6 %6\ \%, no fuel.
  4. A generator on an infinite bus has E=1.5 puE = 1.5\ \text{pu}, total reactance 1.2 pu1.2\ \text{pu}, V=1.0 puV = 1.0\ \text{pu}. What is its steady-state power limit, and its angle at 0.8 pu0.8\ \text{pu}?
Answers 6 to 9
  1. A=π⋅602=11 310 m2A = \pi \cdot 60^2 = 11\,310\ \text{m}^2; P=12⋅1.225⋅11 310⋅729⋅0.42=2.12 MWP = \tfrac{1}{2} \cdot 1.225 \cdot 11\,310 \cdot 729 \cdot 0.42 = 2.12\ \text{MW}.
  2. Voc=45(1+0.003⋅35)=49.7 VV_\text{oc} = 45(1 + 0.003 \cdot 35) = 49.7\ \text{V}; 1000/49.7=20.11000/49.7 = 20.1, so 2020 modules.
  3. CRF=0.0782\text{CRF} = 0.0782; LCOE=(1 000 000⋅0.0782+20 000)/(8760⋅0.2)=56.1\text{LCOE} = (1\,000\,000 \cdot 0.0782 + 20\,000)/(8760 \cdot 0.2) = 56.1 per MWh.
  4. Pmax=1.5/1.2=1.25 puP_\text{max} = 1.5/1.2 = 1.25\ \text{pu}; δ=arcsin⁡(0.8/1.25)=39.8∘\delta = \arcsin(0.8/1.25) = 39.8^\circ.

Transmission lines

Lessons: Resistance and Inductance, Capacitance and Cables, Short and Medium Lines, Long Lines, Ferranti Effect and Loadability.

  1. Conductors at the corners of an equilateral triangle of side 5 m5\ \text{m} have a GMR of 9 mm9\ \text{mm}. Find LL and XX per km.
  2. Estimate the no-load Ferranti rise of a 200 km200\ \text{km} overhead line (wave speed 2.95×105 km/s2.95 \times 10^5\ \text{km/s}).
  3. A 220 kV220\ \text{kV} line has Zc=380 ΩZ_c = 380\ \Omega. Find its SIL. Below SIL, does it supply or absorb reactive power?
  4. Why does a cable need the π\pi model at lengths where an overhead line can use the short-line model?
Answers 10 to 13
  1. L=2×10−7ln⁡(5/0.009)=1.264 mH/kmL = 2 \times 10^{-7}\ln(5/0.009) = 1.264\ \text{mH/km}; X=0.397 Ω/kmX = 0.397\ \Omega/\text{km}.
  2. βℓ=2π⋅50⋅200/295 000=0.213 rad\beta\ell = 2\pi \cdot 50 \cdot 200/295\,000 = 0.213\ \text{rad}; rise ≈0.2132/2=2.3 %\approx 0.213^2/2 = 2.3\ \%.
  3. 2202/380=127 MW220^2/380 = 127\ \text{MW}; below SIL it supplies (generates) reactive power.
  4. A cable's shunt capacitance is 1515 to 3030 times larger, so its charging current is significant even over a few kilometres.

Reactive power, load flow and dispatch

Lessons: Reactive Power and Voltage, Voltage Control, Bus Types and Y-Bus, Gauss–Seidel, Newton–Raphson, DC Load Flow, Economic Dispatch, Unit Commitment.

  1. Two buses at 1.0 pu1.0\ \text{pu} joined by X=0.25 puX = 0.25\ \text{pu} transfer 1.0 pu1.0\ \text{pu}. What is the angle between them?
  2. Build the Y-bus of three buses joined in a triangle by lines of x=0.1x = 0.1, 0.20.2 and 0.25 pu0.25\ \text{pu} (1–2, 1–3, 2–3), ignoring resistance and charging.
  3. In that network, bus 1 is the slack, bus 2 injects 0.5 pu0.5\ \text{pu} and bus 3 draws 1.0 pu1.0\ \text{pu}. Solve the DC load flow for the angles and the line flows.
  4. Two units have incremental costs 8+0.008P18 + 0.008P_1 and 7+0.012P27 + 0.012P_2 (per MWh, P in MW). Dispatch 600 MW600\ \text{MW} without losses.
  5. Which bus types does a load flow have, and which two quantities are given at each?
Answers 14 to 18
  1. sin⁡δ=1.0⋅0.25=0.25\sin\delta = 1.0 \cdot 0.25 = 0.25, δ=14.5∘\delta = 14.5^\circ.
  2. Y=−j[15−10−5−1014−4−5−49]Y = -j\begin{bmatrix} 15 & -10 & -5 \\ -10 & 14 & -4 \\ -5 & -4 & 9 \end{bmatrix} pu (diagonal = sum of the connected susceptances, off-diagonal = minus the branch susceptance).
  3. With θ1=0\theta_1 = 0: [14−4−49][θ2θ3]=[0.5−1.0]\begin{bmatrix} 14 & -4 \\ -4 & 9 \end{bmatrix}\begin{bmatrix} \theta_2 \\ \theta_3 \end{bmatrix} = \begin{bmatrix} 0.5 \\ -1.0 \end{bmatrix} gives θ2=0.0045 rad\theta_2 = 0.0045\ \text{rad}, θ3=−0.1091 rad\theta_3 = -0.1091\ \text{rad}; flows P12=(0−0.0045)/0.1=−0.045P_{12} = (0 - 0.0045)/0.1 = -0.045, P13=0.1091/0.2=0.545P_{13} = 0.1091/0.2 = 0.545, P23=(0.0045+0.1091)/0.25=0.455 puP_{23} = (0.0045 + 0.1091)/0.25 = 0.455\ \text{pu}. Check: bus 3 receives 0.545+0.455=1.00.545 + 0.455 = 1.0, and the slack supplies 0.50.5.
  4. λ=10.48\lambda = 10.48 per MWh: P1=310 MWP_1 = 310\ \text{MW}, P2=290 MWP_2 = 290\ \text{MW}.
  5. Slack (∣V∣\lvert V \rvert, θ\theta), PV or generator (PP, ∣V∣\lvert V \rvert), PQ or load (PP, QQ).

Faults

Lessons: Symmetrical Faults, Fault Levels and Breaker Duty, Symmetrical Components, Sequence Networks, Unsymmetrical Faults.

  1. A generator (x′′=0.20 pux'' = 0.20\ \text{pu}) feeds a step-up transformer (x=0.10 pux = 0.10\ \text{pu}), both on 100 MVA100\ \text{MVA}. Find the three-phase fault current at the 132 kV132\ \text{kV} terminals in pu, kA and MVA (prefault voltage 1.0 pu1.0\ \text{pu}).
  2. At a bus with Z1=Z2=j0.2Z_1 = Z_2 = j0.2 and Z0=j0.1 puZ_0 = j0.1\ \text{pu}, compare the bolted single-line-to-ground and three-phase fault currents.
  3. Why is the first peak of a fault current larger than 2\sqrt{2} times its symmetrical rms value, and on what does the extra depend?
  4. Find the symmetrical components of Ia=10∠0∘I_a = 10\angle 0^\circ, Ib=0I_b = 0, Ic=0 AI_c = 0\ \text{A}.
Answers 19 to 22
  1. if=1/0.3=3.33 pui_f = 1/0.3 = 3.33\ \text{pu}; Ib=100 000/(3⋅132)=437.4 AI_b = 100\,000/(\sqrt{3} \cdot 132) = 437.4\ \text{A}, so 1.458 kA1.458\ \text{kA}; 333 MVA333\ \text{MVA}.
  2. SLG: 3/(0.2+0.2+0.1)=6.0 pu3/(0.2 + 0.2 + 0.1) = 6.0\ \text{pu}; three-phase: 1/0.2=5.0 pu1/0.2 = 5.0\ \text{pu}. The earth fault is larger because Z0<Z1Z_0 < Z_1.
  3. The DC offset: a fault starting near a voltage zero in an inductive circuit needs a decaying DC component so that the current starts from its prefault value. Its size depends on the switching instant and its decay on X/RX/R (κ=1.02+0.98e−3R/X\kappa = 1.02 + 0.98e^{-3R/X} in IEC 60909-0:2016).
  4. I0=I1=I2=10/3=3.33 A∠0∘I_0 = I_1 = I_2 = 10/3 = 3.33\ \text{A}\angle 0^\circ.

Protection

Lessons: Protection Principles, Overcurrent and IDMT, Coordination and Grading, Distance Protection, Differential Protection, Earthing Systems, Surges, Insulation and Arc Flash.

  1. An IEC standard-inverse relay (IEC 60255-151) has a pickup of 400 A400\ \text{A} and TMS 0.10.1. How fast does it operate at 4000 A4000\ \text{A}?
  2. A downstream relay operates in 0.30 s0.30\ \text{s} at the maximum fault current. With a grading margin of 0.3 s0.3\ \text{s}, what operating time must the upstream relay have at that current?
  3. In a TN system (230 V230\ \text{V} to earth) a final circuit has a fault-loop impedance of 0.8 Ω0.8\ \Omega. What is the earth-fault current, and does a type B 32 A32\ \text{A} circuit breaker (instantaneous trip at 3 to 5 times rated current) disconnect in time?
  4. A distance relay's zone 1 is set to 80 %80\ \% of the protected line. Why not 100 %100\ \%?
Answers 23 to 26
  1. t=0.1⋅0.14/(100.02−1)=0.297 st = 0.1 \cdot 0.14/(10^{0.02} - 1) = 0.297\ \text{s}.
  2. 0.30+0.3=0.60 s0.30 + 0.3 = 0.60\ \text{s}.
  3. I=230/0.8=287.5 AI = 230/0.8 = 287.5\ \text{A}, above 5⋅32=160 A5 \cdot 32 = 160\ \text{A}, so the breaker trips instantaneously, well within 0.4 s0.4\ \text{s}.
  4. CT and VT errors, line-impedance data and the fault resistance make the measured impedance uncertain by several percent; a 100 %100\ \% reach could overreach into the next line and trip for faults there. The last 20 %20\ \% is covered by zone 2 with a delay (or by a communication scheme).

Stability, distribution, power quality and the modern grid

Lessons: Swing Equation, Equal-Area Criterion, Frequency Control, Voltage Stability, Distribution Systems, Power Quality, HVDC and FACTS, Smart Grid and DER.

  1. A generator delivers Pm=0.8 puP_m = 0.8\ \text{pu} with Pmax=2.0 puP_\text{max} = 2.0\ \text{pu} before and after a fault; during the fault it delivers nothing. With H=5 sH = 5\ \text{s}, find the critical clearing angle and time.
  2. A 30 GW30\ \text{GW} system with H=4 sH = 4\ \text{s} (on the online capacity) loses 1 GW1\ \text{GW}. What is the initial rate of change of frequency?
  3. An 11 kV11\ \text{kV} feeder of 1.2+j1.4 Ω1.2 + j1.4\ \Omega carries 4 MW+j2 Mvar4\ \text{MW} + j2\ \text{Mvar}. Estimate the voltage drop in percent.
  4. A current has harmonics of 2020, 1212, 77 and 5 %5\ \% of the fundamental. What is its THD?
  5. Name two reasons why a 600 km600\ \text{km} submarine link is built as HVDC.
Answers 27 to 31
  1. δ0=arcsin⁡0.4=23.58∘\delta_0 = \arcsin 0.4 = 23.58^\circ, δmax=156.42∘\delta_\text{max} = 156.42^\circ; cos⁡δcr=[Pm(δmax−δ0)+Pmaxcos⁡δmax]/Pmax\cos\delta_{cr} = [P_m(\delta_\text{max} - \delta_0) + P_\text{max}\cos\delta_\text{max}]/P_\text{max} gives δcr=89.4∘\delta_{cr} = 89.4^\circ; tcr=4H(δcr−δ0)/(ωsPm)=0.302 st_{cr} = \sqrt{4H(\delta_{cr} - \delta_0)/(\omega_s P_m)} = 0.302\ \text{s}.
  2. RoCoF=ΔPf0/(2HS)=1000⋅50/(2⋅4⋅30 000)=0.208 Hz/s\text{RoCoF} = \Delta P f_0/(2HS) = 1000 \cdot 50/(2 \cdot 4 \cdot 30\,000) = 0.208\ \text{Hz/s}.
  3. ΔV≈(RP+XQ)/V=(1.2⋅4×106+1.4⋅2×106)/11 000=691 V\Delta V \approx (RP + XQ)/V = (1.2 \cdot 4 \times 10^6 + 1.4 \cdot 2 \times 10^6)/11\,000 = 691\ \text{V}, 6.3 %6.3\ \%.
  4. THD=0.202+0.122+0.072+0.052=24.9 %\text{THD} = \sqrt{0.20^2 + 0.12^2 + 0.07^2 + 0.05^2} = 24.9\ \%.
  5. An AC cable of that length would need more charging current than its rating; DC has no charging current in steady state and lower losses over long distances; HVDC can also link asynchronous grids and controls the power flow precisely.

Checking answers in Python

python · try it yourself
import numpy as np

# 16: DC load flow of the triangle network
B = np.array([[14.0, -4.0], [-4.0, 9.0]])
th2, th3 = np.linalg.solve(B, [0.5, -1.0])
print(f"16: theta2 = {th2:.4f}, theta3 = {th3:.4f} rad; P12 = {(0 - th2)/0.1:.3f}, P13 = {(0 - th3)/0.2:.3f}, P23 = {(th2 - th3)/0.25:.3f} pu")

# 17: equal incremental cost
lam = (600 + 8 / 0.008 + 7 / 0.012) / (1 / 0.008 + 1 / 0.012)
print(f"17: lambda = {lam:.2f}, P1 = {(lam - 8)/0.008:.0f} MW, P2 = {(lam - 7)/0.012:.0f} MW")

# 22: symmetrical components
a = np.exp(2j * np.pi / 3)
A = np.array([[1, 1, 1], [1, a, a**2], [1, a**2, a]]) / 3
print("22: I0, I1, I2 =", np.round(np.abs(A @ np.array([10, 0, 0])), 3))

# 23: IEC standard inverse
print(f"23: t = {0.1 * 0.14 / (10**0.02 - 1):.3f} s")

# 27: critical clearing angle and time
Pm, Pmax, H, f = 0.8, 2.0, 5.0, 50.0
d0 = np.arcsin(Pm / Pmax); dmax = np.pi - d0
dcr = np.arccos((Pm * (dmax - d0) + Pmax * np.cos(dmax)) / Pmax)
tcr = np.sqrt(4 * H * (dcr - d0) / (2 * np.pi * f * Pm))
print(f"27: delta0 = {np.degrees(d0):.2f} deg, delta_cr = {np.degrees(dcr):.1f} deg, t_cr = {tcr:.3f} s")

# 30: THD
print(f"30: THD = {100 * np.sqrt(np.sum(np.array([0.20, 0.12, 0.07, 0.05])**2)):.1f} %")
16: theta2 = 0.0045, theta3 = -0.1091 rad; P12 = -0.045, P13 = 0.545, P23 = 0.455 pu
17: lambda = 10.48, P1 = 310 MW, P2 = 290 MW
22: I0, I1, I2 = [3.333 3.333 3.333]
23: t = 0.297 s
27: delta0 = 23.58 deg, delta_cr = 89.4 deg, t_cr = 0.302 s
30: THD = 24.9 %

Test yourself

A balanced load gives two-wattmeter readings of 6 kW and 6 kW. Its power factor is…

  1. 0.5
  2. 0.866
  3. 1
  4. 0

In a DC load flow, the flow on a line is…

  1. (θi−θj)/xij(\theta_i - \theta_j)/x_{ij}
  2. (Vi−Vj)/rij(V_i - V_j)/r_{ij}
  3. ViVj/xijV_iV_j/x_{ij}
  4. xij(θi−θj)x_{ij}(\theta_i - \theta_j)

Which fault usually gives the largest current near a solidly earthed transformer?

  1. three-phase
  2. line-to-line
  3. single line-to-ground (when Z0<Z1Z_0 < Z_1)
  4. open conductor

Doubling a system's inertia H for the same loss of generation changes the initial RoCoF by a factor of…

  1. 2
  2. 1/2
  3. 4
  4. 1