Balanced Three-Phase Systems and Per-Phase Analysis
A workshop takes its supply from a board through a cable. On it run a delta-connected oven and a bank of star-connected heaters. What voltage do the loads actually get, how much current flows in the cable, and what does the cable waste? Writing out all three phases means nine complex unknowns; for a balanced system you need to solve only one phase. This lesson turns that shortcut into a reliable method, which every later calculation in the course (load flow, faults, stability) relies on. Star and delta loads, line and phase quantities and the balanced source were introduced in Three-Phase Circuits; here they are combined with line impedance and mixed loads.
Safety: three-phase installations can kill. This lesson works by calculation and simulation only; nothing here is built or measured on the mains.
Why one phase is enough
In a balanced system the source voltages have equal magnitude and are apart, and every phase has the same impedances. Then the three currents are also equal and apart, they sum to zero, and every star point is at the same potential as the source neutral, whether or not a neutral wire is present. You can therefore join all star points with an imaginary zero-impedance neutral and cut out one phase: phase a, from line to neutral, with its share of every element. The other phases are the same answer shifted by and .
The recipe:
- Convert every delta element (load or source) to an equivalent star: , .
- Draw one phase from line a to neutral, with the line impedance in series and the star-equivalent loads in parallel.
- Solve it with ordinary phasor analysis (AC Nodal and Mesh).
- Convert back: line voltages are times larger and lead by ; a delta load's phase current is the line current divided by , leading by .
- Multiply powers by three: .
Constant power: why three phases
In phase a, and . Adding the three phases,
because the three double-frequency terms cancel. A single-phase load's power pulses at between and ; a balanced three-phase load draws a steady flow, so its motor torque does not pulsate. The program below checks this numerically.
Worked example: the workshop
Given: a balanced source (phase a reference ); a cable of per phase; an oven of per phase in delta; heaters of per phase in star. (Calculation only.)
Find: the load voltage, the cable current, the oven's phase current, the total power, the cable loss and the voltage drop.
Solve: the oven in star is . In parallel with :
Check: the source delivers , which equals the of the loads plus the cable loss. The approximate drop formula , with the load's , gives and agrees with .
In Python: one phase, then all three
The program solves the per-phase circuit, then solves the full three-phase circuit by nodal analysis with the oven really in delta and no neutral wire, to show that the shortcut gives the same answer.
import numpy as np
a = np.exp(2j * np.pi / 3)
pol = lambda z: f"{abs(z):7.3f} at {np.degrees(np.angle(z)):+7.2f} deg"
V, Zl = 230.0, 0.05 + 0.08j
Zd, Zh = 30 + 15j, 12.0 # oven per phase (delta), heater per phase (star)
# 1) per-phase equivalent
Zp = 1 / (3 / Zd + 1 / Zh) # delta -> star is Zd/3
Ia = V / (Zl + Zp)
Vl = Ia * Zp
print("per phase: Ia =", pol(Ia), "A, V_load =", pol(Vl), "V")
S = 3 * Vl * np.conj(Ia)
print(f"load P = {S.real/1e3:.2f} kW, Q = {S.imag/1e3:.2f} kvar, pf = {S.real/abs(S):.4f}")
print(f"cable loss = {3 * abs(Ia)**2 * Zl.real:.0f} W")
# 2) full three-phase nodal analysis: unknowns = load-bus voltages (a, b, c) and heater star point n
Es = V * np.array([1, a**2, a]) # source phase voltages, sequence a-b-c
yl, yd, yh = 1 / Zl, 1 / Zd, 1 / Zh
Y = np.zeros((4, 4), complex); J = np.zeros(4, complex)
for k in range(3):
Y[k, k] += yl + 2 * yd + yh # cable, two delta branches, heater
J[k] += yl * Es[k]
for m in range(3):
if m != k:
Y[k, m] -= yd # delta branch between lines k and m
Y[k, 3] -= yh; Y[3, k] -= yh
Y[3, 3] = 3 * yh
U = np.linalg.solve(Y, J)
I = (Es - U[:3]) * yl
print("three-phase:", ", ".join(pol(i) for i in I))
print("heater star point below 1e-9 V:", abs(U[3]) < 1e-9, "| line currents sum to zero:", abs(I.sum()) < 1e-9)
print("oven phase current Iab =", pol((U[0] - U[1]) * yd), "A")
# 3) instantaneous power is constant
t = np.linspace(0, 0.02, 9)
p = sum(np.sqrt(2) * abs(e) * np.cos(2*np.pi*50*t + np.angle(e)) *
np.sqrt(2) * abs(i) * np.cos(2*np.pi*50*t + np.angle(i)) for e, i in zip(Es, I))
print("p(t) over one period (kW):", np.round(p / 1e3, 3))per phase: Ia = 38.240 at -14.39 deg A, V_load = 227.401 at -0.63 deg V
load P = 25.34 kW, Q = 6.21 kvar, pf = 0.9713
cable loss = 219 W
three-phase: 38.240 at -14.39 deg, 38.240 at -134.39 deg, 38.240 at +105.61 deg
heater star point below 1e-9 V: True | line currents sum to zero: True
oven phase current Iab = 11.743 at +2.81 deg A
p(t) over one period (kW): [25.558 25.558 25.558 25.558 25.558 25.558 25.558 25.558 25.558]
The full solution has the heater star point at zero volts with no neutral wire, exactly as the per-phase argument says, and the oven's delta phase current is : of the oven's own line current () and ahead of it. The instantaneous source power is a constant .
Interactive: the per-phase circuit and the delta-star equivalence
The netlist lab is the per-phase circuit of the figure (the cable inductance is , the oven's is ). Its plot sweeps frequency; read the values at the cursor. There it shows the load bus l at , the cable current , in the oven branch and in the heater. Slide the heater resistance down (more heaters switched on) and watch the drop grow.
The three-phase lab, set to delta with and (no cable), reads line currents of , a phase current and . Switch it to star with , and the line currents and power are identical: is the star equivalent. (Without the cable the oven gets the full , so its current is a little higher than the above.)
Guided lab (simulation only, plus a resistor analogue)
Hand calculation. Redo the worked example with the heaters switched off: .
Simulation. In the netlist lab raise RB to its maximum (, nearly off) and compare with your hand result; in Python delete the heater term.
What an engineer would measure. With a CAT III rated power analyser at the board and at the workshop, a qualified electrician would see line voltages near at the board and about at the loads at full load, three line currents within a few percent of (real loads are never perfectly balanced), and a power factor near . Clamp meters are typically good to to of reading, so a voltage drop is at the edge of what two separate instruments can resolve; measuring the drop directly between the two ends with one instrument is better.
Bench analogue. The per-phase circuit is just a source, a series impedance and a load. Build it at signal level: a function generator at rms, , a resistor for the cable and for the load, and measure the drop with a DMM on AC volts.
Hazards and safe setup. Function-generator levels only. Never measure on the mains or on a distribution board.
Pitfalls
- Forgetting the factor 3 in power, or using on a per-phase power.
- Using the line voltage in the per-phase circuit. The per-phase circuit is line-to-neutral: , not .
- Converting a delta load with instead of .
- Applying the method to unbalanced systems. With unequal phases the star points shift; use full three-phase analysis (Unbalanced Loads) or symmetrical components.
Practice
- A balanced delta load of per phase is fed at (line) with no line impedance. Find the line current and the total power.
- In the worked example, what cable resistance per phase would make the loss of the load power?
- A balanced load draws at pf lagging from a supply. Find the line current and the per-phase star-equivalent impedance.
Answer
- Star equivalent , ; ; .
- with gives (the current hardly changes with so small a resistance).
- ; at : .
Test yourself
The star equivalent of a balanced delta load of per phase is…
In a balanced three-wire system without a neutral, the load star point is at…
- the line voltage
- the same potential as the source neutral
- half the phase voltage
- an undefined potential
The instantaneous power of a balanced three-phase load is…
- pulsating at 100 Hz
- constant
- zero on average
- pulsating at 150 Hz
A per-phase calculation gives kVA per phase. The three-phase total is…
- 10 + j4 kVA
- 17.3 + j6.9 kVA
- 30 + j12 kVA
- 90 + j36 kVA