Symmetrical Faults: Thevenin at the Fault and the DC Offset
A tree falls across all three conductors of a line, or an excavator cuts a cable: the impedance between the phases collapses and the current jumps to many times its normal value within a few milliseconds. Circuit breakers must be able to make and break that current, busbars and cables must survive its heating and magnetic forces, and protection relays must recognise it. Calculating fault currents is therefore one of the first studies for any new plant or substation. The three-phase (symmetrical) fault is the simplest to calculate, because the network stays balanced and one phase of the positive-sequence circuit tells the whole story. It is not the most common fault (single line-to-ground faults are, see Unsymmetrical Faults), but it is often among the most severe and it sets many equipment ratings.
Safety. Fault currents in power systems are tens of kiloamperes; the arc energy can kill at a distance (Surges, Insulation Coordination and Arc Flash). Everything here is calculation and simulation only; the bench lab uses a function generator and a small inductor.
Thevenin at the fault point
Just before the fault the network carries its normal load, and the voltage at the fault point F is (from a load flow, or taken as ). A bolted fault forces . By superposition the post-fault state is the prefault state plus the response of the dead network (all sources shorted) to a source applied at F. That response is fixed by the Thevenin impedance seen from F (Thevenin and Norton):
with the fault impedance (zero for a bolted fault). The change in every other bus voltage and branch current follows from the same dead network. Load currents are usually small next to fault currents and are often neglected, together with the prefault angle differences: all generator EMFs equal to in phase.
Which generator reactance? A synchronous machine's current does not stay constant after a fault. The flux trapped in its damper windings and field first holds the current high: the subtransient reactance applies for the first few cycles, then the transient reactance for about a second, and finally the synchronous reactance (Synchronous Machines: EMF and Synchronous Reactance). Breaker interrupting duty and relay settings use or according to the time of interest; steady-state fault current with is small and matters mainly for slow back-up protection.
The DC offset
Each phase of the fault loop is an RL circuit driven by a sinusoid. Closing it at time zero with gives (RL First-Order Circuits):
The current must start from zero, so a decaying DC component appears unless the fault strikes exactly when . For a highly inductive circuit ( near ), a fault at a voltage zero () gives almost the full offset, and the first peak approaches twice the AC peak. IEC 60909-0:2016 expresses the first peak as with
which is for and approaches for large . In a three-phase fault the three phases close at angles apart, so at least one phase always has a large offset. The peak current sets the making capacity of breakers and the mechanical forces on busbars.
Worked example: a fault on the 132 kV bus of Plant P1
Given: Plant P1: G1 , , ; T1 , , ; two circuits of each to an infinite bus; all on . Prefault voltage , no load. Bolted three-phase fault at bus H.
Find: the initial symmetrical fault current, each side's contribution and the fault level.
Solve:
The generator supplies and the grid .
Check: the contributions add to (both are pure reactive currents, so they add arithmetically). The infinite bus supplies the larger share because its path has the lower reactance. As the generator's current decays toward its transient and synchronous values, the fault current falls to and ; the grid's share does not decay, because an infinite bus has no machine dynamics.
In Python: contributions and the generator decrement
import numpy as np
import matplotlib.pyplot as plt
Sb, Vhv, Vlv = 100e6, 132e3, 11e3 # Plant P1 bases
Ib_hv = Sb / (np.sqrt(3) * Vhv)
Ib_lv = Sb / (np.sqrt(3) * Vlv)
print(f"base currents: {Ib_hv:.1f} A at 132 kV, {Ib_lv:.0f} A at 11 kV")
# 1) three-phase fault on the 132 kV bus H: Thevenin at the fault
xg = {"subtransient": 0.18, "transient": 0.30, "synchronous": 1.6}
xt, xline = 0.10, 0.40
x_grid = xline / 2 # two circuits in parallel to the infinite bus
for name, x in xg.items():
zgen = x + xt
zth = zgen * x_grid / (zgen + x_grid)
If = 1.0 / zth # prefault voltage 1.0 pu
print(f"{name:12s}: Zth = j{zth:.4f} pu, If = {If:.3f} pu = {If*Ib_hv/1e3:.3f} kA, "
f"from G1 {1/zgen:.3f} pu, from grid {1/x_grid:.3f} pu, {If*100:.0f} MVA")
# 2) unloaded G1 shorted at its terminals: the AC envelope decays from subtransient to steady state
Xdpp, Xdp, Xd = 0.18, 0.30, 1.6
Tdpp, Tdp, Ta = 0.035, 1.0, 0.25 # time constants (s), typical values
t = np.linspace(0, 0.3, 3001)
iac = (1/Xdpp - 1/Xdp) * np.exp(-t/Tdpp) + (1/Xdp - 1/Xd) * np.exp(-t/Tdp) + 1/Xd
w = 2 * np.pi * 50
i_a = np.sqrt(2) * (iac * np.cos(w*t) - (1/Xdpp) * np.exp(-t/Ta)) # phase with the largest offset
for tt in [0.0, 0.05, 0.1, 0.3]:
k = int(round(tt / 0.0001))
print(f"t = {tt:4.2f} s: AC rms {iac[k]:.3f} pu = {iac[k]*Ib_lv/1e3:.1f} kA")
print(f"largest instantaneous current: {abs(i_a).max():.2f} pu = {abs(i_a).max()*Ib_lv/1e3:.1f} kA (first half-cycle)")
plt.plot(t*1e3, i_a, lw=1, label="phase current (fully offset)")
plt.plot(t*1e3, np.sqrt(2)*iac, "--", label="AC envelope (peak)")
plt.plot(t*1e3, -np.sqrt(2)*(1/Xdpp)*np.exp(-t/Ta), ":", label="DC offset")
plt.xlabel("time after the fault (ms)"); plt.ylabel("current (pu of 5249 A rms base)")
plt.title("G1 terminal short circuit"); plt.legend(); plt.grid(alpha=0.3)
plt.show()base currents: 437.4 A at 132 kV, 5249 A at 11 kV
subtransient: Zth = j0.1167 pu, If = 8.571 pu = 3.749 kA, from G1 3.571 pu, from grid 5.000 pu, 857 MVA
transient : Zth = j0.1333 pu, If = 7.500 pu = 3.280 kA, from G1 2.500 pu, from grid 5.000 pu, 750 MVA
synchronous : Zth = j0.1789 pu, If = 5.588 pu = 2.444 kA, from G1 0.588 pu, from grid 5.000 pu, 559 MVA
t = 0.00 s: AC rms 5.556 pu = 29.2 kA
t = 0.05 s: AC rms 3.734 pu = 19.6 kA
t = 0.10 s: AC rms 3.203 pu = 16.8 kA
t = 0.30 s: AC rms 2.632 pu = 13.8 kA
largest instantaneous current: 14.59 pu = 76.6 kA (first half-cycle)
The second part shorts the unloaded generator at its own terminals (typical time constants , , armature ): the AC component starts at () and has fallen by half within a few hundred milliseconds, while the DC offset pushes the first peak to nearly . Generator breakers are among the hardest to design for exactly this reason: the DC offset can be so large that the current has no zero crossings for several cycles.
Cross-check in SPICE: closing angle and the first peak
Two identical RL loops with (, , at ) are driven by rms. Loop A closes at a voltage zero, loop B at a voltage peak. The steady AC peak is .
cat > fault.cir <<'EOF'
* RL fault loop, X/R = 10 at 50 Hz: A closes at a voltage zero, B at a voltage peak
VA a 0 SIN(0 1.41421 50 0 0 0)
RA a b 0.1
LA b 0 3.1831m
VB c 0 SIN(0 1.41421 50 0 0 90)
RB c d 0.1
LB d 0 3.1831m
.control
tran 10u 60m uic
let iA = -i(VA)
let iB = -i(VB)
meas tran peakA MAX iA FROM=0 TO=20m
meas tran peakB MIN iB FROM=0 TO=20m
let ratioA = peakA / 1.40720
let ratioB = -peakB / 1.40720
print ratioA ratioB
.endc
.end
EOF
ngspice -b fault.cir 2>&1 | grep -E '^(peaka|peakb|ratioa|ratiob)'peaka = 2.443969e+00 at= 9.442902e-03
peakb = -1.495498e+00 at= 1.466290e-02
ratioa = 1.736760e+00
ratiob = 1.062747e+00
Loop A peaks at after , times the AC peak, close to IEC 60909's for (the standard's formula is a fit). Loop B, closed after the "no-offset" angle , has almost none: times.
Interactive: the offset in the netlist lab
Loop A in the netlist lab, solved from zero current at . Play it, or move the time cursor: the current peaks at at and swings asymmetrically until the offset decays (). Raise R1 to lower : at () the offset dies within a cycle.
Guided lab: DC offset at signal level
Hand calculation. Use a inductor (measure its resistance, typically to ) with a current shunt, driven at so that . With , ; predict , , and the first peak for closing at a voltage zero, and .
Simulation. Put your values into the netlist (SIN at , tstop ) or the formula above.
What you would measure. Set the function generator to burst mode (one burst of 10 cycles, peak, start phase , then ), and look at the shunt voltage on a scope triggered by the burst. Expect the first peak about times the steady peak at and close to times at , within roughly : the generator's output resistance adds to (include it, or use a low-impedance amplifier), and the inductor's core can be slightly nonlinear.
Hazards and safe setup. Function-generator levels only (, tens of milliamperes). Never try to "see" a fault current on mains equipment: a short circuit on a supply circuit produces an arc that can cause burns and eye injury even at .
Pitfalls
- Using for breaker duty. Interrupting and making duties need (or for delayed clearing); underestimates them severalfold.
- Forgetting the DC offset when checking making capacity and busbar forces: use the peak , not the rms value.
- Adding contributions with different angles arithmetically when resistances matter: add them as phasors.
- Prefault voltage of exactly 1.0 pu. Standards apply a voltage factor instead (Fault Levels and Breaker Duty).
Practice
- Repeat the worked example with one of the two lines out of service.
- What are the per-unit and kiloampere values of G1's subtransient contribution at its terminals in the worked example?
- A fault loop has . Estimate the first peak as a multiple of the AC peak.
Answer
- ; , .
- of the base current : (the transformer passes the same per-unit current).
- .
Test yourself
The fault current at a bus with prefault voltage 1.0 pu and Thevenin impedance j0.125 pu (bolted fault) is…
- 0.125 pu
- 8 pu
- 1.125 pu
- 12.5 pu
The DC offset in a fault current is largest when the fault occurs…
- at a voltage peak in an inductive circuit
- at a voltage zero in an inductive circuit
- in a purely resistive circuit
- never; it is always zero
Which generator reactance gives the largest initial fault current?
- they give the same
IEC 60909's peak factor for is about…
- 1.0
- 1.41
- 1.75
- 2.83