Balanced Three-Phase Systems and Per-Phase Analysis

A workshop takes its supply from a 400 V400\ \text{V} board through a cable. On it run a delta-connected oven and a bank of star-connected heaters. What voltage do the loads actually get, how much current flows in the cable, and what does the cable waste? Writing out all three phases means nine complex unknowns; for a balanced system you need to solve only one phase. This lesson turns that shortcut into a reliable method, which every later calculation in the course (load flow, faults, stability) relies on. Star and delta loads, line and phase quantities and the balanced source were introduced in Three-Phase Circuits; here they are combined with line impedance and mixed loads.

Safety: 230/400 V230/400\ \text{V} three-phase installations can kill. This lesson works by calculation and simulation only; nothing here is built or measured on the mains.

Why one phase is enough

In a balanced system the source voltages have equal magnitude and are 120∘120^\circ apart, and every phase has the same impedances. Then the three currents are also equal and 120∘120^\circ apart, they sum to zero, and every star point is at the same potential as the source neutral, whether or not a neutral wire is present. You can therefore join all star points with an imaginary zero-impedance neutral and cut out one phase: phase a, from line to neutral, with its share of every element. The other phases are the same answer shifted by −120∘-120^\circ and +120∘+120^\circ.

The recipe:

  1. Convert every delta element (load or source) to an equivalent star: ZY=ZΔ/3Z_Y = Z_\Delta/3, Vph=VL/(3∠30∘)\mathbf{V}_\text{ph} = \mathbf{V}_{L}/(\sqrt{3}\angle 30^\circ).
  2. Draw one phase from line a to neutral, with the line impedance in series and the star-equivalent loads in parallel.
  3. Solve it with ordinary phasor analysis (AC Nodal and Mesh).
  4. Convert back: line voltages are 3\sqrt{3} times larger and lead by 30∘30^\circ; a delta load's phase current is the line current divided by 3\sqrt{3}, leading by 30∘30^\circ.
  5. Multiply powers by three: S3ϕ=3 VphI∗\mathbf{S}_{3\phi} = 3\,\mathbf{V}_\text{ph}\mathbf{I}^*.
~230 V0 deg 0.05 Ohm j0.08 Ohm (cable) 10 Ohmj5 Ohm 12 Ohm load bus oven 30+j15 Ohm (delta) = 10+j5 Ohm (star); heater 12 Ohm Ia N

Constant power: why three phases

In phase a, va=2Vcos⁡ωtv_a = \sqrt{2}V\cos\omega t and ia=2Icos⁡(ωt−ϕ)i_a = \sqrt{2}I\cos(\omega t - \phi). Adding the three phases,

p(t)=vaia+vbib+vcic=3VIcos⁡ϕp(t) = v_a i_a + v_b i_b + v_c i_c = 3VI\cos\phi

because the three double-frequency terms VIcos⁡(2ωt−ϕ−k⋅240∘)VI\cos(2\omega t - \phi - k\cdot 240^\circ) cancel. A single-phase load's power pulses at 100 Hz100\ \text{Hz} between VI(cos⁡ϕ−1)VI(\cos\phi - 1) and VI(cos⁡ϕ+1)VI(\cos\phi + 1); a balanced three-phase load draws a steady flow, so its motor torque does not pulsate. The program below checks this numerically.

Worked example: the workshop

Given: a balanced 230/400 V230/400\ \text{V} source (phase a reference 230 V∠0∘230\ \text{V}\angle 0^\circ); a cable of 0.05+j0.08 Ω0.05 + j0.08\ \Omega per phase; an oven of 30+j15 Ω30 + j15\ \Omega per phase in delta; heaters of 12 Ω12\ \Omega per phase in star. (Calculation only.)

Find: the load voltage, the cable current, the oven's phase current, the total power, the cable loss and the voltage drop.

Solve: the oven in star is (30+j15)/3=10+j5 Ω(30 + j15)/3 = 10 + j5\ \Omega. In parallel with 12 Ω12\ \Omega:

Zp=(110+j5+112)−1=5.776+j1.415 Ω=5.947 Ω∠13.76∘Ia=230 V(0.05+j0.08) Ω+Zp=38.24 A∠−14.39∘Vload=IaZp=227.4 V∠−0.63∘,VL,load=3⋅227.4=393.9 VIoven, line=227.4 V11.18 Ω=20.34 A,Ioven, phase=20.34 A3=11.74 ASload=3 VloadIa∗=25.34 kW+j6.21 kvar,pf=0.971 laggingPcable=3⋅(38.24 A)2⋅0.05 Ω=219 W,drop=230−227.4230=1.13 %\begin{aligned} Z_p &= \left(\frac{1}{10 + j5} + \frac{1}{12}\right)^{-1} = 5.776 + j1.415\ \Omega = 5.947\ \Omega\angle 13.76^\circ \\ \mathbf{I}_a &= \frac{230\ \text{V}}{(0.05 + j0.08)\ \Omega + Z_p} = 38.24\ \text{A}\angle -14.39^\circ \\ \mathbf{V}_\text{load} &= \mathbf{I}_a Z_p = 227.4\ \text{V}\angle -0.63^\circ, \qquad V_{L,\text{load}} = \sqrt{3} \cdot 227.4 = 393.9\ \text{V} \\ I_\text{oven, line} &= \frac{227.4\ \text{V}}{11.18\ \Omega} = 20.34\ \text{A}, \qquad I_\text{oven, phase} = \frac{20.34\ \text{A}}{\sqrt{3}} = 11.74\ \text{A} \\ \mathbf{S}_\text{load} &= 3\,\mathbf{V}_\text{load}\mathbf{I}_a^* = 25.34\ \text{kW} + j6.21\ \text{kvar}, \qquad \text{pf} = 0.971\ \text{lagging} \\ P_\text{cable} &= 3 \cdot (38.24\ \text{A})^2 \cdot 0.05\ \Omega = 219\ \text{W}, \qquad \text{drop} = \frac{230 - 227.4}{230} = 1.13\ \% \end{aligned}

Check: the source delivers 3⋅230⋅38.24cos⁡14.39∘=25.56 kW3 \cdot 230 \cdot 38.24 \cos 14.39^\circ = 25.56\ \text{kW}, which equals the 25.34 kW25.34\ \text{kW} of the loads plus the 0.22 kW0.22\ \text{kW} cable loss. The approximate drop formula ΔV≈I(Rcos⁡ϕ+Xsin⁡ϕ)\Delta V \approx I(R\cos\phi + X\sin\phi), with the load's ϕ=13.76∘\phi = 13.76^\circ, gives 38.24 (0.05⋅0.971+0.08⋅0.238)=2.58 V38.24\,(0.05 \cdot 0.971 + 0.08 \cdot 0.238) = 2.58\ \text{V} and agrees with 230−227.4=2.6 V230 - 227.4 = 2.6\ \text{V}.

In Python: one phase, then all three

The program solves the per-phase circuit, then solves the full three-phase circuit by nodal analysis with the oven really in delta and no neutral wire, to show that the shortcut gives the same answer.

python · try it yourself
import numpy as np

a = np.exp(2j * np.pi / 3)
pol = lambda z: f"{abs(z):7.3f} at {np.degrees(np.angle(z)):+7.2f} deg"

V, Zl = 230.0, 0.05 + 0.08j
Zd, Zh = 30 + 15j, 12.0                       # oven per phase (delta), heater per phase (star)

# 1) per-phase equivalent
Zp = 1 / (3 / Zd + 1 / Zh)                    # delta -> star is Zd/3
Ia = V / (Zl + Zp)
Vl = Ia * Zp
print("per phase: Ia =", pol(Ia), "A, V_load =", pol(Vl), "V")
S = 3 * Vl * np.conj(Ia)
print(f"load P = {S.real/1e3:.2f} kW, Q = {S.imag/1e3:.2f} kvar, pf = {S.real/abs(S):.4f}")
print(f"cable loss = {3 * abs(Ia)**2 * Zl.real:.0f} W")

# 2) full three-phase nodal analysis: unknowns = load-bus voltages (a, b, c) and heater star point n
Es = V * np.array([1, a**2, a])               # source phase voltages, sequence a-b-c
yl, yd, yh = 1 / Zl, 1 / Zd, 1 / Zh
Y = np.zeros((4, 4), complex); J = np.zeros(4, complex)
for k in range(3):
    Y[k, k] += yl + 2 * yd + yh               # cable, two delta branches, heater
    J[k] += yl * Es[k]
    for m in range(3):
        if m != k:
            Y[k, m] -= yd                     # delta branch between lines k and m
    Y[k, 3] -= yh; Y[3, k] -= yh
Y[3, 3] = 3 * yh
U = np.linalg.solve(Y, J)
I = (Es - U[:3]) * yl
print("three-phase:", ", ".join(pol(i) for i in I))
print("heater star point below 1e-9 V:", abs(U[3]) < 1e-9, "| line currents sum to zero:", abs(I.sum()) < 1e-9)
print("oven phase current Iab =", pol((U[0] - U[1]) * yd), "A")

# 3) instantaneous power is constant
t = np.linspace(0, 0.02, 9)
p = sum(np.sqrt(2) * abs(e) * np.cos(2*np.pi*50*t + np.angle(e)) *
        np.sqrt(2) * abs(i) * np.cos(2*np.pi*50*t + np.angle(i)) for e, i in zip(Es, I))
print("p(t) over one period (kW):", np.round(p / 1e3, 3))
per phase: Ia =  38.240 at  -14.39 deg A, V_load = 227.401 at   -0.63 deg V
load P = 25.34 kW, Q = 6.21 kvar, pf = 0.9713
cable loss = 219 W
three-phase:  38.240 at  -14.39 deg,  38.240 at -134.39 deg,  38.240 at +105.61 deg
heater star point below 1e-9 V: True | line currents sum to zero: True
oven phase current Iab =  11.743 at   +2.81 deg A
p(t) over one period (kW): [25.558 25.558 25.558 25.558 25.558 25.558 25.558 25.558 25.558]

The full solution has the heater star point at zero volts with no neutral wire, exactly as the per-phase argument says, and the oven's delta phase current is 11.74 A∠2.81∘11.74\ \text{A}\angle 2.81^\circ: 1/31/\sqrt{3} of the oven's own line current (20.34 A∠−27.19∘20.34\ \text{A}\angle -27.19^\circ) and 30∘30^\circ ahead of it. The instantaneous source power is a constant 25.56 kW25.56\ \text{kW}.

Interactive: the per-phase circuit and the delta-star equivalence

The netlist lab is the per-phase circuit of the figure (the cable inductance is 0.08/(2π⋅50)=254.6 μH0.08/(2\pi \cdot 50) = 254.6\ \mu\text{H}, the oven's 5 Ω5\ \Omega is 15.92 mH15.92\ \text{mH}). Its plot sweeps frequency; read the values at the 50 Hz50\ \text{Hz} cursor. There it shows the load bus l at 227.4 V∠−0.6∘227.4\ \text{V}\angle -0.6^\circ, the cable current 38.24 A∠−14.4∘38.24\ \text{A}\angle -14.4^\circ, 20.34 A20.34\ \text{A} in the oven branch and 18.95 A18.95\ \text{A} in the heater. Slide the heater resistance down (more heaters switched on) and watch the drop grow.

0100200100m1101001k10kf (Hz)|V| (V)|V(l)||V(s)|phasors at f = 50.00 Hz (magnitude @ phase)V(s)230 V @ 0.0 degV(m)228 V @ 0.1 degV(l)227 V @ -0.6 degV(a)102 V @ 62.8 degI(V1)38.2 A @ 165.6 degI(RL)38.2 A @ -14.4 degI(LL)38.2 A @ -14.4 degI(RA)20.3 A @ -27.2 degI(LA)20.3 A @ -27.2 degI(RB)19.0 A @ -0.6 deg

The three-phase lab, set to delta with R=30 ΩR = 30\ \Omega and X=15 ΩX = 15\ \Omega (no cable), reads line currents of 20.57 A∠−26.6∘20.57\ \text{A}\angle -26.6^\circ, a phase current Iab=11.88 A∠3.4∘\mathbf{I}_{ab} = 11.88\ \text{A}\angle 3.4^\circ and P=12.70 kWP = 12.70\ \text{kW}. Switch it to star with R=10 ΩR = 10\ \Omega, X=5 ΩX = 5\ \Omega and the line currents and power are identical: ZΔ/3Z_\Delta/3 is the star equivalent. (Without the cable the oven gets the full 230 V230\ \text{V}, so its current is a little higher than the 20.34 A20.34\ \text{A} above.)

VaVbVcIaIbIcV solid, I thin (own scale)delta-pk0+pk0T2Tphase voltages, peak 325 V-pk0+pk0T2Tline currents, peak 29.1 AP = 12.7 kW Q = 6.35 kvar S = 14.2 kVApf = 0.894 balanced IN = 0 A

Guided lab (simulation only, plus a resistor analogue)

Hand calculation. Redo the worked example with the heaters switched off: Ia=230/(0.05+j0.08+10+j5)\mathbf{I}_a = 230/(0.05 + j0.08 + 10 + j5).

Simulation. In the netlist lab raise RB to its maximum (50 Ω50\ \Omega, nearly off) and compare with your hand result; in Python delete the heater term.

What an engineer would measure. With a CAT III rated power analyser at the board and at the workshop, a qualified electrician would see line voltages near 400 V400\ \text{V} at the board and about 394 V394\ \text{V} at the loads at full load, three line currents within a few percent of 38 A38\ \text{A} (real loads are never perfectly balanced), and a power factor near 0.970.97. Clamp meters are typically good to 22 to 3 %3\ \% of reading, so a 1 %1\ \% voltage drop is at the edge of what two separate instruments can resolve; measuring the drop directly between the two ends with one instrument is better.

Bench analogue. The per-phase circuit is just a source, a series impedance and a load. Build it at signal level: a function generator at 5 V5\ \text{V} rms, 50 Hz50\ \text{Hz}, a 1 Ω1\ \Omega resistor for the cable and 100 Ω100\ \Omega for the load, and measure the 1 %1\ \% drop with a DMM on AC volts.

Hazards and safe setup. Function-generator levels only. Never measure on the mains or on a distribution board.

Pitfalls

  • Forgetting the factor 3 in power, or using 3\sqrt{3} on a per-phase power.
  • Using the line voltage in the per-phase circuit. The per-phase circuit is line-to-neutral: 230 V230\ \text{V}, not 400 V400\ \text{V}.
  • Converting a delta load with ZΔZ_\Delta instead of ZΔ/3Z_\Delta/3.
  • Applying the method to unbalanced systems. With unequal phases the star points shift; use full three-phase analysis (Unbalanced Loads) or symmetrical components.

Practice

  1. A balanced delta load of 45+j24 Ω45 + j24\ \Omega per phase is fed at 400 V400\ \text{V} (line) with no line impedance. Find the line current and the total power.
  2. In the worked example, what cable resistance per phase would make the loss 1 %1\ \% of the load power?
  3. A balanced load draws 50 kW50\ \text{kW} at pf 0.80.8 lagging from a 400 V400\ \text{V} supply. Find the line current and the per-phase star-equivalent impedance.
Answer
  1. Star equivalent 15+j8 Ω15 + j8\ \Omega, ∣Z∣=17 Ω\lvert Z \rvert = 17\ \Omega; IL=230.9/17=13.58 AI_L = 230.9/17 = 13.58\ \text{A}; P=3⋅13.582⋅15=8.30 kWP = 3 \cdot 13.58^2 \cdot 15 = 8.30\ \text{kW}.
  2. 3I2R=253 W3 I^2 R = 253\ \text{W} with I≈38.2 AI \approx 38.2\ \text{A} gives R≈0.058 ΩR \approx 0.058\ \Omega (the current hardly changes with so small a resistance).
  3. IL=50 000/(3⋅400⋅0.8)=90.2 AI_L = 50\,000/(\sqrt{3} \cdot 400 \cdot 0.8) = 90.2\ \text{A}; ∣Z∣=230.9/90.2=2.56 Ω\lvert Z \rvert = 230.9/90.2 = 2.56\ \Omega at 36.87∘36.87^\circ: 2.05+j1.54 Ω2.05 + j1.54\ \Omega.

Test yourself

The star equivalent of a balanced delta load of ZΔZ_\Delta per phase is…

  1. 3ZΔ3Z_\Delta
  2. ZΔ/3Z_\Delta/3
  3. 3ZΔ\sqrt{3}Z_\Delta
  4. ZΔZ_\Delta

In a balanced three-wire system without a neutral, the load star point is at…

  1. the line voltage
  2. the same potential as the source neutral
  3. half the phase voltage
  4. an undefined potential

The instantaneous power of a balanced three-phase load is…

  1. pulsating at 100 Hz
  2. constant
  3. zero on average
  4. pulsating at 150 Hz

A per-phase calculation gives S=10+j4\mathbf{S} = 10 + j4 kVA per phase. The three-phase total is…

  1. 10 + j4 kVA
  2. 17.3 + j6.9 kVA
  3. 30 + j12 kVA
  4. 90 + j36 kVA