The Per-Unit System for Multi-Voltage Networks

A generator at 11 kV11\ \text{kV} feeds a 132 kV132\ \text{kV} line through a step-up transformer, and a second transformer steps down to a 33 kV33\ \text{kV} load. In ohms, every impedance has to be referred through the turns ratios to one side before you can add anything, and a transformer whose nameplate ratio is not exactly the ratio of the system voltages makes that bookkeeping error-prone. In per unit, the transformers disappear and the whole network becomes one circuit of small, comparable numbers. The Per-Unit System for Transformers and Machines defined bases, base impedance and the change-of-base formula for a single transformer; this lesson applies them to a network with several voltage zones, including the case where a nameplate ratio does not match the chosen bases.

Safety: these are generation and transmission networks, studied by calculation and simulation only.

Voltage zones

A network is split into zones by its transformers. The rules:

  1. Choose one power base SbS_b for the whole network (this course uses 100 MVA100\ \text{MVA}).
  2. Choose the voltage base in one zone, usually the nominal voltage of the main network.
  3. Carry it through every transformer in the ratio of that transformer's nameplate voltages. Then each transformer's ideal part has a ratio of exactly 1:11 : 1 in per unit and vanishes.
  4. Convert every nameplate impedance to the common bases:
znew=znameplate SbSrated(VratedVb)2,zline=ZΩZb,Zb=Vb2Sbz_\text{new} = z_\text{nameplate}\,\frac{S_b}{S_\text{rated}}\left(\frac{V_\text{rated}}{V_{b}}\right)^2, \qquad z_\text{line} = \frac{Z_\Omega}{Z_b}, \quad Z_b = \frac{V_b^2}{S_b}

using in the voltage ratio the rated and base voltages on the same side of the transformer.

When a network has a loop, rule 3 can be inconsistent: going round the loop through different transformers may give two different bases for one zone. Then one transformer keeps a ratio different from 1:11 : 1 in per unit, an off-nominal tap, modelled in load flow as a π\pi circuit (Voltage Control). Radial networks, like the one here, never have that problem.

Load models in per unit

A load given as S=P+jQ\mathbf{S} = P + jQ at rated voltage becomes, as a constant impedance,

zload=v2s∗=1p−jqat v=1 puz_\text{load} = \frac{v^2}{\mathbf{s}^*} = \frac{1}{p - jq} \quad \text{at } v = 1\ \text{pu}

A constant-power load needs an iterative solution instead; that is the load-flow problem of the Load Flow section.

~ 60 km line4.8 + j24 Ohm 40 + j20 MVA T1 100 MVA11/138 kV, 12 % T2 50 MVA132/33 kV, 10 % Vb = 10.52 kVVb = 132 kVVb = 33 kV 1.0455 j0.1312 0.0275 + j0.1377 j0.200 load 2 + j1 per unit, 100 MVA

Worked example: generator to load across three voltages

Given: an 11 kV11\ \text{kV} source bus held at 11.0 kV11.0\ \text{kV}; T1 100 MVA100\ \text{MVA}, 11/138 kV11/138\ \text{kV}, x=12 %x = 12\ \%; a 132 kV132\ \text{kV} line of 4.8+j24 Ω4.8 + j24\ \Omega; T2 50 MVA50\ \text{MVA}, 132/33 kV132/33\ \text{kV}, x=10 %x = 10\ \%; a load of 40 MW+j20 Mvar40\ \text{MW} + j20\ \text{Mvar} at 33 kV33\ \text{kV} treated as a constant impedance. Transformer resistances neglected.

Find: the load voltage in kV and the line current in amperes.

Solve: Sb=100 MVAS_b = 100\ \text{MVA}, Vb=132 kVV_b = 132\ \text{kV} on the line. Through T1's nameplate ratio, the generator-zone base is 132⋅11/138=10.52 kV132 \cdot 11/138 = 10.52\ \text{kV}; through T2, the load-zone base is 33 kV33\ \text{kV}.

vs=11.010.52=1.0455 pu,zT1=j0.12⋅100100(138132)2=j0.1312 puzline=4.8+j241322/100=4.8+j24174.24=0.0275+j0.1377 pu,zT2=j0.10⋅10050=j0.200 puzload=10.4−j0.2=2+j1 pui=1.0455j0.1312+0.0275+j0.1377+j0.200+2+j1=0.4176 pu∠−35.9∘vload=i zload=0.9337 pu∠−9.36∘  ⇒  0.9337⋅33 kV=30.81 kVIline=0.4176⋅100 MVA3⋅132 kV=0.4176⋅437.4 A=182.6 A\begin{aligned} v_s &= \frac{11.0}{10.52} = 1.0455\ \text{pu}, \qquad z_{T1} = j0.12 \cdot \frac{100}{100}\left(\frac{138}{132}\right)^2 = j0.1312\ \text{pu} \\ z_\text{line} &= \frac{4.8 + j24}{132^2/100} = \frac{4.8 + j24}{174.24} = 0.0275 + j0.1377\ \text{pu}, \qquad z_{T2} = j0.10 \cdot \frac{100}{50} = j0.200\ \text{pu} \\ z_\text{load} &= \frac{1}{0.4 - j0.2} = 2 + j1\ \text{pu} \\ i &= \frac{1.0455}{j0.1312 + 0.0275 + j0.1377 + j0.200 + 2 + j1} = 0.4176\ \text{pu}\angle -35.9^\circ \\ v_\text{load} &= i\,z_\text{load} = 0.9337\ \text{pu}\angle -9.36^\circ \;\Rightarrow\; 0.9337 \cdot 33\ \text{kV} = 30.81\ \text{kV} \\ I_\text{line} &= 0.4176 \cdot \frac{100\ \text{MVA}}{\sqrt{3} \cdot 132\ \text{kV}} = 0.4176 \cdot 437.4\ \text{A} = 182.6\ \text{A} \end{aligned}

Check: in the program the same circuit is solved in ohms referred to the 132 kV132\ \text{kV} side, with the source raised by T1's real ratio (11⋅138/11=138 kV11 \cdot 138/11 = 138\ \text{kV}) and the load referred up by (132/33)2(132/33)^2: it gives the same 182.6 A182.6\ \text{A} and 30.81 kV30.81\ \text{kV}. The load voltage is 6.6 %6.6\ \% low, and the load, being a constant impedance, takes only 0.93372⋅40=34.9 MW0.9337^2 \cdot 40 = 34.9\ \text{MW}: this network needs T2's tap changer (Voltage Control).

In Python: per unit and ohms side by side

python · try it yourself
import numpy as np

Sb, Vb_line = 100e6, 132e3
Vb_gen = Vb_line * 11 / 138                       # carried through T1's nameplate ratio
Vb_load = Vb_line * 33 / 132                      # through T2's
Zb = Vb_line**2 / Sb
print(f"voltage bases: {Vb_gen/1e3:.2f} kV | {Vb_line/1e3:.0f} kV | {Vb_load/1e3:.0f} kV, Zb(line) = {Zb:.2f} ohm")

def rebase(z, S_rated, V_rated, V_base):
    return z * (Sb / S_rated) * (V_rated / V_base) ** 2

vs = 11e3 / Vb_gen
zt1 = 1j * rebase(0.12, 100e6, 138e3, Vb_line)    # HV-side rated and base voltages
zl = (4.8 + 24j) / Zb
zt2 = 1j * rebase(0.10, 50e6, 132e3, Vb_line)
zload = 1 / np.conj(complex(40e6, 20e6) / Sb)
i = vs / (zt1 + zl + zt2 + zload)
v = i * zload
Ib = Sb / (np.sqrt(3) * Vb_line)
print(f"vs = {vs:.4f} pu, zT1 = j{zt1.imag:.4f}, zline = {zl.real:.4f} + j{zl.imag:.4f}, zT2 = j{zt2.imag:.3f}")
print(f"i = {abs(i):.4f} pu at {np.degrees(np.angle(i)):.1f} deg -> {abs(i)*Ib:.1f} A in the line")
print(f"v_load = {abs(v):.4f} pu at {np.degrees(np.angle(v)):.2f} deg -> {abs(v)*Vb_load/1e3:.2f} kV")
print(f"load takes {(abs(v)**2 / np.conj(zload)).real * 100:.1f} MW")

# Check in ohms, everything referred to the 132 kV side
E = 11e3 * 138 / 11 / np.sqrt(3)                  # source phase voltage seen through T1
Zt1 = 1j * 0.12 * 138e3**2 / 100e6
Zt2 = 1j * 0.10 * 132e3**2 / 50e6
Zload = (33e3**2 / np.conj(complex(40e6, 20e6))) * (132 / 33)**2
I = E / (Zt1 + 4.8 + 24j + Zt2 + Zload)
V = I * Zload * np.sqrt(3) * 33 / 132
print(f"in ohms: I = {abs(I):.1f} A, V_load = {abs(V)/1e3:.2f} kV")
voltage bases: 10.52 kV | 132 kV | 33 kV, Zb(line) = 174.24 ohm
vs = 1.0455 pu, zT1 = j0.1312, zline = 0.0275 + j0.1377, zT2 = j0.200
i = 0.4176 pu at -35.9 deg -> 182.6 A in the line
v_load = 0.9337 pu at -9.36 deg -> 30.81 kV
load takes 34.9 MW
in ohms: I = 182.6 A, V_load = 30.81 kV

Interactive: the per-unit circuit

The netlist lab can work directly in per unit if each reactance xx is entered as an inductor L=x/(2π⋅50)L = x/(2\pi \cdot 50): 417.5 μH417.5\ \mu\text{H} for T1, 438.4 μH438.4\ \mu\text{H} for the line, 636.6 μH636.6\ \mu\text{H} for T2 and 3.183 mH3.183\ \text{mH} for the load's j1j1; a "volt" is then a per-unit voltage and an "ampere" a per-unit current. Its plot sweeps frequency, so read the values at the 50 Hz50\ \text{Hz} cursor: the load bus c reads 933.7 mV∠−9.4∘933.7\ \text{mV}\angle -9.4^\circ (that is 0.9337 pu0.9337\ \text{pu}), the current 417.6 mA∠−35.9∘417.6\ \text{mA}\angle -35.9^\circ (0.4176 pu0.4176\ \text{pu}) and the 132 kV132\ \text{kV} sending end h 1.014 pu1.014\ \text{pu}. Slide the load resistance RD down (more load) and watch the voltage profile sag.

0.00.51.0100m1101001k10kf (Hz)|V| (V)|V(c)||V(h)|phasors at f = 50.00 Hz (magnitude @ phase)V(s)1.05 V @ 0.0 degV(h)1.01 V @ -2.5 degV(m)1.00 V @ -2.1 degV(r)974 mV @ -5.0 degV(c)934 mV @ -9.4 degV(x)418 mV @ 54.1 degI(V1)418 mA @ 144.1 degI(LT1)418 mA @ -35.9 degI(RL1)418 mA @ -35.9 degI(LL1)418 mA @ -35.9 degI(LT2)418 mA @ -35.9 degI(RD)418 mA @ -35.9 degI(LD)418 mA @ -35.9 deg

Guided lab: a two-zone resistor network in per unit

Hand calculation. On the bench, a "network" of resistors with two voltage zones needs a transformer, so use per unit the other way round: take a per-unit circuit and scale it to bench values. Choose 1 pu=5 V1\ \text{pu} = 5\ \text{V} and Zb=100 ΩZ_b = 100\ \Omega (Ib=50 mAI_b = 50\ \text{mA}). A per-unit chain of 0.10.1, 0.150.15 and a load of 2 pu2\ \text{pu} becomes 1010, 1515 and 200 Ω200\ \Omega from a 5 V5\ \text{V} DC source (resistive only).

Simulation. Compute the per-unit load voltage, 2/2.25=0.889 pu2/2.25 = 0.889\ \text{pu}, and convert: 4.44 V4.44\ \text{V}, current 0.444 pu=22.2 mA0.444\ \text{pu} = 22.2\ \text{mA}.

What you would measure. With a current-limited bench supply at 5.00 V5.00\ \text{V} (limit 100 mA100\ \text{mA}) and 1 % resistors, a DMM would read 4.44 V4.44\ \text{V} within about ±0.03 V\pm 0.03\ \text{V} (resistor tolerance dominates) and 22.2 mA22.2\ \text{mA} within about ±0.3 mA\pm 0.3\ \text{mA}.

Hazards and safe setup. 5 V5\ \text{V}, current limit set first; the resistors dissipate at most 0.1 W0.1\ \text{W}.

Pitfalls

  • Using the system nominal voltage instead of the zone base carried through the nameplate ratio. The generator zone here is 10.52 kV10.52\ \text{kV}, not 11 kV11\ \text{kV}; the source is 1.0455 pu1.0455\ \text{pu}, not 1.01.0.
  • Rebasing a transformer impedance with voltages from different sides. Use rated and base voltages on the same side.
  • Forgetting line impedances are in ohms. Divide by the zone's ZbZ_b; never rebase them with the transformer formula.
  • Constant-impedance versus constant-power loads. They give different answers when the voltage is off nominal.

Practice

  1. A 60 MVA60\ \text{MVA}, 13.8 kV13.8\ \text{kV} generator has xd′′=0.20x''_d = 0.20. Express it on 100 MVA100\ \text{MVA} and a 13.2 kV13.2\ \text{kV} base.
  2. On 100 MVA100\ \text{MVA}, 132 kV132\ \text{kV}, what is ZbZ_b, and what is a 35 Ω35\ \Omega reactance in per unit?
  3. In the worked example, by what ratio must T2's tap change to bring the load to 33 kV33\ \text{kV}? (Ignore the change in current.)
Answer
  1. 0.20⋅(100/60)(13.8/13.2)2=0.364 pu0.20 \cdot (100/60)(13.8/13.2)^2 = 0.364\ \text{pu}.
  2. Zb=174.24 ΩZ_b = 174.24\ \Omega; x=35/174.24=0.201 pux = 35/174.24 = 0.201\ \text{pu}.
  3. About 1/0.9337=1.0711/0.9337 = 1.071: roughly 7 %7\ \% more LV turns (or fewer HV turns); in practice slightly more, since the current rises with the voltage.

Test yourself

The voltage base of a zone is carried through a transformer in the ratio of…

  1. the system nominal voltages
  2. the transformer's nameplate voltages
  3. the actual measured voltages
  4. the square root of 3

A 50 MVA transformer has x = 10 %. On a 100 MVA base (same voltage) it is…

  1. 0.05 pu
  2. 0.10 pu
  3. 0.20 pu
  4. 0.50 pu

A load of 0.6 + j0.8 pu at 1 pu voltage, as a constant impedance, is…

  1. 0.6 + j0.8 pu
  2. 0.6 - j0.8 pu
  3. 1/(0.6 - j0.8) = 0.6 + j0.8 pu
  4. 1/(0.6 + j0.8) = 0.6 - j0.8 pu

Why does a loop of transformers sometimes leave an off-nominal ratio in per unit?

  1. Per unit only works for radial networks
  2. Bases carried round the loop through different nameplate ratios may disagree
  3. Transformers in loops have no impedance
  4. The power base changes