Symmetrical Faults: Thevenin at the Fault and the DC Offset

A tree falls across all three conductors of a 132 kV132\ \text{kV} line, or an excavator cuts a cable: the impedance between the phases collapses and the current jumps to many times its normal value within a few milliseconds. Circuit breakers must be able to make and break that current, busbars and cables must survive its heating and magnetic forces, and protection relays must recognise it. Calculating fault currents is therefore one of the first studies for any new plant or substation. The three-phase (symmetrical) fault is the simplest to calculate, because the network stays balanced and one phase of the positive-sequence circuit tells the whole story. It is not the most common fault (single line-to-ground faults are, see Unsymmetrical Faults), but it is often among the most severe and it sets many equipment ratings.

Safety. Fault currents in power systems are tens of kiloamperes; the arc energy can kill at a distance (Surges, Insulation Coordination and Arc Flash). Everything here is calculation and simulation only; the bench lab uses a function generator and a small inductor.

Thevenin at the fault point

Just before the fault the network carries its normal load, and the voltage at the fault point F is VF0\mathbf{V}_F^0 (from a load flow, or taken as 1.0 pu1.0\ \text{pu}). A bolted fault forces VF=0\mathbf{V}_F = 0. By superposition the post-fault state is the prefault state plus the response of the dead network (all sources shorted) to a source −VF0-\mathbf{V}_F^0 applied at F. That response is fixed by the Thevenin impedance ZthZ_\text{th} seen from F (Thevenin and Norton):

IF=VF0Zth+ZF\mathbf{I}_F = \frac{\mathbf{V}_F^0}{Z_\text{th} + Z_F}

with ZFZ_F the fault impedance (zero for a bolted fault). The change in every other bus voltage and branch current follows from the same dead network. Load currents are usually small next to fault currents and are often neglected, together with the prefault angle differences: all generator EMFs equal to 1.0 pu1.0\ \text{pu} in phase.

Which generator reactance? A synchronous machine's current does not stay constant after a fault. The flux trapped in its damper windings and field first holds the current high: the subtransient reactance Xd′′X_d'' applies for the first few cycles, then the transient reactance Xd′X_d' for about a second, and finally the synchronous reactance XdX_d (Synchronous Machines: EMF and Synchronous Reactance). Breaker interrupting duty and relay settings use Xd′′X_d'' or Xd′X_d' according to the time of interest; steady-state fault current with XdX_d is small and matters mainly for slow back-up protection.

The DC offset

Each phase of the fault loop is an RL circuit driven by a sinusoid. Closing it at time zero with v=2Vsin⁡(ωt+α)v = \sqrt{2}V\sin(\omega t + \alpha) gives (RL First-Order Circuits):

i(t)=2V∣Z∣[sin⁡(ωt+α−φ)−sin⁡(α−φ) e−t/τ],φ=arctan⁡XR, τ=LRi(t) = \frac{\sqrt{2}V}{\lvert Z \rvert}\Big[ \sin(\omega t + \alpha - \varphi) - \sin(\alpha - \varphi)\,e^{-t/\tau} \Big], \qquad \varphi = \arctan\frac{X}{R},\ \tau = \frac{L}{R}

The current must start from zero, so a decaying DC component appears unless the fault strikes exactly when α=φ\alpha = \varphi. For a highly inductive circuit (φ\varphi near 90∘90^\circ), a fault at a voltage zero (α=0\alpha = 0) gives almost the full offset, and the first peak approaches twice the AC peak. IEC 60909-0:2016 expresses the first peak as ip=κ2Ik′′i_p = \kappa\sqrt{2}I_k'' with

κ=1.02+0.98 e−3R/X\kappa = 1.02 + 0.98\,e^{-3R/X}

which is 1.7461.746 for X/R=10X/R = 10 and approaches 22 for large X/RX/R. In a three-phase fault the three phases close at angles 120∘120^\circ apart, so at least one phase always has a large offset. The peak current sets the making capacity of breakers and the mechanical forces on busbars.

~G1, X''d 0.18 T1, x 0.10 bus H, 132 kV line, x 0.40line, x 0.40grid F 1.0 pu j0.1167F shorted

Worked example: a fault on the 132 kV bus of Plant P1

Given: Plant P1: G1 100 MVA100\ \text{MVA}, 11 kV11\ \text{kV}, Xd′′=0.18 puX_d'' = 0.18\ \text{pu}; T1 100 MVA100\ \text{MVA}, 11/132 kV11/132\ \text{kV}, x=0.10 pux = 0.10\ \text{pu}; two 132 kV132\ \text{kV} circuits of x=0.40 pux = 0.40\ \text{pu} each to an infinite bus; all on 100 MVA100\ \text{MVA}. Prefault voltage 1.0 pu1.0\ \text{pu}, no load. Bolted three-phase fault at bus H.

Find: the initial symmetrical fault current, each side's contribution and the fault level.

Solve:

Zth=j(0.18+0.10)∥j0.402=j0.28⋅0.200.48=j0.1167 puIF=1.00.1167=8.571 pu,Ib=100×106 VA3⋅132 kV=437.4 AIF=8.571⋅437.4 A=3.749 kA,SF=8.571⋅100 MVA=857 MVA\begin{aligned} Z_\text{th} &= j(0.18 + 0.10) \parallel j\frac{0.40}{2} = j\frac{0.28 \cdot 0.20}{0.48} = j0.1167\ \text{pu} \\ I_F &= \frac{1.0}{0.1167} = 8.571\ \text{pu}, \qquad I_b = \frac{100 \times 10^6\ \text{VA}}{\sqrt{3} \cdot 132\ \text{kV}} = 437.4\ \text{A} \\ I_F &= 8.571 \cdot 437.4\ \text{A} = 3.749\ \text{kA}, \qquad S_F = 8.571 \cdot 100\ \text{MVA} = 857\ \text{MVA} \end{aligned}

The generator supplies 1/0.28=3.571 pu1/0.28 = 3.571\ \text{pu} and the grid 1/0.20=5.000 pu1/0.20 = 5.000\ \text{pu}.

Check: the contributions add to 8.571 pu8.571\ \text{pu} (both are pure reactive currents, so they add arithmetically). The infinite bus supplies the larger share because its path has the lower reactance. As the generator's current decays toward its transient and synchronous values, the fault current falls to 7.507.50 and 5.59 pu5.59\ \text{pu}; the grid's share does not decay, because an infinite bus has no machine dynamics.

In Python: contributions and the generator decrement

python · try it yourself
import numpy as np
import matplotlib.pyplot as plt

Sb, Vhv, Vlv = 100e6, 132e3, 11e3                     # Plant P1 bases
Ib_hv = Sb / (np.sqrt(3) * Vhv)
Ib_lv = Sb / (np.sqrt(3) * Vlv)
print(f"base currents: {Ib_hv:.1f} A at 132 kV, {Ib_lv:.0f} A at 11 kV")

# 1) three-phase fault on the 132 kV bus H: Thevenin at the fault
xg = {"subtransient": 0.18, "transient": 0.30, "synchronous": 1.6}
xt, xline = 0.10, 0.40
x_grid = xline / 2                                     # two circuits in parallel to the infinite bus
for name, x in xg.items():
    zgen = x + xt
    zth = zgen * x_grid / (zgen + x_grid)
    If = 1.0 / zth                                     # prefault voltage 1.0 pu
    print(f"{name:12s}: Zth = j{zth:.4f} pu, If = {If:.3f} pu = {If*Ib_hv/1e3:.3f} kA, "
          f"from G1 {1/zgen:.3f} pu, from grid {1/x_grid:.3f} pu, {If*100:.0f} MVA")

# 2) unloaded G1 shorted at its terminals: the AC envelope decays from subtransient to steady state
Xdpp, Xdp, Xd = 0.18, 0.30, 1.6
Tdpp, Tdp, Ta = 0.035, 1.0, 0.25                     # time constants (s), typical values
t = np.linspace(0, 0.3, 3001)
iac = (1/Xdpp - 1/Xdp) * np.exp(-t/Tdpp) + (1/Xdp - 1/Xd) * np.exp(-t/Tdp) + 1/Xd
w = 2 * np.pi * 50
i_a = np.sqrt(2) * (iac * np.cos(w*t) - (1/Xdpp) * np.exp(-t/Ta))   # phase with the largest offset
for tt in [0.0, 0.05, 0.1, 0.3]:
    k = int(round(tt / 0.0001))
    print(f"t = {tt:4.2f} s: AC rms {iac[k]:.3f} pu = {iac[k]*Ib_lv/1e3:.1f} kA")
print(f"largest instantaneous current: {abs(i_a).max():.2f} pu = {abs(i_a).max()*Ib_lv/1e3:.1f} kA (first half-cycle)")

plt.plot(t*1e3, i_a, lw=1, label="phase current (fully offset)")
plt.plot(t*1e3, np.sqrt(2)*iac, "--", label="AC envelope (peak)")
plt.plot(t*1e3, -np.sqrt(2)*(1/Xdpp)*np.exp(-t/Ta), ":", label="DC offset")
plt.xlabel("time after the fault (ms)"); plt.ylabel("current (pu of 5249 A rms base)")
plt.title("G1 terminal short circuit"); plt.legend(); plt.grid(alpha=0.3)
plt.show()
base currents: 437.4 A at 132 kV, 5249 A at 11 kV
subtransient: Zth = j0.1167 pu, If = 8.571 pu = 3.749 kA, from G1 3.571 pu, from grid 5.000 pu, 857 MVA
transient   : Zth = j0.1333 pu, If = 7.500 pu = 3.280 kA, from G1 2.500 pu, from grid 5.000 pu, 750 MVA
synchronous : Zth = j0.1789 pu, If = 5.588 pu = 2.444 kA, from G1 0.588 pu, from grid 5.000 pu, 559 MVA
t = 0.00 s: AC rms 5.556 pu = 29.2 kA
t = 0.05 s: AC rms 3.734 pu = 19.6 kA
t = 0.10 s: AC rms 3.203 pu = 16.8 kA
t = 0.30 s: AC rms 2.632 pu = 13.8 kA
largest instantaneous current: 14.59 pu = 76.6 kA (first half-cycle)

The second part shorts the unloaded generator at its own 11 kV11\ \text{kV} terminals (typical time constants Td′′=35 msT_d'' = 35\ \text{ms}, Td′=1.0 sT_d' = 1.0\ \text{s}, armature Ta=0.25 sT_a = 0.25\ \text{s}): the AC component starts at 5.56 pu5.56\ \text{pu} (29 kA29\ \text{kA}) and has fallen by half within a few hundred milliseconds, while the DC offset pushes the first peak to nearly 77 kA77\ \text{kA}. Generator breakers are among the hardest to design for exactly this reason: the DC offset can be so large that the current has no zero crossings for several cycles.

Cross-check in SPICE: closing angle and the first peak

Two identical RL loops with X/R=10X/R = 10 (R=0.1 ΩR = 0.1\ \Omega, L=3.1831 mHL = 3.1831\ \text{mH}, X=1 ΩX = 1\ \Omega at 50 Hz50\ \text{Hz}) are driven by 1 V1\ \text{V} rms. Loop A closes at a voltage zero, loop B at a voltage peak. The steady AC peak is 2/∣Z∣=1.4072 A\sqrt{2}/\lvert Z \rvert = 1.4072\ \text{A}.

bash · try it yourself
cat > fault.cir <<'EOF'
* RL fault loop, X/R = 10 at 50 Hz: A closes at a voltage zero, B at a voltage peak
VA a 0 SIN(0 1.41421 50 0 0 0)
RA a b 0.1
LA b 0 3.1831m
VB c 0 SIN(0 1.41421 50 0 0 90)
RB c d 0.1
LB d 0 3.1831m
.control
tran 10u 60m uic
let iA = -i(VA)
let iB = -i(VB)
meas tran peakA MAX iA FROM=0 TO=20m
meas tran peakB MIN iB FROM=0 TO=20m
let ratioA = peakA / 1.40720
let ratioB = -peakB / 1.40720
print ratioA ratioB
.endc
.end
EOF
ngspice -b fault.cir 2>&1 | grep -E '^(peaka|peakb|ratioa|ratiob)'
peaka               =  2.443969e+00 at=  9.442902e-03
peakb               =  -1.495498e+00 at=  1.466290e-02
ratioa = 1.736760e+00
ratiob = 1.062747e+00

Loop A peaks at 2.444 A2.444\ \text{A} after 9.44 ms9.44\ \text{ms}, 1.7371.737 times the AC peak, close to IEC 60909's κ=1.746\kappa = 1.746 for X/R=10X/R = 10 (the standard's formula is a fit). Loop B, closed 5.7∘5.7^\circ after the "no-offset" angle φ=84.3∘\varphi = 84.3^\circ, has almost none: 1.0631.063 times.

Interactive: the offset in the netlist lab

Loop A in the netlist lab, solved from zero current at t=0t = 0. Play it, or move the time cursor: the current peaks at 2.444 A2.444\ \text{A} at 9.4 ms9.4\ \text{ms} and swings asymmetrically until the offset decays (τ=L/R=31.8 ms\tau = L/R = 31.8\ \text{ms}). Raise R1 to lower X/RX/R: at R=1 ΩR = 1\ \Omega (X/R=1X/R = 1) the offset dies within a cycle.

-101020406080100t (ms)V-2.0 A0 A2.0 AI (A)I(L1)V(a)at t = 100.0 msV(a)5.17 fVV(b)134 mVI(V1)1.34 AI(R1)-1.34 AI(L1)-1.34 A

Guided lab: DC offset at signal level

Hand calculation. Use a 10 mH10\ \text{mH} inductor (measure its resistance, typically 22 to 10 Ω10\ \Omega) with a 1 Ω1\ \Omega current shunt, driven at 500 Hz500\ \text{Hz} so that X=31.4 ΩX = 31.4\ \Omega. With Rtotal=5 ΩR_\text{total} = 5\ \Omega, X/R=6.3X/R = 6.3; predict ∣Z∣\lvert Z \rvert, φ\varphi, τ\tau and the first peak for closing at a voltage zero, and κ=1.02+0.98e−3/6.3=1.63\kappa = 1.02 + 0.98e^{-3/6.3} = 1.63.

Simulation. Put your values into the netlist (SIN at 500 Hz500\ \text{Hz}, tstop 10 ms10\ \text{ms}) or the formula above.

What you would measure. Set the function generator to burst mode (one burst of 10 cycles, 2 V2\ \text{V} peak, start phase 0∘0^\circ, then 90∘90^\circ), and look at the shunt voltage on a scope triggered by the burst. Expect the first peak about 1.61.6 times the steady peak at 0∘0^\circ and close to 1.01.0 times at 90∘90^\circ, within roughly ±5 %\pm 5\ \%: the generator's 50 Ω50\ \Omega output resistance adds to RR (include it, or use a low-impedance amplifier), and the inductor's core can be slightly nonlinear.

Hazards and safe setup. Function-generator levels only (≤5 V\le 5\ \text{V}, tens of milliamperes). Never try to "see" a fault current on mains equipment: a short circuit on a supply circuit produces an arc that can cause burns and eye injury even at 230 V230\ \text{V}.

Pitfalls

  • Using XdX_d for breaker duty. Interrupting and making duties need Xd′′X_d'' (or Xd′X_d' for delayed clearing); XdX_d underestimates them severalfold.
  • Forgetting the DC offset when checking making capacity and busbar forces: use the peak κ2Ik′′\kappa\sqrt{2}I_k'', not the rms value.
  • Adding contributions with different angles arithmetically when resistances matter: add them as phasors.
  • Prefault voltage of exactly 1.0 pu. Standards apply a voltage factor cc instead (Fault Levels and Breaker Duty).

Practice

  1. Repeat the worked example with one of the two lines out of service.
  2. What are the per-unit and kiloampere values of G1's subtransient contribution at its 11 kV11\ \text{kV} terminals in the worked example?
  3. A fault loop has X/R=20X/R = 20. Estimate the first peak as a multiple of the AC peak.
Answer
  1. Zth=0.28∥0.40=0.1647 puZ_\text{th} = 0.28 \parallel 0.40 = 0.1647\ \text{pu}; IF=6.071 pu=2.656 kAI_F = 6.071\ \text{pu} = 2.656\ \text{kA}, 607 MVA607\ \text{MVA}.
  2. 3.571 pu3.571\ \text{pu} of the 11 kV11\ \text{kV} base current 5249 A5249\ \text{A}: 18.75 kA18.75\ \text{kA} (the transformer passes the same per-unit current).
  3. κ=1.02+0.98e−0.15=1.863\kappa = 1.02 + 0.98e^{-0.15} = 1.863.

Test yourself

The fault current at a bus with prefault voltage 1.0 pu and Thevenin impedance j0.125 pu (bolted fault) is…

  1. 0.125 pu
  2. 8 pu
  3. 1.125 pu
  4. 12.5 pu

The DC offset in a fault current is largest when the fault occurs…

  1. at a voltage peak in an inductive circuit
  2. at a voltage zero in an inductive circuit
  3. in a purely resistive circuit
  4. never; it is always zero

Which generator reactance gives the largest initial fault current?

  1. XdX_d
  2. Xd′X_d'
  3. Xd′′X_d''
  4. they give the same

IEC 60909's peak factor κ\kappa for X/R=10X/R = 10 is about…

  1. 1.0
  2. 1.41
  3. 1.75
  4. 2.83