Sequence Impedances and Sequence Networks
Symmetrical components split an unbalanced problem into three balanced ones. To use them, every element of the network needs three impedances, one per sequence, and the network needs to be drawn three times: the positive-, negative- and zero-sequence networks. The positive-sequence network is the familiar per-phase circuit. The negative-sequence network looks almost the same but has no sources. The zero-sequence network is the surprising one: whether zero-sequence current can flow at all depends on how transformers are connected and how neutrals are earthed, so it can look completely different from the other two. Getting it right decides earth-fault currents, which are the most common faults on overhead lines.
Safety. Earth faults at grid voltages raise the potential of the ground around the fault (step and touch voltages, see Earthing Systems). This lesson is calculation and simulation only.
Sequence impedances of the main elements
| Element | |||
|---|---|---|---|
| synchronous generator | (or , by time scale); the only element with an EMF, positive sequence only | (average of and ) | (small, from leakage) plus if the star point is earthed through ; open if unearthed |
| transformer | leakage impedance | same as | leakage impedance or open, depending on the winding connection (table below) |
| overhead line, transposed | same as | , typically to times (earth return, earth-wire effects) | |
| cable | from the manufacturer | same as | depends strongly on sheath bonding and earthing; measured or calculated in detail |
| induction motor | locked-rotor impedance (for faults) | about the locked-rotor impedance | usually open (star point not earthed) |
Why ? A neutral impedance carries the sum of the three phase currents, , so it drops . Seen per phase in the zero-sequence network, that is an impedance . In the positive and negative networks the neutral current is zero, so does not appear at all.
Transformers in the zero-sequence network
Zero-sequence current in a winding needs a return path through its neutral, and a delta winding lets it circulate inside the delta but not leave through the lines:
| Connection | Zero-sequence path |
|---|---|
| YNyn (both stars earthed) | series leakage impedance between the two sides: zero-sequence current passes through |
| YNd | from the YN side to the reference through the leakage impedance (the delta acts as a short circuit for ); open towards the delta side |
| Yd, Yy, Dd, Dyn seen from D | open from the unearthed or delta side |
| Dyn | from the yn side to the reference; open towards the D side |
| any earthed star with | add in series on that side |
Three-limb core-type transformers also have a finite zero-sequence magnetising impedance (the flux returns through air and the tank), which matters for some connections; here it is neglected. One more effect: a star–delta transformer shifts positive-sequence quantities by and negative-sequence quantities by the opposite angle (Three-Phase Transformers and Vector Groups). Magnitudes are unaffected, so fault-current calculations at one bus can ignore the shift, but currents and voltages transferred across the transformer must include it.
Plant P1's sequence networks
Plant P1: G1 (, ) with its star point earthed through a resistor, T1 connected YNd1 (HV star solidly earthed, LV delta, ), two circuits each with , , and beyond them the infinite bus. For the zero sequence the remote grid is solidly earthed with (an assumption added for this lesson).
Worked example: Thevenin sequence impedances at bus H
Given: Plant P1 as above, on .
Find: , , seen from the bus H.
Solve:
The generator does not appear in at all: the delta winding of T1 blocks its zero-sequence path.
Check: at bus H, because the YN winding of a large transformer is a strong local earth: a single line-to-ground fault at H will draw more current than a three-phase fault (Unsymmetrical Faults). At the generator's terminals the opposite holds: there is dominated by , so an earth fault on the generator side is limited to about , which is exactly why generators are earthed through high impedance: an internal earth fault then does little damage.
In Python: sequence Z-buses for Plant P1
import numpy as np
# Plant P1 sequence data, pu on 100 MVA (reactances; resistances neglected)
X1g, X2g, X0g = 0.18, 0.18, 0.06 # G1: subtransient, negative, zero sequence
Zb11 = 11.0**2 / 100 # base impedance at 11 kV, ohm
Rn = 635.0 / Zb11 # G1 neutral resistor 635 ohm, in pu
xT = 0.10 # T1 YNd1: HV star solidly earthed, LV delta
x1L, x0L = 0.40, 1.20 # each 132 kV circuit
x0grid = 0.05 # remote grid's zero-sequence reactance (earthed)
def par(*z):
return 1 / sum(1 / zz for zz in z)
def zbus(branches):
"""branches: (node_a, node_b or None, z). Nodes 'G' (11 kV) and 'H' (132 kV)."""
idx = {"G": 0, "H": 1}
Y = np.zeros((2, 2), dtype=complex)
for a, b, z in branches:
y = 1 / z
Y[idx[a], idx[a]] += y
if b is not None:
Y[idx[b], idx[b]] += y
Y[idx[a], idx[b]] -= y; Y[idx[b], idx[a]] -= y
return np.linalg.inv(Y)
# positive and negative sequence: G1 to reference, T1 between G and H, lines from H to the infinite bus (reference)
Z1 = zbus([("G", None, 1j * X1g), ("G", "H", 1j * xT), ("H", None, 1j * x1L / 2)])
Z2 = zbus([("G", None, 1j * X2g), ("G", "H", 1j * xT), ("H", None, 1j * x1L / 2)])
# zero sequence: the delta winding isolates G from H. G1: j X0 + 3 Rn to reference. H: T1's leakage
# reactance straight to the reference (the YN winding with the delta as a short), and the lines plus the grid
Z0 = zbus([("G", None, 1j * X0g + 3 * Rn), ("H", None, 1j * xT), ("H", None, 1j * (x0L / 2 + x0grid))])
for bus, k in [("H (132 kV)", 1), ("G (11 kV)", 0)]:
z1, z2, z0 = Z1[k, k], Z2[k, k], Z0[k, k]
print(f"bus {bus}: Z1 = {z1.imag:.4f}j, Z2 = {z2.imag:.4f}j, Z0 = {abs(z0.real):.1f} + {z0.imag:.4f}j pu")
print(f"G1 neutral resistor: {Rn:.1f} pu, so 3Rn = {3*Rn:.0f} pu")
print(f"zero-sequence coupling between G and H: Z0[G,H] = {abs(Z0[0, 1]):.4f} pu (delta winding)")
print(f"check by hand at H: Z0 = {par(xT, x0L/2 + x0grid):.4f} pu")bus H (132 kV): Z1 = 0.1167j, Z2 = 0.1167j, Z0 = 0.0 + 0.0867j pu
bus G (11 kV): Z1 = 0.1125j, Z2 = 0.1125j, Z0 = 1574.4 + 0.0600j pu
G1 neutral resistor: 524.8 pu, so 3Rn = 1574 pu
zero-sequence coupling between G and H: Z0[G,H] = 0.0000 pu (delta winding)
check by hand at H: Z0 = 0.0867 pu
Interactive: measure a zero-sequence impedance by injection
How do utilities find of a real network? By injecting a test current into the three phases connected together (so it is pure zero sequence) and measuring the voltage. The netlist lab does that on Plant P1's zero-sequence network at bus H: a source into node h, T1's to the reference ( at ), and the lines' (LL, ) in series with the grid's . Read the value (the lab sweeps frequency): h shows at , i.e. . The transformer takes of the current. Lengthen the lines with the LL slider and almost all of it goes through T1.
Guided lab: positive and zero sequence of a three-wire model
Hand calculation. A low-voltage model "line": three insulated wires twisted loosely together over , with a fourth wire as the return. Predict that the zero-sequence loop (three wires in parallel out, return wire back) and the positive-sequence loop (one wire out, another back, halved) have different inductances because the mutual couplings add in one case and cancel in the other.
Simulation. Model the measured self and mutual inductances in a matrix and transform it with as in the previous lesson.
What you would measure. With an LCR meter at : the loop inductance of wire 1 out and wire 2 back gives ; wires 1, 2 and 3 in parallel out and the return wire back give the zero-sequence loop. Expect (per phase) clearly larger than , by a factor of to depending on how far the return wire runs from the bundle; LCR readings of a few microhenries carry roughly to uncertainty, dominated by lead placement.
Hazards and safe setup. An LCR meter's test signal only; no connection to any supply.
Pitfalls
- Copying the positive network for the zero sequence. Transformer connections and neutral earthing change it completely.
- Forgetting , or adding it in the positive network.
- Putting the generator EMF in the negative or zero network. Balanced sources produce positive sequence only.
- Assuming for lines. It is usually two to four times larger.
- Ignoring the shifts when transferring sequence currents across a star–delta transformer.
Practice
- If T1 were connected Yd (HV star unearthed), what would at bus H be?
- G1's neutral resistor is . Estimate the earth-fault current for a fault at the generator terminals (phase voltage ).
- Why does a Dyn11 distribution transformer provide an earthed neutral for the low-voltage network but not for the medium-voltage side?
Answer
- T1 would be open for zero sequence, so only the lines and grid remain: .
- (the generator's own and the system capacitance change this only slightly).
- Its yn winding is earthed, so zero-sequence current from the LV network can return through it (the delta lets it circulate); the delta MV winding offers no path for MV zero-sequence current.
Test yourself
A neutral earthing impedance appears in the zero-sequence network as…
- it does not appear
Seen from its YN side, a YNd transformer in the zero-sequence network is…
- open
- its leakage impedance to the reference
- a short to the delta side
- infinite
Which network contains the generator EMF?
- positive sequence only
- negative sequence only
- zero sequence only
- all three
Typically, the zero-sequence impedance of an overhead line compared with its positive-sequence impedance is…
- smaller
- equal
- 2 to 4 times larger
- 100 times larger