Solar PV: Cells, Arrays and Inverters
A solar module's datasheet says "", but on a hot summer afternoon on a roof it gives perhaps , on a cold clear morning more than its rating, and its voltage on a frosty day can exceed what the inverter tolerates. An engineer designing a PV system, or a grid operator wondering how much a thousand rooftops will push back into a feeder at noon, needs the cell's current–voltage curve, how it moves with sunlight and temperature, and how strings of modules and an inverter turn it into AC at the grid's frequency. This lesson builds that chain with a single-diode model.
Safety: PV strings produce hundreds of volts DC whenever light falls on them, and DC arcs do not self-extinguish like AC arcs; grid-connected inverters are mains equipment. This lesson is calculation and simulation only. The bench lab uses a small panel of a few watts.
The cell as a current source and a diode
A silicon solar cell is a large-area p-n junction. Light generates a current proportional to the irradiance ; the junction behaves as a diode in parallel; a small series resistance (contacts, fingers) and a large shunt resistance complete the single-diode model. For a module of cells in series (shunt resistance neglected):
with ideality factor to and at . The curve runs from the short-circuit current at to the open-circuit voltage at . Power is zero at both ends and peaks at the maximum power point (MPP). The fill factor measures how square the curve is; good crystalline modules reach about to .
How the curve moves:
- Irradiance: is proportional to ; rises only logarithmically. Half the sunlight gives about half the power.
- Temperature: falls by roughly to per kelvin for crystalline silicon (the datasheet gives the coefficient), rises slightly, and power falls by about to . Cells run to above ambient in full sun.
Ratings are at standard test conditions (STC): , cell temperature , air mass 1.5 spectrum (IEC 61215 and IEC 60904 series).
Worked example: one module in four conditions
Given: a 60-cell module with and at STC, , , temperature coefficients () and ().
Find: the MPP and fill factor at STC, at a hot cell temperature, at half irradiance, and on a cold morning at full sun.
Solve: the saturation current follows from : with , so . The program then solves the implicit equation for at each voltage and finds the peak:
| Condition | MPP | FF | ||
|---|---|---|---|---|
| STC | ||||
Check: at is , and the power falls by , which is , inside the usual range. At half irradiance drops by , as the table shows.
import numpy as np
from scipy.optimize import brentq
k, q = 1.380649e-23, 1.602176634e-19
Ns, n, Rs = 60, 1.2, 0.25 # cells, ideality factor, series resistance (ohm, module)
Isc0, Voc0 = 10.0, 41.0 # at STC: 1000 W/m2, 25 C
aI, aV = 0.0005, -0.0030 # temperature coefficients per K (Isc +0.05 %/K, Voc -0.30 %/K)
def module(G, Tc):
Vt = n * Ns * k * (Tc + 273.15) / q
Isc = Isc0 * G / 1000 * (1 + aI * (Tc - 25))
Voc = Voc0 * (1 + aV * (Tc - 25)) + Vt * np.log(G / 1000)
I0 = Isc / np.expm1(Voc / Vt)
def current(V): # solve I = Isc - I0 (exp((V + I Rs)/Vt) - 1) for I
return brentq(lambda I: Isc - I0 * np.expm1((V + I * Rs) / Vt) - I, -1, Isc + 1)
return Isc, Voc, current
for G, Tc in ((1000, 25), (1000, 60), (500, 25), (1000, -10)):
Isc, Voc, cur = module(G, Tc)
V = np.linspace(0, Voc, 801)
I = np.array([cur(v) for v in V])
P = V * I
m = P.argmax()
print(f"G = {G:4d} W/m2, Tc = {Tc:3d} C: Isc = {Isc:5.2f} A, Voc = {Voc:5.2f} V,"
f" MPP {V[m]:5.2f} V x {I[m]:5.2f} A = {P[m]:6.1f} W, FF = {P[m]/(Isc*Voc):.3f}")
# String sizing for an inverter with a 1000 V DC limit and a 200-800 V MPP window
Voc_cold, Vmp_hot = 45.30, 28.90
print(f"max modules per string: {int(1000 // Voc_cold)} (Voc at -10 C)")
print(f"min modules per string: {int(np.ceil(200 / Vmp_hot))} (Vmp at 60 C above 200 V)")
N = 20
print(f"a string of {N}: Voc cold {N*Voc_cold:.0f} V, Vmp hot {N*Vmp_hot:.0f} V, Vmp STC {N*33.31:.0f} V")G = 1000 W/m2, Tc = 25 C: Isc = 10.00 A, Voc = 41.00 V, MPP 33.31 V x 9.44 A = 314.4 W, FF = 0.767
G = 1000 W/m2, Tc = 60 C: Isc = 10.18 A, Voc = 36.70 V, MPP 28.90 V x 9.44 A = 272.8 W, FF = 0.731
G = 500 W/m2, Tc = 25 C: Isc = 5.00 A, Voc = 39.72 V, MPP 33.16 V x 4.73 A = 156.7 W, FF = 0.789
G = 1000 W/m2, Tc = -10 C: Isc = 9.83 A, Voc = 45.30 V, MPP 37.83 V x 9.40 A = 355.6 W, FF = 0.799
max modules per string: 22 (Voc at -10 C)
min modules per string: 7 (Vmp at 60 C above 200 V)
a string of 20: Voc cold 906 V, Vmp hot 578 V, Vmp STC 666 V
Arrays and the inverter
Modules in series form a string (voltages add); strings in parallel add current. The string length is set by the inverter: the coldest-day must stay below its maximum DC voltage (here modules for ), and the hottest-day must stay inside its MPP-tracking window. Bypass diodes across groups of cells let a shaded module pass the string current instead of reverse-biasing its cells (and creating hot spots), at the cost of that group's output.
The inverter does three jobs (Power Electronics & Motor Drives):
- Maximum power point tracking: it varies the DC voltage, usually by perturb-and-observe or incremental conductance, to sit on the MPP as irradiance and temperature change.
- DC to AC conversion synchronised to the grid with a phase-locked loop, as a current source. European weighted efficiencies of modern string inverters are about to .
- Grid functions: anti-islanding (disconnect when the grid is lost), voltage and frequency ride-through, reactive power and volt–var or frequency–watt response as required by the connection rules, for example IEEE 1547-2018 in North America or EN 50549-1:2019 and national codes in Europe (editions current as of 2026) (Smart Grid and DER).
Designers often install more DC than AC capacity (a DC/AC ratio of to ), because the array rarely reaches STC output; the inverter "clips" the few peak hours.
Energy over a year
A rough annual yield is the specific yield in kWh per kWp. It is about to in central Europe and to in sunny regions such as southern Spain, the Middle East or Australia (typical published values, varying with orientation and climate). With , the capacity factor is ; with , . All of that energy arrives in daylight and peaks at midday, which is what causes the evening ramp that Storage and flexible plant must cover.
Guided lab: the I–V curve of a small panel
Hand calculation. A , hobby panel might have and in full sun. Estimate the MPP as about and : , , .
Simulation. Set Ns = 12, Isc0 = 0.37, Voc0 = 7.2, Rs = 1.0 in the program and compare its MPP with your estimate.
What you would measure. In steady sunlight (or under a halogen lamp kept at a safe distance), load the panel with a decade box or a set of resistors from to (or a potentiometer rated for ) and read voltage and current with two DMMs. Plot against and against . Expect the knee near the MPP, a fill factor around to for such small panels, and to scatter from passing clouds; a cardboard shadow over one cell will show the dramatic loss a single shaded cell causes.
Hazards and safe setup. Low-voltage panel only. A halogen lamp gets very hot: keep it away from the panel's plastic and from your hands, and never short a large panel.
Pitfalls
- Sizing strings on STC voltage. The cold-morning sets the limit; exceeding the inverter's maximum DC voltage can destroy it.
- Partial shading. One shaded cell can cut a whole string's current; layout and bypass diodes matter more than module efficiency.
- Rated power as available power. Real output is usually to of STC at noon because of temperature and losses.
- Ignoring the grid. Many inverters on one feeder raise its voltage at midday; see Distribution Systems.
Practice
- A module has at STC and . What is at , and how many fit in a string?
- A rooftop yields a year. What is its specific yield and capacity factor?
- Why does a PV module produce more power on a cold sunny day than at STC?
Answer
- ; , so modules.
- ; .
- The voltage, and therefore the power, rises as the cell temperature falls below .
Test yourself
Halving the irradiance on a PV module roughly…
- halves Voc and halves Isc
- halves Isc and lowers Voc only slightly
- keeps Isc and halves Voc
- has no effect at the MPP
The maximum number of modules in a string is limited by…
- the hottest-day Vmp
- the coldest-day Voc against the inverter's maximum DC voltage
- the module current
- the grid frequency
A module's MPP is 33.3 V × 9.44 A with Isc = 10 A and Voc = 41 V. Its fill factor is about…
- 0.67
- 0.77
- 0.81
- 0.94
What does anti-islanding protection in a grid-tied inverter do?
- tracks the MPP
- stops the inverter feeding a section of network that has lost its grid supply
- limits the DC voltage
- corrects the power factor