Symmetrical Components
Most faults are not balanced: a single conductor touches the ground, or two conductors swing together in the wind. Many loads are not balanced either: a railway traction supply draws from two phases only, and a street of houses never shares its load perfectly among three phases. Writing the three-phase circuit equations for every unbalanced case is possible but messy, because the phases are coupled. In 1918 Charles Fortescue showed a way out: any set of three phasors can be split into three balanced sets, and in a symmetrical network each balanced set flows through its own uncoupled circuit. That turns one coupled three-phase problem into three single-phase ones, the basis of every unbalanced-fault calculation and of many protection functions.
Safety. Unbalanced faults and loads on mains and grid systems: calculation and simulation only.
The three sequences
- Positive sequence (subscript 1): three equal phasors apart in the normal order a, b, c. This is what a healthy, balanced system contains.
- Negative sequence (2): equal, apart, but in the order a, c, b. In a motor it produces a field rotating backwards, which induces double-frequency currents in the rotor and heats it.
- Zero sequence (0): three equal phasors in phase. Zero-sequence currents add up in the neutral or earth instead of cancelling; they can only flow where there is a return path.
With the operator (so and ), the phase quantities are
The same transformation applies to currents. All components are referred to phase a: is the positive-sequence voltage of phase a, and phase b's is . Two results worth remembering:
So a three-wire system without a neutral or earth path has no zero-sequence current at all, and an earth-fault relay that sums the three phase currents (residual connection of CTs) measures directly. The factor 3 in the power appears because is not unitary with this scaling; some texts use to remove it.
Why it decouples the network
For a symmetrical (transposed) three-phase element, the phase impedance matrix has equal diagonal entries and equal off-diagonal (mutual) entries . Transforming it with gives a diagonal matrix:
The sequence impedances are and : positive-sequence currents produce only positive-sequence voltage drops, and so on. For a line, is much larger than (typically to times) because zero-sequence current returns through the earth and the mutual coupling adds instead of cancelling. Rotating machines have . The next lesson builds the sequence networks of generators, transformers and lines.
Worked example: one phase loaded
Given: a three-phase four-wire supply where only phase a is loaded: , .
Find: the sequence currents.
Solve:
Check: recombine for phase b: . Equal sequence currents are exactly the signature of a single line-to-ground fault, which the unsymmetrical-faults lesson uses: there the three sequence networks end up in series.
Interactive: an unbalanced load and its sequence currents
The three-phase lab with a four-wire star load, , , (kb ) and (kc ). It shows , , and a neutral current of . The program below decomposes these: (one third of the neutral current), and . Switch the lab to 3-wire: the neutral current disappears, so ; the currents become , and and the star point shifts by , a large zero-sequence voltage at the load. Calculation only: this is a system.
In Python: the transformation, power invariance and voltage unbalance
import numpy as np
a = np.exp(2j * np.pi / 3) # the operator a = 1 at 120 degrees
A = np.array([[1, 1, 1], [1, a**2, a], [1, a, a**2]])
Ainv = np.linalg.inv(A) # equals A.conj().T / 3
def polar(mag, deg):
return mag * np.exp(1j * np.radians(deg))
def deg(v):
d = np.degrees(np.angle(v))
return 0.0 if abs(d) < 0.05 or abs(v) < 1e-9 else d # avoid printing -0.0
def show(label, x, names):
print(label + ": " + ", ".join(f"{n} {abs(v):7.3f} at {deg(v):7.1f} deg" for n, v in zip(names, x)))
# 1) A single-phase load on phase a: Ia = 10 A, Ib = Ic = 0
I012 = Ainv @ np.array([10, 0, 0])
show("one phase loaded", I012, ["I0", "I1", "I2"])
# 2) The unbalanced 4-wire star load of the three-phase lab (230 V, Za = 20 + j10, Zb = 0.5 Za, Zc = 2 Za)
V = np.array([polar(230, 0), polar(230, -120), polar(230, 120)])
Za = 20 + 10j
Z = np.array([Za, 0.5 * Za, 2 * Za])
I = V / Z
show("line currents", I, ["Ia", "Ib", "Ic"])
I012 = Ainv @ I
show("sequence currents", I012, ["I0", "I1", "I2"])
print(f"neutral current {abs(I.sum()):.3f} A = 3 x I0 = {3*abs(I012[0]):.3f} A")
S_abc = (V * np.conj(I)).sum()
S_012 = 3 * ((Ainv @ V) * np.conj(I012)).sum()
print(f"power: phase sum {S_abc.real:.1f} W + j{S_abc.imag:.1f} var, sequence sum {S_012.real:.1f} W + j{S_012.imag:.1f} var")
print("back to phases:", np.allclose(A @ I012, I))
# 3) Voltage unbalance from three measured line-voltage magnitudes (no angles needed)
U = np.array([400.0, 392.0, 405.0])
beta = (U**4).sum() / (U**2).sum() ** 2
vuf = np.sqrt((1 - np.sqrt(3 - 6 * beta)) / (1 + np.sqrt(3 - 6 * beta)))
# check: build the triangle of line voltages and decompose it
ang_b = -np.pi + np.arccos((U[0]**2 + U[1]**2 - U[2]**2) / (2 * U[0] * U[1]))
Vab, Vbc = U[0], U[1] * np.exp(1j * ang_b)
Vca = -(Vab + Vbc)
L012 = Ainv @ np.array([Vab, Vbc, Vca])
print(f"line voltages {U.tolist()} V: unbalance V2/V1 = {100*vuf:.2f} % (formula), "
f"{100*abs(L012[2])/abs(L012[1]):.2f} % (triangle), |Vca| check {abs(Vca):.1f} V")one phase loaded: I0 3.333 at 0.0 deg, I1 3.333 at 0.0 deg, I2 3.333 at 0.0 deg
line currents: Ia 10.286 at -26.6 deg, Ib 20.572 at -146.6 deg, Ic 5.143 at 93.4 deg
sequence currents: I0 4.536 at -127.5 deg, I1 12.000 at -26.6 deg, I2 4.536 at 74.3 deg
neutral current 13.607 A = 3 x I0 = 13.607 A
power: phase sum 7406.0 W + j3703.0 var, sequence sum 7406.0 W + j3703.0 var
back to phases: True
line voltages [400.0, 392.0, 405.0] V: unbalance V2/V1 = 1.89 % (formula), 1.89 % (triangle), |Vca| check 405.0 V
The last line computes the voltage unbalance factor from three line-voltage magnitudes, the way power-quality instruments report it (a well-known closed form that needs only the three magnitudes, checked here against a full decomposition of the voltage triangle). A spread of to is unbalance, just inside the that EN 50160 allows for of the 10-minute values in a week on public networks. Line voltages carry no zero sequence, so the measure is purely negative over positive sequence. Motors are sensitive: a common rule (from NEMA MG 1) derates them noticeably above unbalance, because the negative-sequence current heats the rotor.
Guided lab: sequence components of a low-voltage three-phase source
Hand calculation. For three phasors you choose (e.g. , , ), compute , , by hand with and .
Simulation. Check with the program.
What you would measure. Generate a low-voltage three-phase set with a three-channel arbitrary-waveform generator (or three channels of an audio interface) at rms, deliberately unbalanced, and record all three on a four-channel scope (common ground). Read amplitudes and phase differences from the scope's measurements (typically amplitude, phase at ), and compute the components: expect agreement with the set values within those uncertainties. A amplitude error alone shows up as about to of apparent negative sequence, so measuring small unbalance needs good instruments.
Hazards and safe setup. Signal-generator outputs only. Never connect a scope to a three-phase mains supply: its ground lead is earthed, and line-to-line voltages exceed most probes' ratings.
Pitfalls
- Mixing up and . The belongs to the analysis direction (phase to sequence).
- Forgetting that components are per phase a. Phase b's positive-sequence voltage is , not .
- Expecting zero-sequence current without a path. No neutral, no earth connection, no .
- Dropping the factor 3 in power (with this scaling of ).
- Phase sequence. With a c-b-a supply, the roles of positive and negative sequence swap.
Practice
- Phase currents , , (a load between two lines). Find , , .
- Show that .
- An earth-fault relay is connected to the sum of three CT secondaries. A balanced load of flows. What does it see, and what does it see during a single-phase earth fault?
Answer
- ; ; : equal magnitudes, no zero sequence, the signature of a line-to-line fault.
- and ; the sum is .
- Balanced: (apart from CT mismatch). Earth fault: the fault current (on top of the balanced load), i.e. referred to the primary.
Test yourself
Which sequence component is the neutral current divided by 3?
- positive
- negative
- zero
- none
A negative-sequence current in an induction motor…
- adds torque
- creates a backward-rotating field that heats the rotor
- has no effect
- flows only in the neutral
For a transposed line with self impedance and mutual impedance , the zero-sequence impedance is…
Only phase a carries 10 A (four-wire). The sequence currents are…
- , others 0
- A
- , others 0
- A,