Voltage Stability: PV Curves and Collapse
Several large blackouts did not start with a short circuit or a frequency collapse. Voltages in a heavily loaded region sagged over minutes, tap changers pushed load voltages back up, generators hit their reactive limits one after another, and the voltage suddenly fell away. A network can only deliver so much power to a load over a given reactance; near that limit, extra load lowers the power actually delivered. This lesson draws the PV (nose) curve of the simplest system, finds the maximum loadability in closed form, and explains why reactive support, tap changers and load behaviour decide how close to the nose a system may run.
Safety: transmission voltages and load behaviour are studied here by calculation and simulation only. The bench analogue is a resistor network on a current-limited low-voltage supply.
The two-bus system
A source (a strong grid) feeds a load through a reactance . The load has a constant power factor, . With the load voltage, the power-flow equations (Reactive Power and Voltage) reduce to a quadratic in :
For each there are two solutions: the upper, normal one, and a lower one at low voltage and high current. They merge at the nose, the maximum power the network can deliver at that power factor. Setting the discriminant to zero gives, for a lagging load (; use for leading):
At unity power factor at , the familiar maximum power transfer, reached when the load resistance equals the source reactance in magnitude.
Why the nose is unstable
Above the nose no operating point exists. On the lower branch the system behaves backwards: a load that tries to draw more power (lower resistance) gets less. Loads whose power recovers after a voltage dip make this dangerous:
- On-load tap changers at distribution transformers restore the customer voltage within a minute or so, which restores constant-impedance load power and pushes the transmission system further toward the nose.
- Thermostatic loads (heating, cooling) run longer at low voltage, restoring energy over minutes.
- Induction motors draw nearly constant power and more reactive power as voltage falls; below a critical voltage they stall and draw starting current.
- Generator reactive limits. Over-excitation limiters reduce a generator's reactive output after a time delay; the system loses the voltage support it was counting on.
Voltage stability is mostly a local and reactive-power problem: reactive power cannot be transported far, because losses () grow rapidly with load.
Worked example: a weak connection
Given: , (a long line or weak tie on ), a load at power factor lagging drawing .
Find: the load voltage, the maximum loadability at this power factor and the margin.
Solve: , , .
The loadability margin is .
Check: the load voltage of is already unacceptable for customers, while the margin to collapse is only about a fifth of the load. Compensating the load to unity power factor raises to ; overcompensating to leading raises it to , but the nose voltage then moves up to . Heavy capacitive compensation can hide the approaching limit behind normal-looking voltages, which is why operators track margins in MW, not voltages alone.
In Python: PV curves for several power factors
import numpy as np
import matplotlib.pyplot as plt
E, X = 1.0, 0.5
def pv_curve(pf, lead=False, n=400):
s = np.sin(np.arccos(pf)) * (-1 if lead else 1)
t = s / pf
Pmax = E**2 * pf / (2 * X * (1 + s))
P = np.linspace(0, Pmax, n)
b = 2 * P * t * X - E**2
disc = np.maximum(b**2 - 4 * X**2 * P**2 * (1 + t**2), 0)
Vu, Vl = np.sqrt((-b + np.sqrt(disc)) / 2), np.sqrt((-b - np.sqrt(disc)) / 2)
return P, Vu, Vl, Pmax, E / np.sqrt(2 * (1 + s))
fig, ax = plt.subplots(figsize=(6, 3.6))
for pf, lead, name in [(0.90, False, "0.90 lag"), (0.95, False, "0.95 lag"), (1.0, False, "unity"), (0.95, True, "0.95 lead")]:
P, Vu, Vl, Pmax, Vn = pv_curve(pf, lead)
print(f"pf {name:9s}: Pmax = {Pmax:.3f} pu at V = {Vn:.3f} pu")
line, = ax.plot(P, Vu, label=name); ax.plot(P, Vl, "--", color=line.get_color())
P0, s = 0.6, np.sin(np.arccos(0.95)); Q0 = P0 * s / 0.95
b = 2 * Q0 * X - 1; c = X**2 * (P0**2 + Q0**2)
V0 = np.sqrt((-b + np.sqrt(b * b - 4 * c)) / 2)
print(f"operating point P = {P0} pu, pf 0.95 lag: V = {V0:.3f} pu, margin = {(pv_curve(0.95)[3] - P0) / P0:.1%}")
ax.plot(P0, V0, "ko")
ax.set_xlabel("load P (pu)"); ax.set_ylabel("load voltage V (pu)"); ax.set_ylim(0, 1.1)
ax.grid(alpha=0.3); ax.legend(fontsize=8); fig.tight_layout()
plt.show()pf 0.90 lag : Pmax = 0.627 pu at V = 0.590 pu
pf 0.95 lag : Pmax = 0.724 pu at V = 0.617 pu
pf unity : Pmax = 1.000 pu at V = 0.707 pu
pf 0.95 lead: Pmax = 1.381 pu at V = 0.853 pu
operating point P = 0.6 pu, pf 0.95 lag: V = 0.806 pu, margin = 20.7%
The dashed lower branches are the unstable solutions. In larger networks the same curve is traced by continuation power flow: a load-flow solver (Newton–Raphson) is stepped along increasing load, and the Jacobian becomes singular at the nose. Its smallest singular value or eigenvalue is a practical proximity indicator.
Interactive: maximum power through a reactance
A unity-power-factor version of the example in the netlist lab: a () source behind ( at , i.e. ) feeding a load resistor RL. Read the values at the cursor (the plot sweeps frequency). At the load voltage is and ; at (equal to ) it is and , the nose; at the voltage is and has fallen back to : the lower branch, where a "bigger" load takes less power.
Guided lab: a DC nose curve
Hand calculation. A bench supply behind a resistor (the "line") feeds a load resistor . Power ; maximum at , . Tabulate and for from to .
Simulation. Enter the circuit in the netlist lab (DC analysis) with a slider on .
What you would measure. Use switched resistors ( to ) for ; a , rheostat will not do, because its winding is rated for only however little of it is in circuit, and the low settings carry up to and DMMs for and . Plot against : the DC analogue of the nose, with the maximum at . Expect agreement within the tolerance of the resistors; the line resistor warms up and drifts, so take readings quickly.
Hazards and safe setup. Bench supply at with the current limit at ; the line resistor dissipates up to when is near zero, so use a resistor on a heat-proof surface and never set below .
Pitfalls
- Judging security by voltage. Compensated systems can be near the nose at normal voltage; use loadability margins.
- Constant-power load models everywhere. They exaggerate collapse at low voltage; real loads mix constant impedance, current and power with time-varying recovery.
- Forgetting the generators' reactive limits. A PV bus at its limit becomes a PQ bus, and the nose moves sharply left.
- Tap changers as a cure. At the nose they make things worse; blocking tap changers on low transmission voltage is a standard emergency action, as is undervoltage load shedding.
Practice
- Find and for , and unity power factor.
- For pf lagging and , what is the nose power, and by how much does correcting to unity raise it?
- Why does reactive power support have to be close to the load?
Answer
- at .
- ; unity gives , more.
- Sending through reactance consumes of reactive power and drops voltage roughly in proportion to ; distant sources lose most of it on the way, especially when the system is stressed and currents are high.
Test yourself
At the nose of a PV curve…
- the voltage is maximum
- the network delivers its maximum power at that power factor; the load-flow Jacobian is singular
- the frequency collapses
- the load is purely reactive
For , pu and a unity-power-factor load, the maximum deliverable power is…
- 0.5 pu
- 0.707 pu
- 1.0 pu
- 2.0 pu
Why can on-load tap changers push a stressed system toward voltage collapse?
- they inject harmonics
- they restore load voltage, and so load power, demanding more from the transmission system near its limit
- they reduce the frequency
- they open breakers
Heavy shunt-capacitor compensation near a load…
- lowers the maximum loadability
- raises loadability but can move the nose to near-normal voltages, hiding the margin
- has no effect on voltage stability
- turns the load into a generator