Line Resistance and Inductance: GMR and GMD
Every calculation of power flow, voltage drop or fault current on an overhead line starts from two numbers per kilometre: the series resistance and the series reactance. Neither comes from a nameplate. The resistance depends on the conductor material, its temperature and the frequency; the inductance depends only on geometry, the conductor radius and how far apart the three phases hang. This lesson derives both for real three-phase lines, introducing the two quantities that every line-design table uses: the geometric mean radius (GMR) and the geometric mean distance (GMD). The field theory behind them (flux linkage, internal inductance, skin effect) is in Inductance and Lossy Media.
Safety: overhead lines are studied here by calculation only. Never approach a line or fly a drone or kite near one; the clearances are there because air breaks down and arcs jump.
Resistance
The DC resistance per unit length is for the conducting cross-section . Two corrections follow:
- Temperature: aluminium has and ; lines are rated for conductor temperatures of about to (higher for special high-temperature conductors), so the hot resistance is about to above .
- Skin effect: AC crowds the current toward the surface within a skin depth , about in aluminium at . Conductors with radii of to therefore see only a few percent increase, which datasheets include as the "AC resistance at ".
- Stranding: strands spiral, so they are a few percent longer than the line.
Overhead conductors are usually ACSR (aluminium conductor, steel reinforced): steel core for strength, aluminium strands for conduction. Only the aluminium counts in .
Inductance of one conductor among three
A long straight conductor of radius carrying current links flux both inside itself and in the space around it. Inside a uniform solid conductor the flux linkage is per metre; outside, between radii and , it is . Both pieces combine neatly if the radius is replaced by
the GMR of a solid round conductor. For a three-phase line with currents summing to zero, the flux linking phase a is set by its own GMR and its distances to the other two phases. If the line is transposed (each phase takes each position for a third of its length, Line Capacitance), each phase sees the same average and
GMR of a stranded conductor. For a conductor made of strands, GMR is the geometric mean of all the distances between strands, with each strand's own used for its "distance to itself". For seven equal strands of radius (one in the middle, six around) the program below gets , where is the overall radius. Manufacturers publish GMR for every conductor; ACSR values are typically to of the overall radius.
Bundles. EHV lines use two, three or four sub-conductors per phase a few tens of centimetres apart. The bundle behaves as one conductor with a larger GMR, for two sub-conductors at spacing , which lowers the inductance and, more importantly at EHV, the surface electric field (corona).
Because depends on a logarithm, it barely changes from line to line: most overhead lines have to at whatever their voltage.
Worked example: a 132 kV line
Given: a transposed single-circuit line with the phases in a horizontal row apart; compact ACSR conductor with trapezoidal aluminium strands (ACSR/TW, which packs of aluminium into a smaller diameter than round strands; a round-strand ACSR is about in radius), overall radius , GMR (from the manufacturer's table); conductor temperature ; skin effect .
Find: , and per kilometre at .
Solve:
Check: , typical for a line, and sits in the usual range. With a solid conductor of the same radius () the inductance would differ by less than : the logarithm forgives small errors in GMR.
In Python: GMR by brute force, then the line
import numpy as np
# GMR of a 7-strand conductor: geometric mean of all strand-to-strand distances (strand radius a = 1)
a = 1.0
pts = np.array([(0.0, 0.0)] + [(2 * a * np.cos(k * np.pi / 3), 2 * a * np.sin(k * np.pi / 3)) for k in range(6)])
logs = []
for i in range(7):
for j in range(7):
d = a * np.exp(-0.25) if i == j else np.hypot(*(pts[i] - pts[j]))
logs.append(np.log(d))
gmr = np.exp(np.mean(logs))
print(f"7-strand GMR = {gmr:.4f} a = {gmr / (3 * a):.4f} x overall radius")
# The 132 kV line
rho20, alpha, A = 2.83e-8, 0.00403, 400e-6
R20 = rho20 / A * 1e3 # ohm/km
R75 = R20 * (1 + alpha * 55)
Rac = 1.02 * R75
print(f"R20 = {R20:.4f}, R75 = {R75:.4f}, Rac = {Rac:.4f} ohm/km")
print(f"skin depth in aluminium at 50 Hz: {np.sqrt(rho20 / (np.pi * 50 * 4e-7 * np.pi)) * 1e3:.1f} mm")
def L_per_km(gmd, gmr):
return 2e-7 * np.log(gmd / gmr) * 1e3 # H/km
gmd = (4 * 4 * 8) ** (1 / 3)
for label, Ds in (("stranded GMR 10.1 mm", 0.0101), ("solid r' = 0.7788 r", 0.7788 * 0.0125)):
L = L_per_km(gmd, Ds)
print(f"{label}: L = {L*1e3:.4f} mH/km, X = {2*np.pi*50*L:.4f} ohm/km")
# Sensitivity: the logarithm in action
for D in (3, 4, 6, 8):
g = (D * D * 2 * D) ** (1 / 3)
print(f"spacing {D} m: X = {2*np.pi*50*L_per_km(g, 0.0101):.3f} ohm/km")7-strand GMR = 2.1767 a = 0.7256 x overall radius
R20 = 0.0707, R75 = 0.0864, Rac = 0.0882 ohm/km
skin depth in aluminium at 50 Hz: 12.0 mm
stranded GMR 10.1 mm: L = 1.2425 mH/km, X = 0.3903 ohm/km
solid r' = 0.7788 r: L = 1.2499 mH/km, X = 0.3927 ohm/km
spacing 3 m: X = 0.372 ohm/km
spacing 4 m: X = 0.390 ohm/km
spacing 6 m: X = 0.416 ohm/km
spacing 8 m: X = 0.434 ohm/km
Doubling the phase spacing raises the reactance by only . Higher voltages need wider spacing for insulation, but bundling brings the reactance back down, so EHV lines also end up near .
Guided lab: the inductance of a two-wire loop
Hand calculation. Two parallel wires of radius , apart, long (a loop out and back), have .
Simulation. Use L_per_km from the program (the loop is twice the single-conductor value) and vary the spacing.
What you would measure. With an LCR meter at (the inductance is tiny at ), tape two wires to a sheet of cardboard at fixed spacings (5, 10, 20, 40 mm) and short them at the far end. Expect to at ; the end connections add a few tenths of a microhenry, and the logarithmic dependence on spacing appears clearly. At the skin depth in copper is , so the internal-inductance term shrinks slightly.
Hazards and safe setup. The LCR meter applies about ; no hazard.
Pitfalls
- Using the physical radius instead of GMR. It underestimates the inductance slightly; use or the manufacturer's GMR.
- Using the DC resistance at for loss studies. Conductors under load run hot.
- Mixing natural logarithms and log base 10. The formula uses .
- Forgetting transposition. Without it, the three phases have different inductances and the line causes unbalance.
Practice
- Find per km for a line with GMD and GMR at .
- A two-conductor bundle has sub-conductor GMR and spacing . What is its equivalent GMR?
- Why does skin effect matter more for the large conductors of a busbar than for a diameter line conductor?
Answer
- .
- .
- Skin depth at is about in aluminium and in copper. A conductor much thicker than that carries little current in its middle, so solid busbars thicker than about gain resistance and are often made as hollow tubes or laminated bars.
Test yourself
The GMR of a solid round conductor of radius r is…
- r
- 0.5r
Phases in a horizontal row at 5 m spacing have a GMD of…
- 5 m
- 6.30 m
- 7.5 m
- 10 m
Doubling the phase spacing of a line changes its reactance by about…
- +100 %
- +50 %
- +10 %
- -50 %
Why are EHV lines built with bundled conductors?
- to raise the inductance
- to reduce surface field (corona) and reactance
- to save aluminium
- to remove skin effect completely