Differential Protection

Kirchhoff's current law gives the most selective protection there is. Measure every current entering a zone; if they do not add up to zero, current is leaving the zone somewhere it should not, through a fault. A fault outside the zone just passes through, in at one end and out at the other, and the sum stays zero however large the current. Differential protection needs no time grading, so it can trip a transformer, generator or busbar in one or two cycles. This lesson shows the principle, the bias characteristic that keeps it stable when CTs are imperfect, and the extra care a transformer needs.

Safety: the protected plant is medium- and high-voltage equipment, studied here by calculation and simulation only. The bench analogue uses resistors and a current-limited 12 V12\ \text{V} supply.

The circulating-current principle

Two CTs of matched ratio sit at the boundaries of the zone, with their secondaries connected so that a through current circulates between them and nothing flows in the relay branch connected across the midpoint (the Merz–Price arrangement). With both currents defined as flowing into the zone:

Id=∣I1+I2∣,Ib=∣I1∣+∣I2∣2I_d = \lvert \mathbf{I}_1 + \mathbf{I}_2 \rvert, \qquad I_b = \frac{\lvert \mathbf{I}_1 \rvert + \lvert \mathbf{I}_2 \rvert}{2}

IdI_d is the differential (operating) current, IbI_b the bias (restraint, stabilising) current. External fault or load: I2=−I1\mathbf{I}_2 = -\mathbf{I}_1, Id=0I_d = 0. Internal fault fed from both ends: the currents add, and IdI_d is the whole fault current.

protected zone CT1CT2 relay: I1 + I2 I I1I2 F-ext external fault: I2 = -I1, relay current 0

Why the bias is needed

Real CTs are not identical. Ratio errors of a few percent, a transformer tap changer that moves the ratio by ±10 %\pm 10\ \%, and above all CT saturation during a heavy external fault produce a false differential current that grows with the through current. A plain overcurrent setting on IdI_d would have to be very high. The biased (percentage) characteristic raises the trip threshold in proportion to the through current. A common dual-slope form:

Id,trip={Is1+k1Ib,Ib≤Ib2Is1+k1Ib2+k2 (Ib−Ib2),Ib>Ib2I_{d,\text{trip}} = \begin{cases} I_{s1} + k_1 I_b, & I_b \le I_{b2} \\ I_{s1} + k_1 I_{b2} + k_2\,(I_b - I_{b2}), & I_b > I_{b2} \end{cases}

with, for example, Is1=0.2 puI_{s1} = 0.2\ \text{pu}, k1=30 %k_1 = 30\ \%, Ib2=2 puI_{b2} = 2\ \text{pu} and k2=80 %k_2 = 80\ \% (values from typical numerical transformer relays; each manufacturer has its own defaults and ranges). The steep second slope covers saturation at high through-fault currents.

High-impedance busbar protection solves the saturation problem differently: a stabilising resistor in the relay branch makes the relay voltage-operated. If one CT saturates completely during an external fault, its secondary looks like its winding plus lead resistance; the healthy CT's current then divides between that path and the relay branch, and a high relay impedance keeps the relay current below its setting. The required setting voltage is Vs>If,sec (Rct+Rleads)V_s > I_{f,\text{sec}}\,(R_{ct} + R_\text{leads}).

Transformer differential

A transformer's two sides carry different currents and, for most vector groups, phase-shifted ones. The relay must apply:

  • Ratio compensation: each side's current divided by its rated current, so both are in per unit.
  • Vector-group compensation: for Dyn11 the LV currents are rotated by 30∘30^\circ (numerically, or by delta-connected CTs in old schemes).
  • Zero-sequence removal on the earthed star side: an external LV earth fault drives zero-sequence current through the LV CTs that never appears on the delta side (Sequence Networks); left in, it would look internal.
  • Inrush restraint: energising a transformer draws magnetising current into one side only, a pure differential current of up to 1010 times rated (Parallel Operation and Inrush). Inrush is rich in second harmonic; relays block when I2f/I1fI_{2f}/I_{1f} exceeds about 15 %15\ \%. Overexcitation is detected by the fifth harmonic.

A restricted earth fault (REF) element on the star winding, comparing neutral current with the residual of the phase CTs, covers earth faults close to the neutral that the overall differential is too insensitive to see.

Worked example: B1 transformer differential

Given: B1's 1000 kVA1000\ \text{kVA}, 11/0.4 kV11/0.4\ \text{kV} Dyn11 transformer, HV CTs 100/1, LV CTs 1600/1, on-load tap range ±5 %\pm 5\ \% (assumed for this example), CTs class 5P20. Bias settings as above. The largest external fault is the LV busbar fault, 23.68 kA23.68\ \text{kA}.

Find: the CT secondary currents at rated load, the through-fault current in pu, the worst false IdI_d for the external fault, and whether the relay stays stable.

Solve:

In,HV=52.49 A→0.525 A sec,In,LV=1443 A→0.902 A secIb=23 680 A1443 A=16.41 puId,false≤(0.05+0.05+0.05)⋅16.41=2.46 pu(tap+two CT errors)Id,trip=0.2+0.3⋅2+0.8 (16.41−2)=12.33 pu\begin{aligned} I_{n,HV} &= 52.49\ \text{A} \to 0.525\ \text{A sec}, \qquad I_{n,LV} = 1443\ \text{A} \to 0.902\ \text{A sec} \\ I_b &= \frac{23\,680\ \text{A}}{1443\ \text{A}} = 16.41\ \text{pu} \\ I_{d,\text{false}} &\le (0.05 + 0.05 + 0.05)\cdot 16.41 = 2.46\ \text{pu} \quad (\text{tap} + \text{two CT errors}) \\ I_{d,\text{trip}} &= 0.2 + 0.3 \cdot 2 + 0.8\,(16.41 - 2) = 12.33\ \text{pu} \end{aligned}

Check: 2.46 pu≪12.33 pu2.46\ \text{pu} \ll 12.33\ \text{pu}: stable for the external fault, with a large margin left for transient CT saturation. At rated load the tap error alone gives Id=0.05 puI_d = 0.05\ \text{pu} against a threshold of 0.2+0.3⋅1=0.5 pu0.2 + 0.3 \cdot 1 = 0.5\ \text{pu}. The relay must apply the 0.5250.525 and 0.9020.902 scaling: without it, a healthy transformer at full load would show 0.902−0.525=0.377 A0.902 - 0.525 = 0.377\ \text{A} of false differential.

In Python: the bias characteristic and inrush harmonics

python · try it yourself
import numpy as np
import matplotlib.pyplot as plt

def trip_level(Ib, Is1=0.2, k1=0.3, Ib2=2.0, k2=0.8):
    Ib = np.asarray(Ib, dtype=float)
    return np.where(Ib <= Ib2, Is1 + k1 * Ib, Is1 + k1 * Ib2 + k2 * (Ib - Ib2))

cases = {"full load, tap +5 %": (1.0, 0.05),
         "external fault, worst errors": (16.41, 2.46),
         "internal fault, 3 pu from HV only": (1.5, 3.0),
         "turn fault, 0.4 pu": (1.2, 0.4)}
for name, (Ib, Id) in cases.items():
    lim = float(trip_level(Ib))
    print(f"{name:34s} Ib = {Ib:5.2f}  Id = {Id:4.2f}  limit = {lim:5.2f}  ->", "TRIP" if Id > lim else "stable")

# Inrush: current flows only while the core is saturated, as caps of a sine (conduction angle in degrees)
t = np.arange(1000) / 1000
for cond in (120, 180, 240):
    b = np.radians(cond) / 2
    i = np.maximum(0, np.cos(2 * np.pi * t) - np.cos(b))
    X = np.abs(np.fft.rfft(i))
    print(f"inrush, conduction {cond:3d} deg: I2/I1 = {X[2] / X[1]:.2f}")

Ib = np.linspace(0, 20, 300)
fig, ax = plt.subplots(figsize=(6, 3.6))
ax.plot(Ib, trip_level(Ib), "k", label="trip threshold")
ax.fill_between(Ib, trip_level(Ib), 20, alpha=0.15, label="trip region")
for name, (b, d) in cases.items():
    ax.plot(b, d, "o", label=name)
ax.set_xlabel("bias current Ib (pu)"); ax.set_ylabel("differential current Id (pu)")
ax.set_xlim(0, 20); ax.set_ylim(0, 16); ax.grid(alpha=0.3); ax.legend(fontsize=7)
fig.tight_layout()
plt.show()
full load, tap +5 %                Ib =  1.00  Id = 0.05  limit =  0.50  -> stable
external fault, worst errors       Ib = 16.41  Id = 2.46  limit = 12.33  -> stable
internal fault, 3 pu from HV only  Ib =  1.50  Id = 3.00  limit =  0.65  -> TRIP
turn fault, 0.4 pu                 Ib =  1.20  Id = 0.40  limit =  0.56  -> stable
inrush, conduction 120 deg: I2/I1 = 0.71
inrush, conduction 180 deg: I2/I1 = 0.42
inrush, conduction 240 deg: I2/I1 = 0.17

The last line is a warning: a fault across a few turns raises the terminal currents only slightly, and the differential misses it. That is what the Buchholz gas relay (oil transformers) and REF are for. An inrush cap of 120∘120^\circ to 240∘240^\circ has a second harmonic of tens of percent of its fundamental (the last three output lines), far above a 15 %15\ \% blocking level.

Interactive: a high-impedance scheme with a saturated CT

An external busbar fault gives 20 A20\ \text{A} secondary in the healthy CT (I1). The CT on the faulted circuit has saturated completely, so it is just its winding plus leads, 5 Ω5\ \Omega (RCT2). The relay branch with its stabilising resistor is RS. With RS at 10 Ω10\ \Omega the relay takes 6.67 A6.67\ \text{A} and would trip falsely; at 1000 Ω1000\ \Omega it takes 99.5 mA99.5\ \text{mA}, just below a 0.1 A0.1\ \text{A} setting, and the voltage at the junction is 99.5 V99.5\ \text{V}, which is the setting voltage If(Rct+Rleads)=100 VI_f(R_{ct} + R_\text{leads}) = 100\ \text{V} the textbook rule asks for.

node voltages (to ground 0)a99.50 VnetlistI1 0 a 20RCT2 a 0 5RS a 0 1000element currents (node 1 to node 2 through it)I10>a20.0 ARCT2a>019.9 ARSa>099.5 mA

Guided lab: a DC differential model

Hand calculation. Two "CTs" are current sources: use two current-limited bench supplies set to 100 mA100\ \text{mA} each in constant-current mode. Connect them as a circulating pair through a relay branch of 47 Ω47\ \Omega, each supply in series with a 22 Ω22\ \Omega, 1 W1\ \text{W} resistor (the CT winding and pilot resistance). A bench supply cannot sink current, and without these resistors one supply would be driven to a negative output voltage in the mismatch case; with them both outputs stay positive (about 1.51.5 to 11.6 V11.6\ \text{V} in the three cases). Predict the relay-branch current for the external case (opposite directions: 00), for a 10 %10\ \% mismatch (set one supply to 90 mA90\ \text{mA}: 10 mA10\ \text{mA}), and for the internal case (both feeding the relay branch: 200 mA200\ \text{mA}, 1.9 W1.9\ \text{W} in 47 Ω47\ \Omega; use a 5 W5\ \text{W} resistor).

Simulation. Put the same circuit in the netlist lab (two I sources and the resistor) and confirm.

What you would measure. A DMM in the relay branch: about 00, 1010 and 200 mA200\ \text{mA}. Bench-supply current limits are typically accurate to ±1 %\pm 1\ \% plus a few mA, which is itself a false differential: exactly the reason for the bias.

Hazards and safe setup. Constant-current supplies with the voltage limit at 12 V12\ \text{V}; resistor power rating checked; never connect the two supply outputs in a way that drives one backwards into the other beyond its rating.

Pitfalls

  • Wrong CT polarity. A reversed CT makes load current look like an internal fault; differential schemes are checked with a primary-injection or on-load "stability" test before commissioning.
  • Missing zero-sequence removal on a transformer with an earthed star winding: external earth faults trip it.
  • Second-harmonic blocking too sensitive. Modern low-loss cores give inrush with less second harmonic; cross-blocking between phases or waveform-based methods may be needed.
  • Assuming differential covers everything. Turn faults and faults near a star point give small IdI_d.

Practice

  1. With the bias settings above, what is the trip threshold at Ib=5 puI_b = 5\ \text{pu}?
  2. A high-impedance relay has setting 0.05 A0.05\ \text{A}; the largest external fault gives 25 A25\ \text{A} secondary and Rct+Rleads=4 ΩR_{ct} + R_\text{leads} = 4\ \Omega. Find the setting voltage and the minimum stabilising resistor.
  3. Why does a Dyn11 transformer differential relay need vector-group compensation even for balanced load?
Answer
  1. 0.2+0.6+0.8⋅3=3.2 pu0.2 + 0.6 + 0.8 \cdot 3 = 3.2\ \text{pu}.
  2. Vs=25⋅4=100 VV_s = 25 \cdot 4 = 100\ \text{V}; RS≥100/0.05=2000 ΩR_S \ge 100/0.05 = 2000\ \Omega (minus the relay's own small burden).
  3. The LV line currents lead the HV ones by 30∘30^\circ; without rotation, equal per-unit magnitudes still give ∣1−ej30∘∣=0.52 pu\lvert 1 - e^{j30^\circ} \rvert = 0.52\ \text{pu} of false differential at full load.

Test yourself

For a fault outside the protected zone, ideal differential protection measures…

  1. the full fault current
  2. zero differential current
  3. twice the load current
  4. only the bias current's harmonics

Why is the trip threshold made to rise with the bias (through) current?

  1. to trip faster for big faults
  2. because CT errors, tap changers and saturation create false differential current proportional to the through current
  3. to block inrush
  4. to measure fault resistance

Transformer inrush is distinguished from an internal fault mainly by…

  1. its large DC offset only
  2. its high second-harmonic content
  3. its negative-sequence current
  4. its frequency of 60 Hz

In a high-impedance busbar scheme the stabilising resistor…

  1. lowers the relay voltage
  2. keeps the relay current below setting when one CT saturates on an external fault
  3. speeds up the CTs
  4. replaces the CTs