Home › Power Systems: Three-Phase, Generation, Grids & Protection › Voltage Stability: PV Curves and Collapse

Voltage Stability: PV Curves and Collapse

Several large blackouts did not start with a short circuit or a frequency collapse. Voltages in a heavily loaded region sagged over minutes, tap changers pushed load voltages back up, generators hit their reactive limits one after another, and the voltage suddenly fell away. A network can only deliver so much power to a load over a given reactance; near that limit, extra load lowers the power actually delivered. This lesson draws the PV (nose) curve of the simplest system, finds the maximum loadability in closed form, and explains why reactive support, tap changers and load behaviour decide how close to the nose a system may run.

Safety: transmission voltages and load behaviour are studied here by calculation and simulation only. The bench analogue is a resistor network on a current-limited low-voltage supply.

The two-bus system

A source EE (a strong grid) feeds a load P+jQP + jQ through a reactance XX. The load has a constant power factor, Q=Ptan⁡φQ = P\tan\varphi. With VV the load voltage, the power-flow equations (Reactive Power and Voltage) reduce to a quadratic in V2V^2:

V4+(2QX−E2)V2+X2(P2+Q2)=0V^4 + \left(2QX - E^2\right)V^2 + X^2\left(P^2 + Q^2\right) = 0

For each PP there are two solutions: the upper, normal one, and a lower one at low voltage and high current. They merge at the nose, the maximum power the network can deliver at that power factor. Setting the discriminant to zero gives, for a lagging load (sin⁡φ>0\sin\varphi > 0; use −sin⁡φ-\sin\varphi for leading):

Pmax⁡=E2cos⁡φ2X (1+sin⁡φ),Vnose=E2 (1+sin⁡φ)P_{\max} = \frac{E^2 \cos\varphi}{2X\,(1 + \sin\varphi)}, \qquad V_\text{nose} = \frac{E}{\sqrt{2\,(1 + \sin\varphi)}}

At unity power factor Pmax⁡=E2/2XP_{\max} = E^2/2X at V=E/2V = E/\sqrt{2}, the familiar maximum power transfer, reached when the load resistance equals the source reactance in magnitude.

Why the nose is unstable

Above the nose no operating point exists. On the lower branch the system behaves backwards: a load that tries to draw more power (lower resistance) gets less. Loads whose power recovers after a voltage dip make this dangerous:

  • On-load tap changers at distribution transformers restore the customer voltage within a minute or so, which restores constant-impedance load power and pushes the transmission system further toward the nose.
  • Thermostatic loads (heating, cooling) run longer at low voltage, restoring energy over minutes.
  • Induction motors draw nearly constant power and more reactive power as voltage falls; below a critical voltage they stall and draw starting current.
  • Generator reactive limits. Over-excitation limiters reduce a generator's reactive output after a time delay; the system loses the voltage support it was counting on.

Voltage stability is mostly a local and reactive-power problem: reactive power cannot be transported far, because QQ losses (I2XI^2X) grow rapidly with load.

Worked example: a weak connection

Given: E=1.0 puE = 1.0\ \text{pu}, X=0.5 puX = 0.5\ \text{pu} (a long line or weak tie on 100 MVA100\ \text{MVA}), a load at power factor 0.950.95 lagging drawing P=0.6 puP = 0.6\ \text{pu}.

Find: the load voltage, the maximum loadability at this power factor and the margin.

Solve: tan⁡φ=0.3287\tan\varphi = 0.3287, sin⁡φ=0.3122\sin\varphi = 0.3122, Q=0.1972 puQ = 0.1972\ \text{pu}.

V4+(2⋅0.1972⋅0.5−1)V2+0.25 (0.36+0.0389)=0 ⇒ V2=0.6492, V=0.806 puPmax⁡=0.952⋅0.5⋅1.3122=0.724 pu,Vnose=12.6245=0.617 pu\begin{aligned} V^4 + (2 \cdot 0.1972 \cdot 0.5 - 1)V^2 + 0.25\,(0.36 + 0.0389) &= 0 \ \Rightarrow\ V^2 = 0.6492,\ V = 0.806\ \text{pu} \\ P_{\max} = \frac{0.95}{2 \cdot 0.5 \cdot 1.3122} = 0.724\ \text{pu}, \qquad V_\text{nose} &= \frac{1}{\sqrt{2.6245}} = 0.617\ \text{pu} \end{aligned}

The loadability margin is (0.724−0.6)/0.6=21 %(0.724 - 0.6)/0.6 = 21\ \%.

Check: the load voltage of 0.81 pu0.81\ \text{pu} is already unacceptable for customers, while the margin to collapse is only about a fifth of the load. Compensating the load to unity power factor raises Pmax⁡P_{\max} to 1.0 pu1.0\ \text{pu}; overcompensating to 0.950.95 leading raises it to 1.38 pu1.38\ \text{pu}, but the nose voltage then moves up to 0.85 pu0.85\ \text{pu}. Heavy capacitive compensation can hide the approaching limit behind normal-looking voltages, which is why operators track margins in MW, not voltages alone.

In Python: PV curves for several power factors

python · try it yourself
import numpy as np
import matplotlib.pyplot as plt

E, X = 1.0, 0.5

def pv_curve(pf, lead=False, n=400):
    s = np.sin(np.arccos(pf)) * (-1 if lead else 1)
    t = s / pf
    Pmax = E**2 * pf / (2 * X * (1 + s))
    P = np.linspace(0, Pmax, n)
    b = 2 * P * t * X - E**2
    disc = np.maximum(b**2 - 4 * X**2 * P**2 * (1 + t**2), 0)
    Vu, Vl = np.sqrt((-b + np.sqrt(disc)) / 2), np.sqrt((-b - np.sqrt(disc)) / 2)
    return P, Vu, Vl, Pmax, E / np.sqrt(2 * (1 + s))

fig, ax = plt.subplots(figsize=(6, 3.6))
for pf, lead, name in [(0.90, False, "0.90 lag"), (0.95, False, "0.95 lag"), (1.0, False, "unity"), (0.95, True, "0.95 lead")]:
    P, Vu, Vl, Pmax, Vn = pv_curve(pf, lead)
    print(f"pf {name:9s}: Pmax = {Pmax:.3f} pu at V = {Vn:.3f} pu")
    line, = ax.plot(P, Vu, label=name); ax.plot(P, Vl, "--", color=line.get_color())

P0, s = 0.6, np.sin(np.arccos(0.95)); Q0 = P0 * s / 0.95
b = 2 * Q0 * X - 1; c = X**2 * (P0**2 + Q0**2)
V0 = np.sqrt((-b + np.sqrt(b * b - 4 * c)) / 2)
print(f"operating point P = {P0} pu, pf 0.95 lag: V = {V0:.3f} pu, margin = {(pv_curve(0.95)[3] - P0) / P0:.1%}")
ax.plot(P0, V0, "ko")
ax.set_xlabel("load P (pu)"); ax.set_ylabel("load voltage V (pu)"); ax.set_ylim(0, 1.1)
ax.grid(alpha=0.3); ax.legend(fontsize=8); fig.tight_layout()
plt.show()
pf 0.90 lag : Pmax = 0.627 pu at V = 0.590 pu
pf 0.95 lag : Pmax = 0.724 pu at V = 0.617 pu
pf unity    : Pmax = 1.000 pu at V = 0.707 pu
pf 0.95 lead: Pmax = 1.381 pu at V = 0.853 pu
operating point P = 0.6 pu, pf 0.95 lag: V = 0.806 pu, margin = 20.7%

The dashed lower branches are the unstable solutions. In larger networks the same curve is traced by continuation power flow: a load-flow solver (Newton–Raphson) is stepped along increasing load, and the Jacobian becomes singular at the nose. Its smallest singular value or eigenvalue is a practical proximity indicator.

Interactive: maximum power through a reactance

A unity-power-factor version of the example in the netlist lab: a 1 V1\ \text{V} (1 pu1\ \text{pu}) source behind 1.592 mH1.592\ \text{mH} (X=0.5 ΩX = 0.5\ \Omega at 50 Hz50\ \text{Hz}, i.e. 0.5 pu0.5\ \text{pu}) feeding a load resistor RL. Read the values at the 50 Hz50\ \text{Hz} cursor (the plot sweeps frequency). At RL=2R_L = 2 the load voltage is 0.970 pu0.970\ \text{pu} and P=V2/R=0.47 puP = V^2/R = 0.47\ \text{pu}; at RL=0.5R_L = 0.5 (equal to XX) it is 0.707 pu0.707\ \text{pu} and P=1.0 puP = 1.0\ \text{pu}, the nose; at RL=0.25R_L = 0.25 the voltage is 0.447 pu0.447\ \text{pu} and PP has fallen back to 0.8 pu0.8\ \text{pu}: the lower branch, where a "bigger" load takes less power.

0.00.51.0100m1101001k10kf (Hz)|V| (V)|V(l)|phasors at f = 50.00 Hz (magnitude @ phase)V(s)1.00 V @ 0.0 degV(l)970 mV @ -14.0 degI(V1)485 mA @ 166.0 degI(LX)485 mA @ -14.0 degI(RL)485 mA @ -14.0 deg

Guided lab: a DC nose curve

Hand calculation. A 12 V12\ \text{V} bench supply behind a 10 Ω10\ \Omega resistor (the "line") feeds a load resistor RLR_L. Power P=144RL/(10+RL)2 WP = 144 R_L/(10 + R_L)^2\ \text{W}; maximum 3.6 W3.6\ \text{W} at RL=10 ΩR_L = 10\ \Omega, 6 V6\ \text{V}. Tabulate VV and PP for RLR_L from 22 to 50 Ω50\ \Omega.

Simulation. Enter the circuit in the netlist lab (DC analysis) with a slider on RLR_L.

What you would measure. Use switched 5 W5\ \text{W} resistors (22 to 50 Ω50\ \Omega) for RLR_L; a 100 Ω100\ \Omega, 5 W5\ \text{W} rheostat will not do, because its winding is rated for only 5/100=0.22 A\sqrt{5/100} = 0.22\ \text{A} however little of it is in circuit, and the low settings carry up to 1 A1\ \text{A} and DMMs for VV and II. Plot VV against PP: the DC analogue of the nose, with the maximum at RL=10 ΩR_L = 10\ \Omega. Expect agreement within the ±5 %\pm 5\ \% tolerance of the resistors; the line resistor warms up and drifts, so take readings quickly.

Hazards and safe setup. Bench supply at 12 V12\ \text{V} with the current limit at 1.5 A1.5\ \text{A}; the 10 Ω10\ \Omega line resistor dissipates up to 14.4 W14.4\ \text{W} when RLR_L is near zero, so use a 25 W25\ \text{W} resistor on a heat-proof surface and never set RLR_L below 2 Ω2\ \Omega.

Pitfalls

  • Judging security by voltage. Compensated systems can be near the nose at normal voltage; use loadability margins.
  • Constant-power load models everywhere. They exaggerate collapse at low voltage; real loads mix constant impedance, current and power with time-varying recovery.
  • Forgetting the generators' reactive limits. A PV bus at its limit becomes a PQ bus, and the nose moves sharply left.
  • Tap changers as a cure. At the nose they make things worse; blocking tap changers on low transmission voltage is a standard emergency action, as is undervoltage load shedding.

Practice

  1. Find Pmax⁡P_{\max} and VnoseV_\text{nose} for E=1.05 puE = 1.05\ \text{pu}, X=0.4 puX = 0.4\ \text{pu} and unity power factor.
  2. For pf 0.90.9 lagging and X=0.5X = 0.5, what is the nose power, and by how much does correcting to unity raise it?
  3. Why does reactive power support have to be close to the load?
Answer
  1. Pmax⁡=1.052/(2⋅0.4)=1.378 puP_{\max} = 1.05^2/(2 \cdot 0.4) = 1.378\ \text{pu} at V=1.05/2=0.742 puV = 1.05/\sqrt{2} = 0.742\ \text{pu}.
  2. 0.627 pu0.627\ \text{pu}; unity gives 1.0 pu1.0\ \text{pu}, 60 %60\ \% more.
  3. Sending QQ through reactance consumes I2XI^2X of reactive power and drops voltage roughly in proportion to QX/VQX/V; distant sources lose most of it on the way, especially when the system is stressed and currents are high.

Test yourself

At the nose of a PV curve…

  1. the voltage is maximum
  2. the network delivers its maximum power at that power factor; the load-flow Jacobian is singular
  3. the frequency collapses
  4. the load is purely reactive

For E=1E = 1, X=0.5X = 0.5 pu and a unity-power-factor load, the maximum deliverable power is…

  1. 0.5 pu
  2. 0.707 pu
  3. 1.0 pu
  4. 2.0 pu

Why can on-load tap changers push a stressed system toward voltage collapse?

  1. they inject harmonics
  2. they restore load voltage, and so load power, demanding more from the transmission system near its limit
  3. they reduce the frequency
  4. they open breakers

Heavy shunt-capacitor compensation near a load…

  1. lowers the maximum loadability
  2. raises loadability but can move the nose to near-normal voltages, hiding the margin
  3. has no effect on voltage stability
  4. turns the load into a generator