Unsymmetrical Faults: Line-to-Ground, Line-to-Line and Double Line-to-Ground
On overhead lines roughly three quarters of all faults involve one conductor and earth: lightning flashes over one insulator string, a branch touches one phase. Faults between two phases, or two phases and earth, make up most of the rest, and balanced three-phase faults are a small minority (a few percent; the exact split varies with voltage level and construction, so treat these as rough figures). The earth-fault current is often the largest current a breaker must interrupt near a solidly earthed transformer, and the smallest a relay must detect at the far end of a high-resistance earth path. With sequence networks each fault type becomes a simple series or parallel connection of the three Thevenin impedances.
Safety. Earth faults on high-voltage systems drive kiloamperes into the ground and raise its potential around the fault and the substation. This lesson is calculation and simulation only.
The three connections
At the fault point, write the boundary conditions in phase quantities, transform them to sequence quantities, and they tell you how to connect the three networks (Thevenin impedances , , , prefault voltage , fault impedance ):
| Fault | Phase conditions | Sequence result |
|---|---|---|
| single line-to-ground (a–g) | , | networks in series: , fault current |
| line-to-line (b–c) | , , | positive and negative in series, no zero sequence: , |
| double line-to-ground (b–c–g) | , | positive in series with ( parallel to ): |
Two quick consequences. With , a bolted line-to-line fault draws of the three-phase fault current. A single line-to-ground fault exceeds the three-phase current whenever , which happens close to solidly earthed transformers and generators.
Worked example: a single line-to-ground fault at bus H
Given: Plant P1's bus H, , (previous lesson), , a bolted fault from phase a to earth; base current at .
Find: the fault current, and the voltages of the healthy phases.
Solve:
Check: , as a bolted fault requires. The three-phase fault at the same bus gave , so the earth fault is larger: switchgear must be rated for it. The healthy phases stay below ; on networks where (unearthed or resistance-earthed systems) they rise towards , the line voltage, which stresses insulation and surge arresters (Earthing Systems). A system is called effectively earthed when the earth-fault factor (healthy-phase voltage during the fault over normal phase voltage) stays at or below about .
In Python: all four fault types and the effect of fault resistance
import numpy as np
a = np.exp(2j * np.pi / 3)
A = np.array([[1, 1, 1], [1, a**2, a], [1, a, a**2]])
Ib = 100e6 / (np.sqrt(3) * 132e3) # base current at 132 kV, A
# Thevenin sequence impedances at bus H of Plant P1 (previous lesson), prefault E = 1.0 pu
Z1 = Z2 = 1j * (0.28 * 0.20 / 0.48) # j0.1167
Z0 = 1j * (0.10 * 0.65 / 0.75) # j0.0867
E = 1.0
def fault(kind, Zf=0.0):
"""Sequence currents I0, I1, I2 (phase a reference) for a fault at the bus."""
if kind == "3ph":
I1 = E / (Z1 + Zf); return np.array([0, I1, 0])
if kind == "SLG": # phase a to ground
I0 = E / (Z1 + Z2 + Z0 + 3 * Zf); return np.array([I0, I0, I0])
if kind == "LL": # phase b to phase c
I1 = E / (Z1 + Z2 + Zf); return np.array([0, I1, -I1])
if kind == "DLG": # phases b and c to ground
Z0f = Z0 + 3 * Zf
I1 = E / (Z1 + Z2 * Z0f / (Z2 + Z0f))
return np.array([-I1 * Z2 / (Z2 + Z0f), I1, -I1 * Z0f / (Z2 + Z0f)])
def phase(I012):
return A @ I012
for kind in ["3ph", "SLG", "LL", "DLG"]:
I012 = fault(kind)
Iabc = phase(I012)
V012 = np.array([0, E, 0]) - np.array([Z0, Z1, Z2]) * I012 # sequence voltages at the fault
Vabc = A @ V012
print(f"{kind:3s}: |Ia, Ib, Ic| = " + ", ".join(f"{abs(i):6.3f}" for i in Iabc)
+ f" pu, largest {abs(Iabc).max()*Ib/1e3:5.3f} kA, earth current 3I0 = {abs(3*I012[0]):6.3f} pu"
+ "; |Va, Vb, Vc| = " + ", ".join(f"{abs(v):.3f}" for v in Vabc))
# SLG through a fault resistance (tree contact, arc): Zf in ohms at 132 kV
Zb = 132e3**2 / 100e6
for Rf in [0, 5, 20, 50]:
I0 = fault("SLG", Rf / Zb)[0]
print(f"SLG with Rf = {Rf:2d} ohm: fault current {abs(3*I0)*Ib/1e3:.3f} kA")
# where the earth-fault current goes: T1's star point or the lines (zero-sequence current divider)
I0 = fault("SLG")[0]
print(f"SLG at H: 3I0 = {abs(3*I0)*Ib:.0f} A, of which T1 neutral {abs(3*I0)*0.65/0.75*Ib:.0f} A, lines {abs(3*I0)*0.10/0.75*Ib:.0f} A")3ph: |Ia, Ib, Ic| = 8.571, 8.571, 8.571 pu, largest 3.749 kA, earth current 3I0 = 0.000 pu; |Va, Vb, Vc| = 0.000, 0.000, 0.000
SLG: |Ia, Ib, Ic| = 9.375, 0.000, 0.000 pu, largest 4.100 kA, earth current 3I0 = 9.375 pu; |Va, Vb, Vc| = 0.000, 0.957, 0.957
LL : |Ia, Ib, Ic| = 0.000, 7.423, 7.423 pu, largest 3.247 kA, earth current 3I0 = 0.000 pu; |Va, Vb, Vc| = 1.000, 0.500, 0.500
DLG: |Ia, Ib, Ic| = 0.000, 9.047, 9.047 pu, largest 3.957 kA, earth current 3I0 = 10.345 pu; |Va, Vb, Vc| = 0.897, 0.000, 0.000
SLG with Rf = 0 ohm: fault current 4.100 kA
SLG with Rf = 5 ohm: fault current 3.960 kA
SLG with Rf = 20 ohm: fault current 2.791 kA
SLG with Rf = 50 ohm: fault current 1.429 kA
SLG at H: 3I0 = 4100 A, of which T1 neutral 3554 A, lines 547 A
Ranked at this bus: double line-to-ground drives the largest earth current ( through the ground, though each faulted phase carries ), single line-to-ground the largest phase current (), then three-phase () and line-to-line (). In the line-to-line case the healthy phase a stays at and the faulted phases drop to . A tree or arc resistance of cuts the earth-fault current from to , which is why distance and earth-fault relays must cope with fault resistance (Distance Protection). Most of the earth current returns through T1's earthed star point (), only through the lines: the zero-sequence current divides in inverse proportion to the zero-sequence impedances.
Interactive: the series connection for a line-to-ground fault
The netlist lab is the figure above in per unit at : a source, and as each, as , and RF standing for . Read the values (the lab sweeps frequency). With RF at the loop current is , i.e. and a fault current of , and node p (the positive-sequence voltage at the fault) reads . A fault resistance at is , so set RF to : the loop current falls to at , giving , as in the program.
Guided lab: earth-fault current from relay records
Hand calculation. Compute the single line-to-ground fault current at bus H for fault resistances of , and , and the share returning through T1's neutral.
Simulation. Run the program or the netlist lab for the same values.
What you would measure. Real faults are recorded, not staged. A numerical relay or disturbance recorder at the substation captures the three phase currents and the neutral current at a few kilohertz sampling; the engineer reads the fault-current phasors from the first clean cycles after inception and compares them with the model. Expect agreement within to for bolted faults (CT accuracy class 5P is composite error at the accuracy limit, network data are uncertain), and use the comparison to estimate the actual fault resistance. On the bench, the analogue is the netlist above built with real inductors at signal level and a decade resistor for , measured with a function generator and a scope: a safe way to see the current fall with fault resistance.
Hazards and safe setup. Bench version at function-generator levels only. Never create an earth fault on a mains circuit, even through a resistor: the protective device may not operate, and exposed metal can reach dangerous touch voltages.
Pitfalls
- Forgetting the factor 3: the fault current of a single line-to-ground fault is , and the fault impedance enters as .
- Using in a line-to-line fault. No earth, no zero sequence.
- Assuming the three-phase fault is always the worst. Near earthed transformers, the earth fault can be larger.
- Ignoring transformer phase shifts when you calculate currents on the other side of a star–delta transformer: a line-to-ground fault on the star side looks like a line-to-line pattern on the delta side.
- Bolted faults only. Arcs and trees add resistance; relays must be set for minimum fault currents as well.
Practice
- With and , find the single line-to-ground and three-phase fault currents. Which is larger?
- Show that a bolted line-to-line fault gives of the three-phase current when .
- In the worked example, what fault resistance (ohms) halves the earth-fault current?
Answer
- SLG: ; three-phase: . The three-phase fault is larger here, as it is far from earthed neutrals.
- , against for the three-phase fault: a ratio of .
- Need , so , .
Test yourself
For a single line-to-ground fault, the sequence networks are connected…
- in parallel
- in series
- positive and negative only, in series
- positive only
A bolted line-to-line fault with draws, compared with a three-phase fault at the same bus…
- the same current
- about 87 %
- about 58 %
- twice as much
Why can a single line-to-ground fault exceed the three-phase fault current?
- it never can
- when , e.g. near a solidly earthed transformer
- when the fault resistance is high
- when the system is unearthed
In a line-to-line fault, the zero-sequence current is…
- equal to the positive sequence
- zero
- three times the fault current
- equal to the negative sequence