Differential Protection
Kirchhoff's current law gives the most selective protection there is. Measure every current entering a zone; if they do not add up to zero, current is leaving the zone somewhere it should not, through a fault. A fault outside the zone just passes through, in at one end and out at the other, and the sum stays zero however large the current. Differential protection needs no time grading, so it can trip a transformer, generator or busbar in one or two cycles. This lesson shows the principle, the bias characteristic that keeps it stable when CTs are imperfect, and the extra care a transformer needs.
Safety: the protected plant is medium- and high-voltage equipment, studied here by calculation and simulation only. The bench analogue uses resistors and a current-limited supply.
The circulating-current principle
Two CTs of matched ratio sit at the boundaries of the zone, with their secondaries connected so that a through current circulates between them and nothing flows in the relay branch connected across the midpoint (the Merz–Price arrangement). With both currents defined as flowing into the zone:
is the differential (operating) current, the bias (restraint, stabilising) current. External fault or load: , . Internal fault fed from both ends: the currents add, and is the whole fault current.
Why the bias is needed
Real CTs are not identical. Ratio errors of a few percent, a transformer tap changer that moves the ratio by , and above all CT saturation during a heavy external fault produce a false differential current that grows with the through current. A plain overcurrent setting on would have to be very high. The biased (percentage) characteristic raises the trip threshold in proportion to the through current. A common dual-slope form:
with, for example, , , and (values from typical numerical transformer relays; each manufacturer has its own defaults and ranges). The steep second slope covers saturation at high through-fault currents.
High-impedance busbar protection solves the saturation problem differently: a stabilising resistor in the relay branch makes the relay voltage-operated. If one CT saturates completely during an external fault, its secondary looks like its winding plus lead resistance; the healthy CT's current then divides between that path and the relay branch, and a high relay impedance keeps the relay current below its setting. The required setting voltage is .
Transformer differential
A transformer's two sides carry different currents and, for most vector groups, phase-shifted ones. The relay must apply:
- Ratio compensation: each side's current divided by its rated current, so both are in per unit.
- Vector-group compensation: for Dyn11 the LV currents are rotated by (numerically, or by delta-connected CTs in old schemes).
- Zero-sequence removal on the earthed star side: an external LV earth fault drives zero-sequence current through the LV CTs that never appears on the delta side (Sequence Networks); left in, it would look internal.
- Inrush restraint: energising a transformer draws magnetising current into one side only, a pure differential current of up to times rated (Parallel Operation and Inrush). Inrush is rich in second harmonic; relays block when exceeds about . Overexcitation is detected by the fifth harmonic.
A restricted earth fault (REF) element on the star winding, comparing neutral current with the residual of the phase CTs, covers earth faults close to the neutral that the overall differential is too insensitive to see.
Worked example: B1 transformer differential
Given: B1's , Dyn11 transformer, HV CTs 100/1, LV CTs 1600/1, on-load tap range (assumed for this example), CTs class 5P20. Bias settings as above. The largest external fault is the LV busbar fault, .
Find: the CT secondary currents at rated load, the through-fault current in pu, the worst false for the external fault, and whether the relay stays stable.
Solve:
Check: : stable for the external fault, with a large margin left for transient CT saturation. At rated load the tap error alone gives against a threshold of . The relay must apply the and scaling: without it, a healthy transformer at full load would show of false differential.
In Python: the bias characteristic and inrush harmonics
import numpy as np
import matplotlib.pyplot as plt
def trip_level(Ib, Is1=0.2, k1=0.3, Ib2=2.0, k2=0.8):
Ib = np.asarray(Ib, dtype=float)
return np.where(Ib <= Ib2, Is1 + k1 * Ib, Is1 + k1 * Ib2 + k2 * (Ib - Ib2))
cases = {"full load, tap +5 %": (1.0, 0.05),
"external fault, worst errors": (16.41, 2.46),
"internal fault, 3 pu from HV only": (1.5, 3.0),
"turn fault, 0.4 pu": (1.2, 0.4)}
for name, (Ib, Id) in cases.items():
lim = float(trip_level(Ib))
print(f"{name:34s} Ib = {Ib:5.2f} Id = {Id:4.2f} limit = {lim:5.2f} ->", "TRIP" if Id > lim else "stable")
# Inrush: current flows only while the core is saturated, as caps of a sine (conduction angle in degrees)
t = np.arange(1000) / 1000
for cond in (120, 180, 240):
b = np.radians(cond) / 2
i = np.maximum(0, np.cos(2 * np.pi * t) - np.cos(b))
X = np.abs(np.fft.rfft(i))
print(f"inrush, conduction {cond:3d} deg: I2/I1 = {X[2] / X[1]:.2f}")
Ib = np.linspace(0, 20, 300)
fig, ax = plt.subplots(figsize=(6, 3.6))
ax.plot(Ib, trip_level(Ib), "k", label="trip threshold")
ax.fill_between(Ib, trip_level(Ib), 20, alpha=0.15, label="trip region")
for name, (b, d) in cases.items():
ax.plot(b, d, "o", label=name)
ax.set_xlabel("bias current Ib (pu)"); ax.set_ylabel("differential current Id (pu)")
ax.set_xlim(0, 20); ax.set_ylim(0, 16); ax.grid(alpha=0.3); ax.legend(fontsize=7)
fig.tight_layout()
plt.show()full load, tap +5 % Ib = 1.00 Id = 0.05 limit = 0.50 -> stable
external fault, worst errors Ib = 16.41 Id = 2.46 limit = 12.33 -> stable
internal fault, 3 pu from HV only Ib = 1.50 Id = 3.00 limit = 0.65 -> TRIP
turn fault, 0.4 pu Ib = 1.20 Id = 0.40 limit = 0.56 -> stable
inrush, conduction 120 deg: I2/I1 = 0.71
inrush, conduction 180 deg: I2/I1 = 0.42
inrush, conduction 240 deg: I2/I1 = 0.17
The last line is a warning: a fault across a few turns raises the terminal currents only slightly, and the differential misses it. That is what the Buchholz gas relay (oil transformers) and REF are for. An inrush cap of to has a second harmonic of tens of percent of its fundamental (the last three output lines), far above a blocking level.
Interactive: a high-impedance scheme with a saturated CT
An external busbar fault gives secondary in the healthy CT (I1). The CT on the faulted circuit has saturated completely, so it is just its winding plus leads, (RCT2). The relay branch with its stabilising resistor is RS. With RS at the relay takes and would trip falsely; at it takes , just below a setting, and the voltage at the junction is , which is the setting voltage the textbook rule asks for.
Guided lab: a DC differential model
Hand calculation. Two "CTs" are current sources: use two current-limited bench supplies set to each in constant-current mode. Connect them as a circulating pair through a relay branch of , each supply in series with a , resistor (the CT winding and pilot resistance). A bench supply cannot sink current, and without these resistors one supply would be driven to a negative output voltage in the mismatch case; with them both outputs stay positive (about to in the three cases). Predict the relay-branch current for the external case (opposite directions: ), for a mismatch (set one supply to : ), and for the internal case (both feeding the relay branch: , in ; use a resistor).
Simulation. Put the same circuit in the netlist lab (two I sources and the resistor) and confirm.
What you would measure. A DMM in the relay branch: about , and . Bench-supply current limits are typically accurate to plus a few mA, which is itself a false differential: exactly the reason for the bias.
Hazards and safe setup. Constant-current supplies with the voltage limit at ; resistor power rating checked; never connect the two supply outputs in a way that drives one backwards into the other beyond its rating.
Pitfalls
- Wrong CT polarity. A reversed CT makes load current look like an internal fault; differential schemes are checked with a primary-injection or on-load "stability" test before commissioning.
- Missing zero-sequence removal on a transformer with an earthed star winding: external earth faults trip it.
- Second-harmonic blocking too sensitive. Modern low-loss cores give inrush with less second harmonic; cross-blocking between phases or waveform-based methods may be needed.
- Assuming differential covers everything. Turn faults and faults near a star point give small .
Practice
- With the bias settings above, what is the trip threshold at ?
- A high-impedance relay has setting ; the largest external fault gives secondary and . Find the setting voltage and the minimum stabilising resistor.
- Why does a Dyn11 transformer differential relay need vector-group compensation even for balanced load?
Answer
- .
- ; (minus the relay's own small burden).
- The LV line currents lead the HV ones by ; without rotation, equal per-unit magnitudes still give of false differential at full load.
Test yourself
For a fault outside the protected zone, ideal differential protection measures…
- the full fault current
- zero differential current
- twice the load current
- only the bias current's harmonics
Why is the trip threshold made to rise with the bias (through) current?
- to trip faster for big faults
- because CT errors, tap changers and saturation create false differential current proportional to the through current
- to block inrush
- to measure fault resistance
Transformer inrush is distinguished from an internal fault mainly by…
- its large DC offset only
- its high second-harmonic content
- its negative-sequence current
- its frequency of 60 Hz
In a high-impedance busbar scheme the stabilising resistor…
- lowers the relay voltage
- keeps the relay current below setting when one CT saturates on an external fault
- speeds up the CTs
- replaces the CTs