Home › Power Systems: Three-Phase, Generation, Grids & Protection › Synchronous Generators on the Grid

Synchronous Generators on the Grid

Once a generator is synchronised to a large grid, its speed is no longer its own: it turns at exactly the speed set by the grid frequency. What the operator can still change are two inputs, the turbine power and the field current. The first sets how many megawatts the unit delivers, the second how many megavars, and both together set the rotor angle, which decides how close the unit is to losing step. This lesson looks at the generator as part of the system: the power station P1 of this course feeding the grid through its step-up transformer and a double-circuit line. The machine itself (synchronous reactance, phasor diagrams, power-angle curve, V-curves, capability chart, synchronising) is covered in Synchronous Machines, the Power-Angle Curve and V-Curves and the Infinite Bus.

Safety: generators, their excitation systems and switchyards are studied here by calculation and simulation only.

Plant P1 and the infinite bus

G1 100 MVA, 11 kVT1 x = 0.10 circuit 1, x = 0.40circuit 2, x = 0.40 infinite busVt E j1.6 (Xd) Vt j0.10 j0.20 (2 lines) 1 at 0 deg per unit, 100 MVA

The grid behind the line is so large compared with one 100 MVA100\ \text{MVA} unit that its voltage and frequency do not change whatever P1 does: an infinite bus, 1.0 pu∠0∘1.0\ \text{pu}\angle 0^\circ. In steady state the generator is an EMF E∠δE\angle\delta behind its synchronous reactance XdX_d (round rotor, resistance neglected), so the whole path is one reactance X=Xd+XT+XL/2=1.6+0.10+0.20=1.90 puX = X_d + X_T + X_L/2 = 1.6 + 0.10 + 0.20 = 1.90\ \text{pu} and

P=E VXsin⁡δ,Qreceived at the bus=E Vcos⁡δ−V2XP = \frac{E\,V}{X}\sin\delta, \qquad Q_\text{received at the bus} = \frac{E\,V\cos\delta - V^2}{X}
  • The governor sets the turbine power PmP_m. In steady state P=PmP = P_m, and the rotor angle δ\delta settles where the curve gives that power.
  • The excitation sets EE. Raising it at constant PP reduces δ\delta (more margin to the peak Pmax=EV/XP_\text{max} = EV/X) and pushes reactive power into the grid; lowering it absorbs reactive power and drives δ\delta toward 90∘90^\circ.

Excitation systems and the AVR

The field winding is fed by an exciter: a DC generator on older units, a brushless AC exciter with rotating diodes, or a static thyristor bridge fed from the generator terminals. An automatic voltage regulator (AVR) measures the terminal voltage and adjusts the field to hold it at a set point, typically within a fraction of a percent. Around the AVR sit limiters that keep the machine inside its capability chart: an over-excitation limiter (field heating), a stator-current limiter, and an under-excitation limiter (stability and stator-end heating). A power system stabiliser (PSS) adds a signal derived from speed or power to damp electromechanical oscillations (Swing Equation).

Grid codes require a range of reactive power at full output, for example a power factor from about 0.850.85 lagging (exporting vars) to 0.950.95 leading (importing) at the connection point. The exact range depends on the code and the unit's size; the European requirements for generators are in Commission Regulation (EU) 2016/631 (Requirements for Generators, "RfG", 2016), implemented differently by each national operator.

Governors and droop

A governor with droop RR (typically 44 to 5 %5\ \%) changes the turbine power in proportion to the frequency error, ΔP/Prated=−(Δf/f0)/R\Delta P/P_\text{rated} = -(\Delta f/f_0)/R. With 5 %5\ \% droop, a fall of 0.1 Hz0.1\ \text{Hz} at 50 Hz50\ \text{Hz} (0.2 %0.2\ \%) raises the output by 4 %4\ \% of rating. Because all units share the same frequency, droop makes them share a load increase in proportion to their ratings, without any communication. Frequency control is the subject of Frequency Control.

Worked example: P1 at 80 MW with the AVR holding 1.0 pu

Given: P1 delivers P=0.8 puP = 0.8\ \text{pu} (80 MW80\ \text{MW}); the AVR holds the terminal voltage at Vt=1.0 puV_t = 1.0\ \text{pu}; Xd=1.6X_d = 1.6, Xe=XT+XL/2=0.30 puX_e = X_T + X_L/2 = 0.30\ \text{pu}; infinite bus 1.0 pu∠0∘1.0\ \text{pu}\angle 0^\circ.

Find: the terminal-voltage angle, the current, the reactive power at the terminals, the internal EMF E∠δE\angle\delta and the steady-state stability margin.

Solve: the terminal bus sends PP through XeX_e only:

sin⁡θ=PXeVtV=0.8⋅0.301⋅1=0.24,θ=13.89∘I=1∠13.89∘−1∠0∘j0.30=0.806 pu∠6.94∘,St=VtI∗=0.800+j0.097 puE=Vt+jXdI=1.725 pu∠61.80∘,Pmax=EVXd+Xe=1.7251.90=0.908 pu\begin{aligned} \sin\theta &= \frac{P X_e}{V_t V} = \frac{0.8 \cdot 0.30}{1 \cdot 1} = 0.24, \qquad \theta = 13.89^\circ \\ \mathbf{I} &= \frac{1\angle 13.89^\circ - 1\angle 0^\circ}{j0.30} = 0.806\ \text{pu}\angle 6.94^\circ, \qquad \mathbf{S}_t = \mathbf{V}_t\mathbf{I}^* = 0.800 + j0.097\ \text{pu} \\ \mathbf{E} &= \mathbf{V}_t + jX_d\mathbf{I} = 1.725\ \text{pu}\angle 61.80^\circ, \qquad P_\text{max} = \frac{E V}{X_d + X_e} = \frac{1.725}{1.90} = 0.908\ \text{pu} \end{aligned}

Check: 1.725⋅11.90sin⁡61.80∘=0.800 pu\frac{1.725 \cdot 1}{1.90}\sin 61.80^\circ = 0.800\ \text{pu}. The unit runs at 88 %88\ \% of its steady-state limit, which is too close: a step of turbine power or the loss of one line circuit (XeX_e rises to 0.500.50) could pull it out of step. In practice the AVR's fast action keeps the effective EMF higher during disturbances, and transient stability is judged with the transient reactance Xd′X'_d (Equal-Area Criterion).

In Python: what the AVR set point does

python · try it yourself
import numpy as np

Xd, Xe, P, V = 1.6, 0.30, 0.8, 1.0
print(" Vt  | theta  |  E    | delta  | Q_t (pu) | P/Pmax")
for Vt in (0.95, 1.00, 1.05):
    th = np.arcsin(P * Xe / (Vt * V))
    Vtp = Vt * np.exp(1j * th)
    I = (Vtp - V) / (1j * Xe)
    E = Vtp + 1j * Xd * I
    St = Vtp * np.conj(I)
    Pmax = abs(E) * V / (Xd + Xe)
    print(f"{Vt:4.2f} | {np.degrees(th):5.2f}  | {abs(E):5.3f} | {np.degrees(np.angle(E)):5.2f}  | {St.imag:+7.3f}  | {P/Pmax:5.3f}")

# Losing one line circuit at the same E and P: the new angle
E = 1.7247
for X in (1.9, 2.1):
    print(f"X = {X:.1f} pu: delta = {np.degrees(np.arcsin(P * X / (E * V))):5.2f} deg, Pmax = {E*V/X:.3f} pu")
 Vt  | theta  |  E    | delta  | Q_t (pu) | P/Pmax
0.95 | 14.63  | 1.596 | 72.19  |  -0.056  | 0.952
1.00 | 13.89  | 1.725 | 61.80  |  +0.097  | 0.881
1.05 | 13.21  | 1.900 | 53.12  |  +0.268  | 0.800
X = 1.9 pu: delta = 61.80 deg, Pmax = 0.908 pu
X = 2.1 pu: delta = 76.93 deg, Pmax = 0.821 pu

A higher voltage set point means more field current, more reactive export and a smaller rotor angle: excitation is the generator's strongest lever on stability. With one circuit out, the angle jumps to 76.9∘76.9^\circ and the margin nearly vanishes.

Interactive: the EMF at a fixed rotor angle

The netlist lab models the per-unit circuit with two sources: E=1.7247∠61.80∘\mathbf{E} = 1.7247\angle 61.80^\circ (V1) behind the total reactance 1.90 pu1.90\ \text{pu} (6.048 mH6.048\ \text{mH} at 50 Hz50\ \text{Hz}) and the infinite bus V2 at 1∠0∘1\angle 0^\circ. Read the values at the 50 Hz50\ \text{Hz} cursor. At the default it shows the current 805.9 mA∠6.9∘805.9\ \text{mA}\angle 6.9^\circ, i.e. 0.806 pu0.806\ \text{pu} as in the worked example. The slider changes only EE with the rotor angle frozen (a snapshot before the governor and the rotor respond): at E=1.30E = 1.30 the current falls to 0.636 pu∠18.6∘0.636\ \text{pu}\angle 18.6^\circ and the bus receives 0.603 pu0.603\ \text{pu} of power while it supplies 0.203 pu0.203\ \text{pu} of reactive power to the under-excited unit; at E=2.10E = 2.10 the current is 0.974 pu∠0.2∘0.974\ \text{pu}\angle 0.2^\circ, nearly in phase with the bus voltage.

0200400100m1101001k10kf (Hz)|I| (A)|I(LX)|phasors at f = 50.00 Hz (magnitude @ phase)V(e)1.72 V @ 61.8 degV(b)1.00 V @ 0.0 degI(V1)806 mA @ -173.1 degI(LX)806 mA @ 6.9 degI(V2)806 mA @ 6.9 deg

Guided lab: two sources and a reactance at signal level

Hand calculation. Two function generators locked to each other (most two-channel generators can do this) at 1 kHz1\ \text{kHz}, 1 V1\ \text{V} rms each, joined through a 10 mH10\ \text{mH} inductor (62.8 Ω62.8\ \Omega); channel 1 leads by 30∘30^\circ. The current is ∣1∠30∘−1∣/62.8=0.518/62.8=8.24 mA\lvert 1\angle 30^\circ - 1 \rvert/62.8 = 0.518/62.8 = 8.24\ \text{mA} and the "power" sent is sin⁡30∘/62.8 W=7.96 mW\sin 30^\circ/62.8\ \text{W} = 7.96\ \text{mW}.

Simulation. Put these values into the netlist (V1 e 0 AC 1 30, LX e b 10m, V2 b 0 AC 1, f = 1000) and change the amplitude of V1.

What you would measure. With a 10 Ω10\ \Omega sense resistor in series and a two-channel oscilloscope, the current amplitude and its phase relative to channel 2. A function generator has a 50 Ω50\ \Omega output resistance, so the two outputs and the sense resistor add 110 Ω110\ \Omega in series with the 62.8 Ω62.8\ \Omega: unbuffered, expect about 0.518/∣110+j62.8∣=4.09 mA0.518/\lvert 110 + j62.8 \rvert = 4.09\ \text{mA}, not 8.24 mA8.24\ \text{mA} (put the 110 Ω110\ \Omega into the netlist as a resistor to compare, or buffer each output with an op-amp follower to approach the ideal case). Beyond that, expect agreement within about 5 %5\ \%: the inductor tolerance and its winding resistance (often a few ohms) are the main errors. Raising the amplitude of channel 1 at a fixed phase swings the current phase just as in the lab.

Hazards and safe setup. Signal generators only; the generators' outputs must share a common ground and be able to sink current (most 50 Ω50\ \Omega outputs can at these levels).

Pitfalls

  • Thinking the field controls megawatts. In steady state P=PmP = P_m, set by the turbine; the field changes the angle and the reactive power.
  • Using XdX_d for transients. Steady-state margins use XdX_d; the first swing after a fault is governed by Xd′X'_d and the AVR.
  • Under-excitation. Running leading (absorbing vars) at high load reduces EE and the stability margin; limiters exist for a reason.
  • Infinite-bus assumption. It fails for a unit that is large compared with its grid, or on a weak, long connection.

Practice

  1. P1 runs at P=0.5 puP = 0.5\ \text{pu} with E=1.5 puE = 1.5\ \text{pu}. Find δ\delta and PmaxP_\text{max}.
  2. A 500 MW500\ \text{MW} unit has 4 %4\ \% droop. How much does its output change for a frequency fall of 0.2 Hz0.2\ \text{Hz}?
  3. Why do grid codes require generators to absorb reactive power as well as supply it?
Answer
  1. Pmax=1.5/1.9=0.789 puP_\text{max} = 1.5/1.9 = 0.789\ \text{pu}; δ=arcsin⁡(0.5/0.789)=39.3∘\delta = \arcsin(0.5/0.789) = 39.3^\circ.
  2. Δf/f0=0.4 %\Delta f/f_0 = 0.4\ \%; ΔP=0.4/4=10 %\Delta P = 0.4/4 = 10\ \% of 500 MW500\ \text{MW}, +50 MW+50\ \text{MW}.
  3. At light load, line and cable charging raise voltages; generators absorbing vars hold them down.

Test yourself

A generator on an infinite bus has its field current increased at constant turbine power. Its rotor angle…

  1. increases
  2. decreases
  3. stays the same
  4. becomes zero

What sets the steady-state real power of a synchronised generator?

  1. the field current
  2. the turbine (governor)
  3. the terminal voltage
  4. the grid frequency alone

Two units of 200 MW and 400 MW, both with 5 % droop, share a load increase of 60 MW. The 400 MW unit takes…

  1. 20 MW
  2. 30 MW
  3. 40 MW
  4. 60 MW

With E = 1.725 pu, X = 1.9 pu and V = 1 pu, the steady-state power limit is about…

  1. 0.53 pu
  2. 0.91 pu
  3. 1.10 pu
  4. 3.28 pu