The Per-Unit System for Multi-Voltage Networks
A generator at feeds a line through a step-up transformer, and a second transformer steps down to a load. In ohms, every impedance has to be referred through the turns ratios to one side before you can add anything, and a transformer whose nameplate ratio is not exactly the ratio of the system voltages makes that bookkeeping error-prone. In per unit, the transformers disappear and the whole network becomes one circuit of small, comparable numbers. The Per-Unit System for Transformers and Machines defined bases, base impedance and the change-of-base formula for a single transformer; this lesson applies them to a network with several voltage zones, including the case where a nameplate ratio does not match the chosen bases.
Safety: these are generation and transmission networks, studied by calculation and simulation only.
Voltage zones
A network is split into zones by its transformers. The rules:
- Choose one power base for the whole network (this course uses ).
- Choose the voltage base in one zone, usually the nominal voltage of the main network.
- Carry it through every transformer in the ratio of that transformer's nameplate voltages. Then each transformer's ideal part has a ratio of exactly in per unit and vanishes.
- Convert every nameplate impedance to the common bases:
using in the voltage ratio the rated and base voltages on the same side of the transformer.
When a network has a loop, rule 3 can be inconsistent: going round the loop through different transformers may give two different bases for one zone. Then one transformer keeps a ratio different from in per unit, an off-nominal tap, modelled in load flow as a circuit (Voltage Control). Radial networks, like the one here, never have that problem.
Load models in per unit
A load given as at rated voltage becomes, as a constant impedance,
A constant-power load needs an iterative solution instead; that is the load-flow problem of the Load Flow section.
Worked example: generator to load across three voltages
Given: an source bus held at ; T1 , , ; a line of ; T2 , , ; a load of at treated as a constant impedance. Transformer resistances neglected.
Find: the load voltage in kV and the line current in amperes.
Solve: , on the line. Through T1's nameplate ratio, the generator-zone base is ; through T2, the load-zone base is .
Check: in the program the same circuit is solved in ohms referred to the side, with the source raised by T1's real ratio () and the load referred up by : it gives the same and . The load voltage is low, and the load, being a constant impedance, takes only : this network needs T2's tap changer (Voltage Control).
In Python: per unit and ohms side by side
import numpy as np
Sb, Vb_line = 100e6, 132e3
Vb_gen = Vb_line * 11 / 138 # carried through T1's nameplate ratio
Vb_load = Vb_line * 33 / 132 # through T2's
Zb = Vb_line**2 / Sb
print(f"voltage bases: {Vb_gen/1e3:.2f} kV | {Vb_line/1e3:.0f} kV | {Vb_load/1e3:.0f} kV, Zb(line) = {Zb:.2f} ohm")
def rebase(z, S_rated, V_rated, V_base):
return z * (Sb / S_rated) * (V_rated / V_base) ** 2
vs = 11e3 / Vb_gen
zt1 = 1j * rebase(0.12, 100e6, 138e3, Vb_line) # HV-side rated and base voltages
zl = (4.8 + 24j) / Zb
zt2 = 1j * rebase(0.10, 50e6, 132e3, Vb_line)
zload = 1 / np.conj(complex(40e6, 20e6) / Sb)
i = vs / (zt1 + zl + zt2 + zload)
v = i * zload
Ib = Sb / (np.sqrt(3) * Vb_line)
print(f"vs = {vs:.4f} pu, zT1 = j{zt1.imag:.4f}, zline = {zl.real:.4f} + j{zl.imag:.4f}, zT2 = j{zt2.imag:.3f}")
print(f"i = {abs(i):.4f} pu at {np.degrees(np.angle(i)):.1f} deg -> {abs(i)*Ib:.1f} A in the line")
print(f"v_load = {abs(v):.4f} pu at {np.degrees(np.angle(v)):.2f} deg -> {abs(v)*Vb_load/1e3:.2f} kV")
print(f"load takes {(abs(v)**2 / np.conj(zload)).real * 100:.1f} MW")
# Check in ohms, everything referred to the 132 kV side
E = 11e3 * 138 / 11 / np.sqrt(3) # source phase voltage seen through T1
Zt1 = 1j * 0.12 * 138e3**2 / 100e6
Zt2 = 1j * 0.10 * 132e3**2 / 50e6
Zload = (33e3**2 / np.conj(complex(40e6, 20e6))) * (132 / 33)**2
I = E / (Zt1 + 4.8 + 24j + Zt2 + Zload)
V = I * Zload * np.sqrt(3) * 33 / 132
print(f"in ohms: I = {abs(I):.1f} A, V_load = {abs(V)/1e3:.2f} kV")voltage bases: 10.52 kV | 132 kV | 33 kV, Zb(line) = 174.24 ohm
vs = 1.0455 pu, zT1 = j0.1312, zline = 0.0275 + j0.1377, zT2 = j0.200
i = 0.4176 pu at -35.9 deg -> 182.6 A in the line
v_load = 0.9337 pu at -9.36 deg -> 30.81 kV
load takes 34.9 MW
in ohms: I = 182.6 A, V_load = 30.81 kV
Interactive: the per-unit circuit
The netlist lab can work directly in per unit if each reactance is entered as an inductor : for T1, for the line, for T2 and for the load's ; a "volt" is then a per-unit voltage and an "ampere" a per-unit current. Its plot sweeps frequency, so read the values at the cursor: the load bus c reads (that is ), the current () and the sending end h . Slide the load resistance RD down (more load) and watch the voltage profile sag.
Guided lab: a two-zone resistor network in per unit
Hand calculation. On the bench, a "network" of resistors with two voltage zones needs a transformer, so use per unit the other way round: take a per-unit circuit and scale it to bench values. Choose and (). A per-unit chain of , and a load of becomes , and from a DC source (resistive only).
Simulation. Compute the per-unit load voltage, , and convert: , current .
What you would measure. With a current-limited bench supply at (limit ) and 1 % resistors, a DMM would read within about (resistor tolerance dominates) and within about .
Hazards and safe setup. , current limit set first; the resistors dissipate at most .
Pitfalls
- Using the system nominal voltage instead of the zone base carried through the nameplate ratio. The generator zone here is , not ; the source is , not .
- Rebasing a transformer impedance with voltages from different sides. Use rated and base voltages on the same side.
- Forgetting line impedances are in ohms. Divide by the zone's ; never rebase them with the transformer formula.
- Constant-impedance versus constant-power loads. They give different answers when the voltage is off nominal.
Practice
- A , generator has . Express it on and a base.
- On , , what is , and what is a reactance in per unit?
- In the worked example, by what ratio must T2's tap change to bring the load to ? (Ignore the change in current.)
Answer
- .
- ; .
- About : roughly more LV turns (or fewer HV turns); in practice slightly more, since the current rises with the voltage.
Test yourself
The voltage base of a zone is carried through a transformer in the ratio of…
- the system nominal voltages
- the transformer's nameplate voltages
- the actual measured voltages
- the square root of 3
A 50 MVA transformer has x = 10 %. On a 100 MVA base (same voltage) it is…
- 0.05 pu
- 0.10 pu
- 0.20 pu
- 0.50 pu
A load of 0.6 + j0.8 pu at 1 pu voltage, as a constant impedance, is…
- 0.6 + j0.8 pu
- 0.6 - j0.8 pu
- 1/(0.6 - j0.8) = 0.6 + j0.8 pu
- 1/(0.6 + j0.8) = 0.6 - j0.8 pu
Why does a loop of transformers sometimes leave an off-nominal ratio in per unit?
- Per unit only works for radial networks
- Bases carried round the loop through different nameplate ratios may disagree
- Transformers in loops have no impedance
- The power base changes