Protection relays deal with currents that last tens of milliseconds. Some threats are faster or different in kind: a lightning stroke drives a voltage wave down a line in microseconds, switching a long line or a capacitor bank sends a surge of twice or three times normal voltage, and a fault inside switchgear turns into an arc that releases its energy as heat, light and pressure in a fraction of a second. This lesson treats overvoltages as travelling waves, shows how surge arresters and insulation levels are matched (insulation coordination), and ends with arc flash as a hazard concept.

Safety: everything here (lightning, switching surges, arc flash) is studied by calculation and simulation only. Impulse testing uses generators of hundreds of kilovolts in screened laboratories. Arc flash and live working are described as concepts: nobody works on or near exposed energised conductors without qualification, a permit, a risk assessment and the protective equipment it specifies.

Kinds of overvoltage

Class (IEC 60071-1:2019) Typical cause Time to crest Typical magnitude
temporary (TOV) earth fault on an unearthed or resonant-earthed system, load rejection, Ferranti rise power frequency, seconds up to 3\sqrt{3} times phase voltage on healthy phases
slow-front switching lines, capacitor banks, fault clearing 2020 to 5000 μs5000\ \mu\text{s} 22 to 33 pu (pu = phase-to-earth crest)
fast-front lightning 0.10.1 to 20 μs20\ \mu\text{s} megavolts if unlimited
very-fast-front disconnector operation in gas-insulated switchgear <0.1 μs< 0.1\ \mu\text{s} 1.51.5 to 2.52.5 pu

The standard test waves follow these classes: the lightning impulse 1.2/50 μs1.2/50\ \mu\text{s} (front time / time to half value) and the switching impulse 250/2500 μs250/2500\ \mu\text{s}.

Surges as travelling waves

A surge on a line is a wave like the ones in Transmission-Line Transients: voltage and current related by the surge impedance ZcZ_c (about 300300 to 400 Ω400\ \Omega for an overhead line, 2020 to 60 Ω60\ \Omega for a cable), travelling near the speed of light on overhead lines and about half of it in cables. A lightning stroke of current II onto a phase conductor splits into two waves of I/2I/2, each carrying

V=I2 Zc,e.g. 30 kA2⋅400 Ω=6 MVV = \frac{I}{2}\,Z_c, \qquad \text{e.g.}\ \frac{30\ \text{kA}}{2} \cdot 400\ \Omega = 6\ \text{MV}

far above any line's insulation, so the insulators flash over. Shield wires above the phases intercept most strokes; a stroke to a tower or shield wire can still flash over "backwards" if the tower footing resistance is high.

At a junction from Z1Z_1 to Z2Z_2 the wave is partly reflected and partly transmitted:

Γ=Z2−Z1Z2+Z1,Vtransmitted=(1+Γ) Vincident\Gamma = \frac{Z_2 - Z_1}{Z_2 + Z_1}, \qquad V_\text{transmitted} = (1 + \Gamma)\,V_\text{incident}

A transformer looks almost like an open circuit to a fast front (Γ≈1\Gamma \approx 1), so the voltage at its terminals doubles. A short cable between an overhead line and a transformer does not cure this: reflections inside the cable build the voltage up step by step toward the same doubled value.

Interactive: a scaled model of line, cable and transformer

The transmission-line lab is lossless and works in nanoseconds with Z0Z_0 up to 150 Ω150\ \Omega, so it is used here as a scaled model (time in units of the cable's one-way delay TdT_d). An overhead line's incoming wave of 5 V5\ \text{V} is represented by its Thevenin equivalent at the junction, a source of 2⋅5=10 V2 \cdot 5 = 10\ \text{V} behind Rs=400 ΩR_s = 400\ \Omega (the line's surge impedance); the cable has Z0=50 ΩZ_0 = 50\ \Omega; the transformer is an open end. The lab shows ΓS=0.7778\Gamma_S = 0.7778, ΓL=1\Gamma_L = 1, a launched wave of 1.111 V1.111\ \text{V}, and the voltage at the transformer climbing 2.222 V2.222\ \text{V} at 1 Td1\,T_d, 3.951 V3.951\ \text{V} at 3 Td3\,T_d, 5.295 V5.295\ \text{V} at 5 Td5\,T_d and 6.340 V6.340\ \text{V} at 7 Td7\,T_d, on its way to the 10 V10\ \text{V} final value, twice the incident wave. Change term to a resistor and lower RL to 50 Ω50\ \Omega to see what an ideal matched termination would do (no reflection at all).

0246source endload endv(x) (V)t = 8.00 Td = 8.00 nsS10.0 VRs 400 OhmZ0 = 50.0 Ohm, one-way delay Td = 1.00 nsopen0 Td2 Td4 Td6 Td8 TdGS = 0.778GL = 1.0001.1111.1110.8640.8640.6720.6720.5230.523024602468t (Td)v at source endv at load end

In a real substation the front of a lightning surge lasts about a microsecond, comparable to a few cable transit times, so the peak at the transformer depends on the cable length, the front steepness and above all on the surge arrester.

Surge arresters and insulation coordination

A metal-oxide (ZnO) arrester is a very nonlinear resistor: it draws microamperes at the system's continuous operating voltage and conducts kiloamperes with only a moderate rise in voltage, clamping the surge at its residual voltage, the lightning impulse protective level UplU_{pl} (stated at a discharge current such as 10 kA10\ \text{kA}). Insulation coordination chooses equipment withstand levels above the protected voltage with a margin. IEC 60071-1 lists standard lightning impulse withstand levels (LIWL, also called BIL) for each highest voltage for equipment UmU_m: for example 75 kV75\ \text{kV} (list 2) at Um=12 kVU_m = 12\ \text{kV}, 125 kV125\ \text{kV} at 24 kV24\ \text{kV}, and 450450, 550550 or 650 kV650\ \text{kV} at 145 kV145\ \text{kV} (several values per UmU_m; the designer picks one).

Distance matters. An arrester dd metres from the transformer protects it less well, because the surge reflected from the transformer reaches the arrester 2d/v2d/v later than the incident wave. For a front of steepness SS (kV/µs), a common estimate is

Ut≈Upl+2SdvU_t \approx U_{pl} + \frac{2 S d}{v}

with v≈300 m/μsv \approx 300\ \text{m}/\mu\text{s} on overhead connections. IEC 60071-2 recommends a safety factor of about 1.151.15 between the withstand voltage of internal (non-self-restoring) insulation and the expected overvoltage.

Worked example: arrester placement at a 132 kV transformer

Given: Um=145 kVU_m = 145\ \text{kV}, transformer LIWL 650 kV650\ \text{kV}; arrester Upl=330 kVU_{pl} = 330\ \text{kV} at 10 kA10\ \text{kA} (an assumed, typical-order value for this voltage); incoming front steepness S=1000 kV/μsS = 1000\ \text{kV}/\mu\text{s}; v=300 m/μsv = 300\ \text{m}/\mu\text{s}.

Find: the voltage at the transformer and the protective margin with the arrester 20 m20\ \text{m} and 60 m60\ \text{m} away.

Solve:

Ut(20 m)=330+2⋅1000⋅20300=463 kV,650463=1.40Ut(60 m)=330+2⋅1000⋅60300=730 kV,650730=0.89\begin{aligned} U_t(20\ \text{m}) &= 330 + \frac{2 \cdot 1000 \cdot 20}{300} = 463\ \text{kV}, & \frac{650}{463} &= 1.40 \\ U_t(60\ \text{m}) &= 330 + \frac{2 \cdot 1000 \cdot 60}{300} = 730\ \text{kV}, & \frac{650}{730} &= 0.89 \end{aligned}

Check: at 20 m20\ \text{m} the margin 1.401.40 exceeds 1.151.15; at 60 m60\ \text{m} the transformer would be overstressed. That is why arresters sit at the transformer terminals, with the shortest possible earth connection: the arrester's own leads add inductive voltage (≈1 μH/m×di/dt\approx 1\ \mu\text{H}/\text{m} \times di/dt) to the protected voltage.

In Python: the lattice behind the lab, and arrester distance

python · try it yourself
import numpy as np

# lattice for the scaled lab: source 10 V behind 400 Ohm, 50 Ohm cable, open end
Vs, Rs, Z0 = 10.0, 400.0, 50.0
GS, GL = (Rs - Z0) / (Rs + Z0), 1.0
V1 = Vs * Z0 / (Rs + Z0)
v_load, a = 0.0, V1
print(f"GS = {GS:.4f}, V1 = {V1:.4f} V")
for k in range(4):
    v_load += (1 + GL) * a                 # each arrival at the open end doubles that wave
    print(f"t = {2*k+1} Td: v at transformer = {v_load:.3f} V")
    a *= GL * GS
print(f"final value = {Vs:.1f} V = 2 x the 5 V incident wave")

# insulation coordination: protected voltage against arrester distance
Upl, S, v, LIWL = 330.0, 1000.0, 300.0, 650.0
for d in (0, 10, 20, 40, 60):
    Ut = Upl + 2 * S * d / v
    print(f"d = {d:2d} m: Ut = {Ut:5.0f} kV, margin = {LIWL/Ut:.2f}", "OK" if LIWL / Ut >= 1.15 else "too small")
print(f"largest distance for a 1.15 margin: {(LIWL/1.15 - Upl) * v / (2*S):.1f} m")

# arc flash: incident energy scales with arcing current x time (same arc, same distance)
t_slow, t_fast = 0.379 + 0.05, 0.05 + 0.05        # B1 incomer at F1 vs an instantaneous maintenance setting
print(f"energy ratio slow/fast clearing = {t_slow/t_fast:.1f}")
GS = 0.7778, V1 = 1.1111 V
t = 1 Td: v at transformer = 2.222 V
t = 3 Td: v at transformer = 3.951 V
t = 5 Td: v at transformer = 5.295 V
t = 7 Td: v at transformer = 6.340 V
final value = 10.0 V = 2 x the 5 V incident wave
d =  0 m: Ut =   330 kV, margin = 1.97 OK
d = 10 m: Ut =   397 kV, margin = 1.64 OK
d = 20 m: Ut =   463 kV, margin = 1.40 OK
d = 40 m: Ut =   597 kV, margin = 1.09 too small
d = 60 m: Ut =   730 kV, margin = 0.89 too small
largest distance for a 1.15 margin: 35.3 m
energy ratio slow/fast clearing = 4.3

Arc flash (concept)

When a fault arcs in air inside switchgear, the arc runs at thousands of kelvin and its power, roughly arc voltage times arcing current, is released as radiant heat, molten metal, a pressure wave and noise. The incident energy on a worker at a working distance is the hazard measure: it grows with the arcing current and, almost linearly, with the arcing time, and falls with distance. IEEE 1584-2018 (Guide for Performing Arc-Flash Hazard Calculations) gives empirical models for 208 V208\ \text{V} to 15 kV15\ \text{kV} that account for electrode configuration and enclosure size; NFPA 70E (2024 edition in the US) and, in Europe, EN 50110-1 and national rules set the work practices. The arc-flash boundary is where the incident energy falls to 1.2 cal/cm21.2\ \text{cal/cm}^2 (5.0 J/cm25.0\ \text{J/cm}^2), the onset of a second-degree burn on bare skin.

The engineering lever is clearing time. B1's incomer R2 clears a busbar fault in 0.379 s0.379\ \text{s} plus its breaker; a temporary "maintenance mode" instantaneous setting, or a light-sensing arc-flash relay, clears in about 0.1 s0.1\ \text{s} in total, cutting the incident energy by the factor 4.34.3 printed above. Other levers are remote racking and switching, arc-resistant switchgear (internal arc classification to IEC 62271-200) and, first of all, working dead.

Guided lab: reflections on a coaxial cable

Hand calculation. A 20 m20\ \text{m} RG-58 cable (Z0=50 ΩZ_0 = 50\ \Omega, velocity factor 0.660.66) has Td=20/(0.66⋅3×108)=101 nsT_d = 20/(0.66 \cdot 3 \times 10^8) = 101\ \text{ns}. Drive it with a 5 V5\ \text{V} (open-circuit) step through Rs=400 ΩR_s = 400\ \Omega in total (a 50 Ω50\ \Omega generator plus a 350 Ω350\ \Omega resistor) and leave the far end open. Predict the staircase at the far end: 1.111.11, 1.981.98 and 2.65 V2.65\ \text{V} at 11, 33 and 5 Td5\,T_d, half the lab's values.

Simulation. Set the lab to Vs 55, Rs 400400, Z0 5050, open end, Td 100100 and compare.

What you would measure. A function generator's square wave at 100 kHz100\ \text{kHz} (rise time a few ns) and a two-channel scope at both ends. Expect the steps within about ±5 %\pm 5\ \% (generator rise time and cable loss round the corners); the staircase is the same physics as a lightning surge climbing to double voltage at a transformer.

Hazards and safe setup. Signal levels only. None of this may be tried with real surge or impulse equipment.

Pitfalls

  • Arrester too far away or with long leads: the protected equipment sees much more than UplU_{pl}.
  • Thinking a short cable protects a transformer. It only delays and staggers the rise toward the doubled voltage.
  • Arrester rating too low for TOV. An arrester whose continuous rating is below the temporary overvoltage on healthy phases during an earth fault will overheat and fail.
  • Arc-flash labels as permission. Calculated incident energy chooses PPE for unavoidable live work; it does not make live work acceptable.

Practice

  1. A 20 kA20\ \text{kA} stroke hits a conductor of Zc=350 ΩZ_c = 350\ \Omega. What voltage wave travels in each direction?
  2. A wave of 500 kV500\ \text{kV} on a 400 Ω400\ \Omega line reaches a 40 Ω40\ \Omega cable. What voltage enters the cable?
  3. With Upl=330 kVU_{pl} = 330\ \text{kV}, S=500 kV/μsS = 500\ \text{kV}/\mu\text{s} and LIWL 550 kV550\ \text{kV}, how far may the arrester be for a 1.151.15 margin?
Answer
  1. 10 kA⋅350 Ω=3.5 MV10\ \text{kA} \cdot 350\ \Omega = 3.5\ \text{MV}.
  2. Γ=(40−400)/440=−0.818\Gamma = (40 - 400)/440 = -0.818; transmitted (1−0.818)⋅500=90.9 kV(1 - 0.818) \cdot 500 = 90.9\ \text{kV}.
  3. Ut≤550/1.15=478.3 kVU_t \le 550/1.15 = 478.3\ \text{kV}; d≤(478.3−330)⋅300/(2⋅500)=44.5 md \le (478.3 - 330) \cdot 300/(2 \cdot 500) = 44.5\ \text{m}.

Test yourself

Why does the voltage of a fast surge double at a transformer's terminals?

  1. the transformer steps it up
  2. the transformer looks almost like an open circuit to a fast front, so the wave reflects with Γ≈1\Gamma \approx 1
  3. the arrester adds voltage
  4. the DC offset

The 1.2/50 µs wave is the standard…

  1. switching impulse
  2. lightning impulse
  3. temporary overvoltage
  4. arc-flash test

Moving a surge arrester further from the transformer it protects…

  1. improves protection
  2. raises the voltage at the transformer by about 2Sd/v2Sd/v
  3. has no effect
  4. lowers the arrester's residual voltage

Which change reduces arc-flash incident energy most directly?

  1. a larger CT
  2. faster fault clearing
  3. a higher LIWL
  4. a longer cable