Reactive Power and Voltage: How P and Q Flow
A transmission operator sees the voltage at a substation sag on a hot afternoon. Pushing more active power into the line from the far end barely helps; switching in a capacitor bank at the substation fixes it within seconds. Why is voltage so tightly tied to reactive power, and active power to the angle between the ends of a line? The answer comes from one phasor equation for a line whose reactance is much larger than its resistance, and it decides how every grid is operated: frequency and angles are managed with active power, voltages with reactive power.
Safety. Everything in this lesson concerns transmission and distribution networks at to . It is studied by calculation and simulation only. The bench analogue at the end uses a function generator at a few volts.
Complex power itself (the power triangle, , power factor) is in Complex Power, Power Factor and Correction; the generator's own power-angle curve is in Synchronous Phasor Diagrams and the Power-Angle Curve. Here the same ideas are applied to a line between two buses.
Two buses and a line
Bus 2 is the reference, , and the sending voltage leads by the power angle : . For a line whose resistance can be neglected (, true for high-voltage overhead lines, where is typically 5 to 15), the power arriving at bus 2 is
Read the two lines separately:
- Active power follows the angle. is proportional to and reaches its maximum at , the steady-state limit of the line. Normal operating angles across a line are well below .
- Reactive power follows the voltage difference. For small , and : reactive power flows from the higher voltage to the lower one, and to raise you must supply reactive power at bus 2 (or raise ).
The voltage-drop approximation
With resistance included, the drop along the line is , and with for a load at bus 2:
The real part is the in-phase drop, which sets the magnitude difference; the imaginary part is the quadrature drop, which mostly sets the angle. So
On a transmission line , so and : Q moves voltage, P moves angle. On a low-voltage cable is comparable to or larger than , and active power drops voltage just as much: that is why rooftop solar can push LV feeder voltages up (Distribution Systems).
The reactive power consumed by the line is , and its series resistance burns . Reactive power cannot be sent far: carrying it raises the current, so it costs both losses and voltage drop. Grids therefore produce reactive power close to where it is used, with generators' excitation, capacitor banks and compensators (Voltage Control).
Worked example: a loaded line in per unit
Given: a line with (on , ; line 1–3 of the course network N4), receiving end held at with a load of (, ).
Find: the sending-end voltage and angle , the line losses, and compare with the approximation.
Solve:
The line absorbs and . The approximation gives against the exact , and against .
Check: two thirds of the drop () comes from the of reactive power, although the load's active power is twice as large. Supply that locally at bus 2 and the drop shrinks to about . In kilovolts the sending end is at .
In Python: exact against approximate, and the – and – curves
import numpy as np
z = 0.02 + 0.08j # line impedance, pu
V2 = 1.0
for P, Q in [(1.0, 0.5), (1.0, 0.0), (0.0, 0.5), (1.5, 0.6)]:
I = np.conj((P + 1j * Q) / V2)
V1 = V2 + z * I
dV_exact = abs(V1) - V2
dV_apx = (z.real * P + z.imag * Q) / V2
d_exact = np.degrees(np.angle(V1))
d_apx = np.degrees((z.imag * P - z.real * Q) / V2**2)
loss = abs(I) ** 2 * z
print(f"P={P:.1f} Q={Q:.1f}: |V1|={abs(V1):.4f} dV {dV_exact:.4f} (apx {dV_apx:.4f}) "
f"delta {d_exact:.2f} (apx {d_apx:.2f}) deg loss {loss.real:.4f}+j{loss.imag:.4f}")
# Lossless line, V1 = V2 = 1 pu, X = 0.08: P and Q2 against the angle
X = 0.08
for d in [5, 10, 30, 60, 90]:
r = np.radians(d)
print(f"delta {d:2d} deg: P = {np.sin(r)/X:6.3f} pu, Q2 = {(np.cos(r)-1)/X:7.3f} pu")P=1.0 Q=0.5: |V1|=1.0623 dV 0.0623 (apx 0.0600) delta 3.78 (apx 4.01) deg loss 0.0250+j0.1000
P=1.0 Q=0.0: |V1|=1.0231 dV 0.0231 (apx 0.0200) delta 4.48 (apx 4.58) deg loss 0.0200+j0.0800
P=0.0 Q=0.5: |V1|=1.0400 dV 0.0400 (apx 0.0400) delta -0.55 (apx -0.57) deg loss 0.0050+j0.0200
P=1.5 Q=0.6: |V1|=1.0834 dV 0.0834 (apx 0.0780) delta 5.72 (apx 6.19) deg loss 0.0522+j0.2088
delta 5 deg: P = 1.089 pu, Q2 = -0.048 pu
delta 10 deg: P = 2.171 pu, Q2 = -0.190 pu
delta 30 deg: P = 6.250 pu, Q2 = -1.675 pu
delta 60 deg: P = 10.825 pu, Q2 = -6.250 pu
delta 90 deg: P = 12.500 pu, Q2 = -12.500 pu
The last five lines are the lossless line with equal end voltages: grows with up to at , while the receiving end has to supply reactive power ( means bus 2 injects it into the line) that grows fast with the angle, because a heavily loaded line absorbs .
Interactive: change the load's reactive power
The netlist lab works in per unit at : the source is , the line is in series with , and the load is ( at ) in parallel with an inductor LL whose reactance sets : is , i.e. . The lab sweeps frequency on its plot; read only the values at the cursor. At the default the receiving node r shows at (the worked example, with the angle measured from this time). Slide LL down to (about of reactive load at the lower voltage) and r falls to ; slide it up to (almost no reactive load) and r rises to , while the angle hardly moves ( to ).
Guided lab: the Q–V link on a signal-level line
Hand calculation. Build the same circuit scaled to the bench: is and . The line becomes and a inductor ( at , close to ), the load in parallel with a choke near (). Predict with the choke (the per-unit circuit gives ), without it.
Simulation. Change the netlist values to your real component values (measure the inductors' resistance with a DMM and add it to the series ) and rerun the Python cell.
What you would measure. A function generator set to rms at (or a few hundred hertz with the inductances scaled down), and a true-rms DMM across the load: expect the predicted ratios within about , limited by the inductors' tolerance (often ) and their resistance. Disconnecting the choke raises the load voltage; disconnecting the resistor instead changes it much less. A two-channel scope shows the small phase shift.
Hazards and safe setup. Function generator output only, a few volts and tens of milliamperes; no mains-powered transformer or variac. Inductors store little energy at this level, but do not break the current of a large choke by hand at higher currents.
Pitfalls
- Sign of Q at the receiving end. Decide whether is the power arriving from the line or injected by the bus, and state it. In the formula above, negative means bus 2 supplies reactive power to the line.
- Using on low-voltage cables. There is not negligible and dominates.
- Pushing reactive power far. Raising the sending-end voltage to cover a remote reactive load costs losses and quickly runs into the sending-end voltage limit (typically to ).
- Mixing angle units. is in radians.
Practice
- A lossless line with links two buses held at . What is the largest power it can carry, and the angle for ?
- A load of is fed through with . Estimate the drop, then find the exact .
- In problem 2, how much reactive power at bus 2 makes and equal (approximately)?
Answer
- ; , .
- . Exact: , at .
- when : , so the bus must supply the load's plus : a source of reactive power (a capacitor bank of about on ).
Test yourself
On a high-voltage line with , the voltage magnitude difference between the ends is mainly set by…
- the active power flow
- the reactive power flow
- the frequency
- the line's charging current only
The active power across a lossless line is . Its theoretical maximum is reached at…
A line carries through . How much reactive power does it absorb?
- 0.12 pu
- 0.144 pu
- 1.2 pu
- 12 pu
Why are capacitor banks placed near loads rather than at the power station?
- capacitors only work at low voltage
- sending reactive power over lines raises current, losses and voltage drop
- generators cannot produce reactive power
- it lowers the frequency