An AC line's power transfer is limited by its reactance: P=V1V2Xsin⁡δP = \frac{V_1 V_2}{X}\sin\delta, and XX grows with length. Beyond a few hundred kilometres of overhead line, or a few tens of kilometres of cable, AC runs out of stability margin or drowns in charging current. Two families of power-electronic equipment get around this: HVDC converts to direct current, where reactance plays no part in steady state, and FACTS (flexible AC transmission systems) controls the reactance, voltage or angle of an AC line directly. This lesson explains both at the system level; the converters themselves belong to Power Electronics.

Safety: HVDC converter stations and FACTS devices operate at hundreds of kilovolts and are studied here by calculation and simulation only. DC arcs do not self-extinguish at a current zero, and converter capacitors stay charged after switch-off; these are concepts here, not bench topics.

Why DC

  • Distance. A DC line has no reactance drop and no stability angle; only resistance limits it. Converters are expensive, lines cheaper (two conductors instead of three, narrower towers), so beyond a break-even distance, typically several hundred kilometres overhead and around 5050 to 100 km100\ \text{km} for cables (where AC charging current eats the cable's capacity), DC is cheaper overall.
  • Submarine and underground cables. Long AC cables need shunt reactors every few tens of kilometres; DC cables do not.
  • Asynchronous links. Two grids that are not synchronised (different frequencies, or one too weak to stay in step) can be linked back to back.
  • Control. The power on a DC link is set by the operator, not by the network's impedances, which helps route power and damp oscillations.

Converter technologies

Line-commutated (LCC) Voltage-source (VSC, today mostly modular multilevel, MMC)
switches thyristors (turn off at current zero only) IGBTs (turn on and off at will)
needs a strong AC network to commutate nothing: can start a dead network (black start)
reactive power consumes about 5050 to 60 %60\ \% of PP; needs filters and capacitor banks controls QQ independently at each end, like a STATCOM
reverse power by reversing voltage polarity by reversing current
typical use very high power bulk links (several GW, up to ±800 kV\pm 800\ \text{kV} and above) offshore wind, cable links, multi-terminal grids, weak networks

Configurations: monopole (one high-voltage conductor, earth, sea or metallic return), bipole (two poles ±Vd\pm V_d; either pole can run alone), back-to-back (both converters in one station), and multi-terminal (three or more converters, which needs DC circuit breakers or converters that can block DC faults).

Power flow on a DC link is a resistor problem. With the rectifier at VrV_r and the inverter at ViV_i over a line resistance RR:

Id=Vr−ViR,Pr=VrId,Ploss=Id2RI_d = \frac{V_r - V_i}{R}, \qquad P_r = V_r I_d, \qquad P_\text{loss} = I_d^2 R

A difference of a few percent between the two voltages moves full power, so the converters' controls (current control at one end, voltage control at the other) set the flow precisely.

FACTS

FACTS devices act on one of the three quantities in P=V1V2Xsin⁡δP = \frac{V_1 V_2}{X}\sin\delta:

  • Voltage: the SVC (thyristor-switched capacitors and thyristor-controlled reactors) and the STATCOM (a VSC behaving as a controllable reactive current source) hold bus voltage by injecting or absorbing reactive power (Voltage Control Devices). A STATCOM keeps its full current at low voltage; an SVC's output falls with V2V^2.
  • Reactance: series capacitors (fixed) and the TCSC (thyristor-controlled series capacitor) cancel part of the line reactance: with compensation degree kk, Xeff=X(1−k)X_\text{eff} = X(1 - k), and the transfer limit rises by 1/(1−k)1/(1 - k). Series capacitors can cause subsynchronous resonance with turbine-generator shafts, which TCSCs can damp.
  • Angle: phase-shifting transformers add a controllable angle to steer flow between parallel paths; the UPFC combines a shunt and a series VSC to control all three.

Worked example: 2 GW over 800 km

Given: 2000 MW2000\ \text{MW} to be carried 800 km800\ \text{km}. Option DC: a ±500 kV\pm 500\ \text{kV} bipole, line resistance 0.0125 Ω/km0.0125\ \Omega/\text{km} per pole, converter losses 0.7 %0.7\ \% per station (an assumed figure of the right order for LCC). Option AC: 400 kV400\ \text{kV} circuits with X=0.33 Ω/kmX = 0.33\ \Omega/\text{km}, operated at an angle of at most 30∘30^\circ across the line for stability margin.

Find: the DC losses, and how many AC circuits the angle limit needs, with and without 50 %50\ \% series compensation.

Solve:

Id=2000 MW2⋅500 kV=2.0 kA,R=0.0125⋅800=10 Ω per polePline=2⋅(2.0 kA)2⋅10 Ω=80 MW (4.0 %),Pconv=2⋅0.007⋅2000=28 MWPAC, one circuit=(400 kV)20.33⋅800 Ωsin⁡30∘=160 000264⋅0.5=303 MW\begin{aligned} I_d &= \frac{2000\ \text{MW}}{2 \cdot 500\ \text{kV}} = 2.0\ \text{kA}, \qquad R = 0.0125 \cdot 800 = 10\ \Omega\ \text{per pole} \\ P_\text{line} &= 2 \cdot (2.0\ \text{kA})^2 \cdot 10\ \Omega = 80\ \text{MW}\ (4.0\ \%), \qquad P_\text{conv} = 2 \cdot 0.007 \cdot 2000 = 28\ \text{MW} \\ P_{\text{AC, one circuit}} &= \frac{(400\ \text{kV})^2}{0.33 \cdot 800\ \Omega}\sin 30^\circ = \frac{160\,000}{264} \cdot 0.5 = 303\ \text{MW} \end{aligned}

Check: uncompensated AC needs 2000/303=6.62000/303 = 6.6, so 7 circuits; with 50 %50\ \% series compensation each carries 606 MW606\ \text{MW} and 4 circuits do, still with shunt reactors for the charging current and intermediate switching stations. The DC bipole does it on one tower line with 108 MW108\ \text{MW} (5.4 %5.4\ \%) of losses. That is the typical picture behind long-distance HVDC: fewer lines and controllable flow, paid for with converter stations.

In Python: transfer limits and a DC link

python · try it yourself
import numpy as np

# AC: angle-limited transfer per 400 kV circuit against length, with series compensation
V, x, dmax = 400e3, 0.33, np.radians(30)
for L in (200, 400, 800):
    for k in (0.0, 0.5):
        P = V**2 / (x * L * (1 - k)) * np.sin(dmax)
        print(f"AC {L:4d} km, compensation {k:.0%}: {P/1e6:6.0f} MW per circuit")

# DC: +-500 kV bipole, 10 Ohm per pole; power set by the rectifier-inverter voltage difference
R = 10.0
for Vi in (500.0, 495.0, 490.0, 480.0):          # inverter voltage (kV); rectifier at 500 kV
    Id = (500.0 - Vi) / R                          # kA per pole
    print(f"Vi = {Vi:.0f} kV: Id = {Id:.1f} kA, sent = {2*500*Id:5.0f} MW, line loss = {2*Id**2*R:4.0f} MW")
AC  200 km, compensation 0%:   1212 MW per circuit
AC  200 km, compensation 50%:   2424 MW per circuit
AC  400 km, compensation 0%:    606 MW per circuit
AC  400 km, compensation 50%:   1212 MW per circuit
AC  800 km, compensation 0%:    303 MW per circuit
AC  800 km, compensation 50%:    606 MW per circuit
Vi = 500 kV: Id = 0.0 kA, sent =     0 MW, line loss =    0 MW
Vi = 495 kV: Id = 0.5 kA, sent =   500 MW, line loss =    5 MW
Vi = 490 kV: Id = 1.0 kA, sent =  1000 MW, line loss =   20 MW
Vi = 480 kV: Id = 2.0 kA, sent =  2000 MW, line loss =   80 MW

The angle limit at 200 km200\ \text{km} is far above the circuit's thermal rating (around 1.51.5 to 2 GW2\ \text{GW} for a large 400 kV400\ \text{kV} circuit), so short AC lines are thermally limited; at 800 km800\ \text{km} the angle limit dominates. On the DC side a 4 %4\ \% voltage difference carries the full 2 GW2\ \text{GW}.

Interactive: one pole of the DC link

One pole of the bipole with volts read as kilovolts and amperes as kiloamperes: the rectifier V1 at 500500, the 10 Ω10\ \Omega line RL, and the inverter V2. At the default V2=490V_2 = 490 the lab shows I(RL)=1.000I(RL) = 1.000 (kA), so the pole sends 500⋅1.0=500 MW500 \cdot 1.0 = 500\ \text{MW} and the line loses 10 MW10\ \text{MW}. Slide the inverter voltage: at 495495 the current halves, at 480480 it doubles. If V2V_2 rose above V1V_1 the current would try to reverse, which a thyristor (LCC) link cannot do: it reverses power by reversing both voltages instead.

node voltages (to ground 0)r500.0 Vi490.0 VnetlistV1 r 0 500RL r i 10V2 i 0 490element currents (node 1 to node 2 through it)V1r>0-1.00 ARLr>i1.00 AV2i>01.00 A

Guided lab: a DC link on the bench

Hand calculation. Two current-limited bench supplies represent rectifier (12.0 V12.0\ \text{V}) and inverter (11.5 V11.5\ \text{V}, connected to absorb power), joined by a 1 Ω1\ \Omega, 5 W5\ \text{W} "line". Predict I=0.5 AI = 0.5\ \text{A}, Psent=6.0 WP_\text{sent} = 6.0\ \text{W}, Ploss=0.25 WP_\text{loss} = 0.25\ \text{W}.

Simulation. Put the same values in the netlist lab.

What you would measure. A DMM in series reads the current; vary the second supply between 11.011.0 and 12.0 V12.0\ \text{V}. Many bench supplies cannot sink current: the "inverter" must be an electronic load in constant-voltage mode, or a supply rated for two-quadrant operation, or simply a power resistor whose voltage you read. Expect the current within ±5 %\pm 5\ \% of (V1−V2)/R(V_1 - V_2)/R, the error dominated by lead and contact resistance comparable to the 1 Ω1\ \Omega line.

Hazards and safe setup. ≤12 V\le 12\ \text{V}, both current limits at 1 A1\ \text{A}; never back-feed a supply that is not designed for it.

Pitfalls

  • "DC has no losses." It has I2RI^2R losses and converter losses; it saves the reactive and stability penalties, not resistance.
  • Forgetting the converter's reactive demand. An LCC station needs large filter and capacitor banks, and a weak AC network makes commutation failures likely.
  • Series compensation without studies. Subsynchronous resonance and protection (distance relays see a capacitor in the line) must be checked.
  • Comparing costs from old data. Converter and cable prices change quickly; break-even distances quoted in older books are not current.

Practice

  1. A ±320 kV\pm 320\ \text{kV} VSC cable link carries 1000 MW1000\ \text{MW}; each cable has R=3 ΩR = 3\ \Omega. Find the current and the cable losses.
  2. A line with X=100 ΩX = 100\ \Omega at 400 kV400\ \text{kV} carries 800 MW800\ \text{MW}. What angle does it need, and what with 40 %40\ \% series compensation?
  3. Why can a VSC link supply a passive island (no generators), and an LCC link not?
Answer
  1. I=1000/(2⋅320)=1.5625 kAI = 1000/(2 \cdot 320) = 1.5625\ \text{kA}; loss 2⋅1.56252⋅3=14.6 MW2 \cdot 1.5625^2 \cdot 3 = 14.6\ \text{MW}.
  2. sin⁡δ=800⋅100/4002=0.5\sin\delta = 800 \cdot 100/400^2 = 0.5, δ=30∘\delta = 30^\circ; with X=60 ΩX = 60\ \Omega, sin⁡δ=0.3\sin\delta = 0.3, δ=17.5∘\delta = 17.5^\circ.
  3. Thyristors need an existing AC voltage to commutate off; a VSC creates its own AC voltage waveform.

Test yourself

What limits power on a long AC line but not on a DC line?

  1. resistance
  2. the reactance and the stability angle
  3. conductor temperature
  4. corona

Which converter type can black-start a dead network?

  1. line-commutated (thyristor)
  2. voltage-source (IGBT)
  3. both
  4. neither

50 % series compensation raises the angle-limited transfer of a line by a factor of…

  1. 1.5
  2. 2
  3. 4
  4. 0.5

On a DC link with 10 Ω10\ \Omega line resistance and the rectifier at 500 kV, the inverter at 490 kV, the current is…

  1. 0.1 kA
  2. 1 kA
  3. 10 kA
  4. 49 kA