A transmission operator sees the voltage at a substation sag on a hot afternoon. Pushing more active power into the line from the far end barely helps; switching in a capacitor bank at the substation fixes it within seconds. Why is voltage so tightly tied to reactive power, and active power to the angle between the ends of a line? The answer comes from one phasor equation for a line whose reactance is much larger than its resistance, and it decides how every grid is operated: frequency and angles are managed with active power, voltages with reactive power.

Safety. Everything in this lesson concerns transmission and distribution networks at 11 kV11\ \text{kV} to 400 kV400\ \text{kV}. It is studied by calculation and simulation only. The bench analogue at the end uses a function generator at a few volts.

Complex power itself (the power triangle, S=VI∗S = VI^*, power factor) is in Complex Power, Power Factor and Correction; the generator's own power-angle curve is in Synchronous Phasor Diagrams and the Power-Angle Curve. Here the same ideas are applied to a line between two buses.

Two buses and a line

bus 1bus 2 V1 at angle deltaV2 at angle 0 R jX I load P + jQ S12S21

Bus 2 is the reference, V2=V2∠0\mathbf{V}_2 = V_2\angle 0, and the sending voltage leads by the power angle δ\delta: V1=V1∠δ\mathbf{V}_1 = V_1\angle\delta. For a line whose resistance can be neglected (R≪XR \ll X, true for high-voltage overhead lines, where X/RX/R is typically 5 to 15), the power arriving at bus 2 is

P=V1V2Xsin⁡δQ2=V1V2cos⁡δ−V22X\begin{aligned} P &= \frac{V_1 V_2}{X}\sin\delta \\ Q_2 &= \frac{V_1 V_2 \cos\delta - V_2^2}{X} \end{aligned}

Read the two lines separately:

  • Active power follows the angle. PP is proportional to sin⁡δ\sin\delta and reaches its maximum V1V2/XV_1V_2/X at δ=90∘\delta = 90^\circ, the steady-state limit of the line. Normal operating angles across a line are well below 30∘30^\circ.
  • Reactive power follows the voltage difference. For small δ\delta, cos⁡δ≈1\cos\delta \approx 1 and Q2≈V2(V1−V2)/XQ_2 \approx V_2(V_1 - V_2)/X: reactive power flows from the higher voltage to the lower one, and to raise V2V_2 you must supply reactive power at bus 2 (or raise V1V_1).

The voltage-drop approximation

With resistance included, the drop along the line is V1−V2=(R+jX)I\mathbf{V}_1 - \mathbf{V}_2 = (R + jX)\mathbf{I}, and with I=(P−jQ)/V2\mathbf{I} = (P - jQ)/V_2 for a load P+jQP + jQ at bus 2:

V1−V2=RP+XQV2+j XP−RQV2\mathbf{V}_1 - \mathbf{V}_2 = \frac{RP + XQ}{V_2} + j\,\frac{XP - RQ}{V_2}

The real part is the in-phase drop, which sets the magnitude difference; the imaginary part is the quadrature drop, which mostly sets the angle. So

ΔV≈RP+XQV2,δ≈XP−RQV22\Delta V \approx \frac{RP + XQ}{V_2}, \qquad \delta \approx \frac{XP - RQ}{V_2^2}

On a transmission line X≫RX \gg R, so ΔV≈XQ/V\Delta V \approx XQ/V and δ≈XP/V2\delta \approx XP/V^2: Q moves voltage, P moves angle. On a low-voltage cable RR is comparable to or larger than XX, and active power drops voltage just as much: that is why rooftop solar can push LV feeder voltages up (Distribution Systems).

The reactive power consumed by the line is I2XI^2X, and its series resistance burns I2RI^2R. Reactive power cannot be sent far: carrying it raises the current, so it costs both losses and voltage drop. Grids therefore produce reactive power close to where it is used, with generators' excitation, capacitor banks and compensators (Voltage Control).

Worked example: a loaded line in per unit

Given: a line with z=0.02+j0.08 puz = 0.02 + j0.08\ \text{pu} (on 100 MVA100\ \text{MVA}, 132 kV132\ \text{kV}; line 1–3 of the course network N4), receiving end held at V2=1.0 puV_2 = 1.0\ \text{pu} with a load of 1.0+j0.5 pu1.0 + j0.5\ \text{pu} (100 MW100\ \text{MW}, 50 Mvar50\ \text{Mvar}).

Find: the sending-end voltage V1V_1 and angle δ\delta, the line losses, and compare with the approximation.

Solve:

I=(P+jQ)∗V2∗=1.0−j0.5 puV1=1+(0.02+j0.08)(1.0−j0.5)=1.06+j0.07=1.0623∠3.78∘ puI2z=1.25 (0.02+j0.08)=0.025+j0.100 pu\begin{aligned} \mathbf{I} &= \frac{(P + jQ)^*}{\mathbf{V}_2^*} = 1.0 - j0.5\ \text{pu} \\ \mathbf{V}_1 &= 1 + (0.02 + j0.08)(1.0 - j0.5) = 1.06 + j0.07 = 1.0623\angle 3.78^\circ\ \text{pu} \\ I^2 z &= 1.25\,(0.02 + j0.08) = 0.025 + j0.100\ \text{pu} \end{aligned}

The line absorbs 2.5 MW2.5\ \text{MW} and 10 Mvar10\ \text{Mvar}. The approximation gives ΔV≈0.02⋅1+0.08⋅0.5=0.060 pu\Delta V \approx 0.02 \cdot 1 + 0.08 \cdot 0.5 = 0.060\ \text{pu} against the exact 0.0623 pu0.0623\ \text{pu}, and δ≈0.08−0.01=0.070 rad=4.0∘\delta \approx 0.08 - 0.01 = 0.070\ \text{rad} = 4.0^\circ against 3.78∘3.78^\circ.

Check: two thirds of the 0.06 pu0.06\ \text{pu} drop (0.040.04) comes from the 0.5 pu0.5\ \text{pu} of reactive power, although the load's active power is twice as large. Supply that 50 Mvar50\ \text{Mvar} locally at bus 2 and the drop shrinks to about 0.02 pu0.02\ \text{pu}. In kilovolts the sending end is at 1.0623⋅132=140.2 kV1.0623 \cdot 132 = 140.2\ \text{kV}.

In Python: exact against approximate, and the PP–δ\delta and QQ–VV curves

python · try it yourself
import numpy as np

z = 0.02 + 0.08j                      # line impedance, pu
V2 = 1.0
for P, Q in [(1.0, 0.5), (1.0, 0.0), (0.0, 0.5), (1.5, 0.6)]:
    I = np.conj((P + 1j * Q) / V2)
    V1 = V2 + z * I
    dV_exact = abs(V1) - V2
    dV_apx = (z.real * P + z.imag * Q) / V2
    d_exact = np.degrees(np.angle(V1))
    d_apx = np.degrees((z.imag * P - z.real * Q) / V2**2)
    loss = abs(I) ** 2 * z
    print(f"P={P:.1f} Q={Q:.1f}: |V1|={abs(V1):.4f}  dV {dV_exact:.4f} (apx {dV_apx:.4f})  "
          f"delta {d_exact:.2f} (apx {d_apx:.2f}) deg  loss {loss.real:.4f}+j{loss.imag:.4f}")

# Lossless line, V1 = V2 = 1 pu, X = 0.08: P and Q2 against the angle
X = 0.08
for d in [5, 10, 30, 60, 90]:
    r = np.radians(d)
    print(f"delta {d:2d} deg: P = {np.sin(r)/X:6.3f} pu, Q2 = {(np.cos(r)-1)/X:7.3f} pu")
P=1.0 Q=0.5: |V1|=1.0623  dV 0.0623 (apx 0.0600)  delta 3.78 (apx 4.01) deg  loss 0.0250+j0.1000
P=1.0 Q=0.0: |V1|=1.0231  dV 0.0231 (apx 0.0200)  delta 4.48 (apx 4.58) deg  loss 0.0200+j0.0800
P=0.0 Q=0.5: |V1|=1.0400  dV 0.0400 (apx 0.0400)  delta -0.55 (apx -0.57) deg  loss 0.0050+j0.0200
P=1.5 Q=0.6: |V1|=1.0834  dV 0.0834 (apx 0.0780)  delta 5.72 (apx 6.19) deg  loss 0.0522+j0.2088
delta  5 deg: P =  1.089 pu, Q2 =  -0.048 pu
delta 10 deg: P =  2.171 pu, Q2 =  -0.190 pu
delta 30 deg: P =  6.250 pu, Q2 =  -1.675 pu
delta 60 deg: P = 10.825 pu, Q2 =  -6.250 pu
delta 90 deg: P = 12.500 pu, Q2 = -12.500 pu

The last five lines are the lossless line with equal end voltages: PP grows with sin⁡δ\sin\delta up to 12.5 pu12.5\ \text{pu} at 90∘90^\circ, while the receiving end has to supply reactive power (Q2<0Q_2 < 0 means bus 2 injects it into the line) that grows fast with the angle, because a heavily loaded line absorbs I2XI^2X.

Interactive: change the load's reactive power

The netlist lab works in per unit at 50 Hz50\ \text{Hz}: the source is V1=1.0623 puV_1 = 1.0623\ \text{pu}, the line is R=0.02 ΩR = 0.02\ \Omega in series with L=0.08/(2π⋅50)=254.6 μHL = 0.08/(2\pi \cdot 50) = 254.6\ \mu\text{H}, and the load is 1 Ω1\ \Omega (P=1 puP = 1\ \text{pu} at 1 pu1\ \text{pu}) in parallel with an inductor LL whose reactance sets QQ: 6.366 mH6.366\ \text{mH} is X=2 ΩX = 2\ \Omega, i.e. Q=0.5 puQ = 0.5\ \text{pu}. The lab sweeps frequency on its plot; read only the values at the 50 Hz50\ \text{Hz} cursor. At the default the receiving node r shows 1.000 pu1.000\ \text{pu} at −3.78∘-3.78^\circ (the worked example, with the angle measured from V1V_1 this time). Slide LL down to 3.183 mH3.183\ \text{mH} (about 0.93 pu0.93\ \text{pu} of reactive load at the lower voltage) and r falls to 0.964 pu0.964\ \text{pu}; slide it up to 63.66 mH63.66\ \text{mH} (almost no reactive load) and r rises to 1.034 pu1.034\ \text{pu}, while the angle hardly moves (−3.1∘-3.1^\circ to −4.4∘-4.4^\circ).

0.00.51.0100m1101001k10kf (Hz)|V| (V)|V(r)||V(s)|phasors at f = 50.00 Hz (magnitude @ phase)V(s)1.06 V @ 0.0 degV(m)1.04 V @ 0.6 degV(r)1.00 V @ -3.8 degI(V1)1.12 A @ 149.7 degI(R1)1.12 A @ -30.3 degI(L1)1.12 A @ -30.3 degI(RL)1.00 A @ -3.8 degI(LL)500 mA @ -93.8 deg

Guided lab: the Q–V link on a signal-level line

Hand calculation. Build the same circuit scaled to the bench: 1 V1\ \text{V} is 1 pu1\ \text{pu} and Zb=100 ΩZ_b = 100\ \Omega. The line becomes 2 Ω2\ \Omega and a 25 mH25\ \text{mH} inductor (X=7.9 ΩX = 7.9\ \Omega at 50 Hz50\ \text{Hz}, close to 0.08 pu0.08\ \text{pu}), the load 100 Ω100\ \Omega in parallel with a choke near 0.64 H0.64\ \text{H} (200 Ω200\ \Omega). Predict V2/V1=0.942V_2/V_1 = 0.942 with the choke (the per-unit circuit gives 1/1.0623=0.9411/1.0623 = 0.941), 0.9770.977 without it.

Simulation. Change the netlist values to your real component values (measure the inductors' resistance with a DMM and add it to the series RR) and rerun the Python cell.

What you would measure. A function generator set to 1.06 V1.06\ \text{V} rms at 50 Hz50\ \text{Hz} (or a few hundred hertz with the inductances scaled down), and a true-rms DMM across the load: expect the predicted ratios within about ±2 %\pm 2\ \%, limited by the inductors' tolerance (often ±10 %\pm 10\ \%) and their resistance. Disconnecting the choke raises the load voltage; disconnecting the 100 Ω100\ \Omega resistor instead changes it much less. A two-channel scope shows the small phase shift.

Hazards and safe setup. Function generator output only, a few volts and tens of milliamperes; no mains-powered transformer or variac. Inductors store little energy at this level, but do not break the current of a large choke by hand at higher currents.

Pitfalls

  • Sign of Q at the receiving end. Decide whether Q2Q_2 is the power arriving from the line or injected by the bus, and state it. In the formula above, negative Q2Q_2 means bus 2 supplies reactive power to the line.
  • Using ΔV≈XQ/V\Delta V \approx XQ/V on low-voltage cables. There RR is not negligible and RPRP dominates.
  • Pushing reactive power far. Raising the sending-end voltage to cover a remote reactive load costs losses and quickly runs into the sending-end voltage limit (typically 1.051.05 to 1.10 pu1.10\ \text{pu}).
  • Mixing angle units. δ≈XP/V2\delta \approx XP/V^2 is in radians.

Practice

  1. A lossless line with X=0.25 puX = 0.25\ \text{pu} links two buses held at 1.0 pu1.0\ \text{pu}. What is the largest power it can carry, and the angle for 1.5 pu1.5\ \text{pu}?
  2. A load of 0.8+j0.6 pu0.8 + j0.6\ \text{pu} is fed through z=0.01+j0.1 puz = 0.01 + j0.1\ \text{pu} with V2=1.0 puV_2 = 1.0\ \text{pu}. Estimate the drop, then find the exact V1V_1.
  3. In problem 2, how much reactive power at bus 2 makes ∣V1∣\lvert V_1 \rvert and ∣V2∣\lvert V_2 \rvert equal (approximately)?
Answer
  1. Pmax=1/0.25=4.0 puP_\text{max} = 1/0.25 = 4.0\ \text{pu}; sin⁡δ=1.5⋅0.25=0.375\sin\delta = 1.5 \cdot 0.25 = 0.375, δ=22.0∘\delta = 22.0^\circ.
  2. ΔV≈0.01⋅0.8+0.1⋅0.6=0.068 pu\Delta V \approx 0.01 \cdot 0.8 + 0.1 \cdot 0.6 = 0.068\ \text{pu}. Exact: V1=1+(0.01+j0.1)(0.8−j0.6)=1.068+j0.074\mathbf{V}_1 = 1 + (0.01 + j0.1)(0.8 - j0.6) = 1.068 + j0.074, ∣V1∣=1.0706 pu\lvert V_1 \rvert = 1.0706\ \text{pu} at 3.96∘3.96^\circ.
  3. ΔV≈0\Delta V \approx 0 when RP+XQ=0RP + XQ = 0: Q=−0.01⋅0.8/0.1=−0.08 puQ = -0.01 \cdot 0.8/0.1 = -0.08\ \text{pu}, so the bus must supply the load's 0.60.6 plus 0.080.08: a 0.68 pu0.68\ \text{pu} source of reactive power (a capacitor bank of about 68 Mvar68\ \text{Mvar} on 100 MVA100\ \text{MVA}).

Test yourself

On a high-voltage line with X≫RX \gg R, the voltage magnitude difference between the ends is mainly set by…

  1. the active power flow
  2. the reactive power flow
  3. the frequency
  4. the line's charging current only

The active power across a lossless line is P=V1V2sin⁡δ/XP = V_1V_2\sin\delta/X. Its theoretical maximum is reached at…

  1. δ=0∘\delta = 0^\circ
  2. δ=30∘\delta = 30^\circ
  3. δ=90∘\delta = 90^\circ
  4. δ=180∘\delta = 180^\circ

A line carries I=1.2 puI = 1.2\ \text{pu} through X=0.1 puX = 0.1\ \text{pu}. How much reactive power does it absorb?

  1. 0.12 pu
  2. 0.144 pu
  3. 1.2 pu
  4. 12 pu

Why are capacitor banks placed near loads rather than at the power station?

  1. capacitors only work at low voltage
  2. sending reactive power over lines raises current, losses and voltage drop
  3. generators cannot produce reactive power
  4. it lowers the frequency