Synchronous Generators on the Grid
Once a generator is synchronised to a large grid, its speed is no longer its own: it turns at exactly the speed set by the grid frequency. What the operator can still change are two inputs, the turbine power and the field current. The first sets how many megawatts the unit delivers, the second how many megavars, and both together set the rotor angle, which decides how close the unit is to losing step. This lesson looks at the generator as part of the system: the power station P1 of this course feeding the grid through its step-up transformer and a double-circuit line. The machine itself (synchronous reactance, phasor diagrams, power-angle curve, V-curves, capability chart, synchronising) is covered in Synchronous Machines, the Power-Angle Curve and V-Curves and the Infinite Bus.
Safety: generators, their excitation systems and switchyards are studied here by calculation and simulation only.
Plant P1 and the infinite bus
The grid behind the line is so large compared with one unit that its voltage and frequency do not change whatever P1 does: an infinite bus, . In steady state the generator is an EMF behind its synchronous reactance (round rotor, resistance neglected), so the whole path is one reactance and
- The governor sets the turbine power . In steady state , and the rotor angle settles where the curve gives that power.
- The excitation sets . Raising it at constant reduces (more margin to the peak ) and pushes reactive power into the grid; lowering it absorbs reactive power and drives toward .
Excitation systems and the AVR
The field winding is fed by an exciter: a DC generator on older units, a brushless AC exciter with rotating diodes, or a static thyristor bridge fed from the generator terminals. An automatic voltage regulator (AVR) measures the terminal voltage and adjusts the field to hold it at a set point, typically within a fraction of a percent. Around the AVR sit limiters that keep the machine inside its capability chart: an over-excitation limiter (field heating), a stator-current limiter, and an under-excitation limiter (stability and stator-end heating). A power system stabiliser (PSS) adds a signal derived from speed or power to damp electromechanical oscillations (Swing Equation).
Grid codes require a range of reactive power at full output, for example a power factor from about lagging (exporting vars) to leading (importing) at the connection point. The exact range depends on the code and the unit's size; the European requirements for generators are in Commission Regulation (EU) 2016/631 (Requirements for Generators, "RfG", 2016), implemented differently by each national operator.
Governors and droop
A governor with droop (typically to ) changes the turbine power in proportion to the frequency error, . With droop, a fall of at () raises the output by of rating. Because all units share the same frequency, droop makes them share a load increase in proportion to their ratings, without any communication. Frequency control is the subject of Frequency Control.
Worked example: P1 at 80 MW with the AVR holding 1.0 pu
Given: P1 delivers (); the AVR holds the terminal voltage at ; , ; infinite bus .
Find: the terminal-voltage angle, the current, the reactive power at the terminals, the internal EMF and the steady-state stability margin.
Solve: the terminal bus sends through only:
Check: . The unit runs at of its steady-state limit, which is too close: a step of turbine power or the loss of one line circuit ( rises to ) could pull it out of step. In practice the AVR's fast action keeps the effective EMF higher during disturbances, and transient stability is judged with the transient reactance (Equal-Area Criterion).
In Python: what the AVR set point does
import numpy as np
Xd, Xe, P, V = 1.6, 0.30, 0.8, 1.0
print(" Vt | theta | E | delta | Q_t (pu) | P/Pmax")
for Vt in (0.95, 1.00, 1.05):
th = np.arcsin(P * Xe / (Vt * V))
Vtp = Vt * np.exp(1j * th)
I = (Vtp - V) / (1j * Xe)
E = Vtp + 1j * Xd * I
St = Vtp * np.conj(I)
Pmax = abs(E) * V / (Xd + Xe)
print(f"{Vt:4.2f} | {np.degrees(th):5.2f} | {abs(E):5.3f} | {np.degrees(np.angle(E)):5.2f} | {St.imag:+7.3f} | {P/Pmax:5.3f}")
# Losing one line circuit at the same E and P: the new angle
E = 1.7247
for X in (1.9, 2.1):
print(f"X = {X:.1f} pu: delta = {np.degrees(np.arcsin(P * X / (E * V))):5.2f} deg, Pmax = {E*V/X:.3f} pu") Vt | theta | E | delta | Q_t (pu) | P/Pmax
0.95 | 14.63 | 1.596 | 72.19 | -0.056 | 0.952
1.00 | 13.89 | 1.725 | 61.80 | +0.097 | 0.881
1.05 | 13.21 | 1.900 | 53.12 | +0.268 | 0.800
X = 1.9 pu: delta = 61.80 deg, Pmax = 0.908 pu
X = 2.1 pu: delta = 76.93 deg, Pmax = 0.821 pu
A higher voltage set point means more field current, more reactive export and a smaller rotor angle: excitation is the generator's strongest lever on stability. With one circuit out, the angle jumps to and the margin nearly vanishes.
Interactive: the EMF at a fixed rotor angle
The netlist lab models the per-unit circuit with two sources: (V1) behind the total reactance ( at ) and the infinite bus V2 at . Read the values at the cursor. At the default it shows the current , i.e. as in the worked example. The slider changes only with the rotor angle frozen (a snapshot before the governor and the rotor respond): at the current falls to and the bus receives of power while it supplies of reactive power to the under-excited unit; at the current is , nearly in phase with the bus voltage.
Guided lab: two sources and a reactance at signal level
Hand calculation. Two function generators locked to each other (most two-channel generators can do this) at , rms each, joined through a inductor (); channel 1 leads by . The current is and the "power" sent is .
Simulation. Put these values into the netlist (V1 e 0 AC 1 30, LX e b 10m, V2 b 0 AC 1, f = 1000) and change the amplitude of V1.
What you would measure. With a sense resistor in series and a two-channel oscilloscope, the current amplitude and its phase relative to channel 2. A function generator has a output resistance, so the two outputs and the sense resistor add in series with the : unbuffered, expect about , not (put the into the netlist as a resistor to compare, or buffer each output with an op-amp follower to approach the ideal case). Beyond that, expect agreement within about : the inductor tolerance and its winding resistance (often a few ohms) are the main errors. Raising the amplitude of channel 1 at a fixed phase swings the current phase just as in the lab.
Hazards and safe setup. Signal generators only; the generators' outputs must share a common ground and be able to sink current (most outputs can at these levels).
Pitfalls
- Thinking the field controls megawatts. In steady state , set by the turbine; the field changes the angle and the reactive power.
- Using for transients. Steady-state margins use ; the first swing after a fault is governed by and the AVR.
- Under-excitation. Running leading (absorbing vars) at high load reduces and the stability margin; limiters exist for a reason.
- Infinite-bus assumption. It fails for a unit that is large compared with its grid, or on a weak, long connection.
Practice
- P1 runs at with . Find and .
- A unit has droop. How much does its output change for a frequency fall of ?
- Why do grid codes require generators to absorb reactive power as well as supply it?
Answer
- ; .
- ; of , .
- At light load, line and cable charging raise voltages; generators absorbing vars hold them down.
Test yourself
A generator on an infinite bus has its field current increased at constant turbine power. Its rotor angle…
- increases
- decreases
- stays the same
- becomes zero
What sets the steady-state real power of a synchronised generator?
- the field current
- the turbine (governor)
- the terminal voltage
- the grid frequency alone
Two units of 200 MW and 400 MW, both with 5 % droop, share a load increase of 60 MW. The 400 MW unit takes…
- 20 MW
- 30 MW
- 40 MW
- 60 MW
With E = 1.725 pu, X = 1.9 pu and V = 1 pu, the steady-state power limit is about…
- 0.53 pu
- 0.91 pu
- 1.10 pu
- 3.28 pu