Surges, Lightning, Insulation Coordination and Arc Flash
Protection relays deal with currents that last tens of milliseconds. Some threats are faster or different in kind: a lightning stroke drives a voltage wave down a line in microseconds, switching a long line or a capacitor bank sends a surge of twice or three times normal voltage, and a fault inside switchgear turns into an arc that releases its energy as heat, light and pressure in a fraction of a second. This lesson treats overvoltages as travelling waves, shows how surge arresters and insulation levels are matched (insulation coordination), and ends with arc flash as a hazard concept.
Safety: everything here (lightning, switching surges, arc flash) is studied by calculation and simulation only. Impulse testing uses generators of hundreds of kilovolts in screened laboratories. Arc flash and live working are described as concepts: nobody works on or near exposed energised conductors without qualification, a permit, a risk assessment and the protective equipment it specifies.
Kinds of overvoltage
| Class (IEC 60071-1:2019) | Typical cause | Time to crest | Typical magnitude |
|---|---|---|---|
| temporary (TOV) | earth fault on an unearthed or resonant-earthed system, load rejection, Ferranti rise | power frequency, seconds | up to times phase voltage on healthy phases |
| slow-front | switching lines, capacitor banks, fault clearing | to | to pu (pu = phase-to-earth crest) |
| fast-front | lightning | to | megavolts if unlimited |
| very-fast-front | disconnector operation in gas-insulated switchgear | to pu |
The standard test waves follow these classes: the lightning impulse (front time / time to half value) and the switching impulse .
Surges as travelling waves
A surge on a line is a wave like the ones in Transmission-Line Transients: voltage and current related by the surge impedance (about to for an overhead line, to for a cable), travelling near the speed of light on overhead lines and about half of it in cables. A lightning stroke of current onto a phase conductor splits into two waves of , each carrying
far above any line's insulation, so the insulators flash over. Shield wires above the phases intercept most strokes; a stroke to a tower or shield wire can still flash over "backwards" if the tower footing resistance is high.
At a junction from to the wave is partly reflected and partly transmitted:
A transformer looks almost like an open circuit to a fast front (), so the voltage at its terminals doubles. A short cable between an overhead line and a transformer does not cure this: reflections inside the cable build the voltage up step by step toward the same doubled value.
Interactive: a scaled model of line, cable and transformer
The transmission-line lab is lossless and works in nanoseconds with up to , so it is used here as a scaled model (time in units of the cable's one-way delay ). An overhead line's incoming wave of is represented by its Thevenin equivalent at the junction, a source of behind (the line's surge impedance); the cable has ; the transformer is an open end. The lab shows , , a launched wave of , and the voltage at the transformer climbing at , at , at and at , on its way to the final value, twice the incident wave. Change term to a resistor and lower RL to to see what an ideal matched termination would do (no reflection at all).
In a real substation the front of a lightning surge lasts about a microsecond, comparable to a few cable transit times, so the peak at the transformer depends on the cable length, the front steepness and above all on the surge arrester.
Surge arresters and insulation coordination
A metal-oxide (ZnO) arrester is a very nonlinear resistor: it draws microamperes at the system's continuous operating voltage and conducts kiloamperes with only a moderate rise in voltage, clamping the surge at its residual voltage, the lightning impulse protective level (stated at a discharge current such as ). Insulation coordination chooses equipment withstand levels above the protected voltage with a margin. IEC 60071-1 lists standard lightning impulse withstand levels (LIWL, also called BIL) for each highest voltage for equipment : for example (list 2) at , at , and , or at (several values per ; the designer picks one).
Distance matters. An arrester metres from the transformer protects it less well, because the surge reflected from the transformer reaches the arrester later than the incident wave. For a front of steepness (kV/µs), a common estimate is
with on overhead connections. IEC 60071-2 recommends a safety factor of about between the withstand voltage of internal (non-self-restoring) insulation and the expected overvoltage.
Worked example: arrester placement at a 132 kV transformer
Given: , transformer LIWL ; arrester at (an assumed, typical-order value for this voltage); incoming front steepness ; .
Find: the voltage at the transformer and the protective margin with the arrester and away.
Solve:
Check: at the margin exceeds ; at the transformer would be overstressed. That is why arresters sit at the transformer terminals, with the shortest possible earth connection: the arrester's own leads add inductive voltage () to the protected voltage.
In Python: the lattice behind the lab, and arrester distance
import numpy as np
# lattice for the scaled lab: source 10 V behind 400 Ohm, 50 Ohm cable, open end
Vs, Rs, Z0 = 10.0, 400.0, 50.0
GS, GL = (Rs - Z0) / (Rs + Z0), 1.0
V1 = Vs * Z0 / (Rs + Z0)
v_load, a = 0.0, V1
print(f"GS = {GS:.4f}, V1 = {V1:.4f} V")
for k in range(4):
v_load += (1 + GL) * a # each arrival at the open end doubles that wave
print(f"t = {2*k+1} Td: v at transformer = {v_load:.3f} V")
a *= GL * GS
print(f"final value = {Vs:.1f} V = 2 x the 5 V incident wave")
# insulation coordination: protected voltage against arrester distance
Upl, S, v, LIWL = 330.0, 1000.0, 300.0, 650.0
for d in (0, 10, 20, 40, 60):
Ut = Upl + 2 * S * d / v
print(f"d = {d:2d} m: Ut = {Ut:5.0f} kV, margin = {LIWL/Ut:.2f}", "OK" if LIWL / Ut >= 1.15 else "too small")
print(f"largest distance for a 1.15 margin: {(LIWL/1.15 - Upl) * v / (2*S):.1f} m")
# arc flash: incident energy scales with arcing current x time (same arc, same distance)
t_slow, t_fast = 0.379 + 0.05, 0.05 + 0.05 # B1 incomer at F1 vs an instantaneous maintenance setting
print(f"energy ratio slow/fast clearing = {t_slow/t_fast:.1f}")GS = 0.7778, V1 = 1.1111 V
t = 1 Td: v at transformer = 2.222 V
t = 3 Td: v at transformer = 3.951 V
t = 5 Td: v at transformer = 5.295 V
t = 7 Td: v at transformer = 6.340 V
final value = 10.0 V = 2 x the 5 V incident wave
d = 0 m: Ut = 330 kV, margin = 1.97 OK
d = 10 m: Ut = 397 kV, margin = 1.64 OK
d = 20 m: Ut = 463 kV, margin = 1.40 OK
d = 40 m: Ut = 597 kV, margin = 1.09 too small
d = 60 m: Ut = 730 kV, margin = 0.89 too small
largest distance for a 1.15 margin: 35.3 m
energy ratio slow/fast clearing = 4.3
Arc flash (concept)
When a fault arcs in air inside switchgear, the arc runs at thousands of kelvin and its power, roughly arc voltage times arcing current, is released as radiant heat, molten metal, a pressure wave and noise. The incident energy on a worker at a working distance is the hazard measure: it grows with the arcing current and, almost linearly, with the arcing time, and falls with distance. IEEE 1584-2018 (Guide for Performing Arc-Flash Hazard Calculations) gives empirical models for to that account for electrode configuration and enclosure size; NFPA 70E (2024 edition in the US) and, in Europe, EN 50110-1 and national rules set the work practices. The arc-flash boundary is where the incident energy falls to (), the onset of a second-degree burn on bare skin.
The engineering lever is clearing time. B1's incomer R2 clears a busbar fault in plus its breaker; a temporary "maintenance mode" instantaneous setting, or a light-sensing arc-flash relay, clears in about in total, cutting the incident energy by the factor printed above. Other levers are remote racking and switching, arc-resistant switchgear (internal arc classification to IEC 62271-200) and, first of all, working dead.
Guided lab: reflections on a coaxial cable
Hand calculation. A RG-58 cable (, velocity factor ) has . Drive it with a (open-circuit) step through in total (a generator plus a resistor) and leave the far end open. Predict the staircase at the far end: , and at , and , half the lab's values.
Simulation. Set the lab to Vs , Rs , Z0 , open end, Td and compare.
What you would measure. A function generator's square wave at (rise time a few ns) and a two-channel scope at both ends. Expect the steps within about (generator rise time and cable loss round the corners); the staircase is the same physics as a lightning surge climbing to double voltage at a transformer.
Hazards and safe setup. Signal levels only. None of this may be tried with real surge or impulse equipment.
Pitfalls
- Arrester too far away or with long leads: the protected equipment sees much more than .
- Thinking a short cable protects a transformer. It only delays and staggers the rise toward the doubled voltage.
- Arrester rating too low for TOV. An arrester whose continuous rating is below the temporary overvoltage on healthy phases during an earth fault will overheat and fail.
- Arc-flash labels as permission. Calculated incident energy chooses PPE for unavoidable live work; it does not make live work acceptable.
Practice
- A stroke hits a conductor of . What voltage wave travels in each direction?
- A wave of on a line reaches a cable. What voltage enters the cable?
- With , and LIWL , how far may the arrester be for a margin?
Answer
- .
- ; transmitted .
- ; .
Test yourself
Why does the voltage of a fast surge double at a transformer's terminals?
- the transformer steps it up
- the transformer looks almost like an open circuit to a fast front, so the wave reflects with
- the arrester adds voltage
- the DC offset
The 1.2/50 µs wave is the standard…
- switching impulse
- lightning impulse
- temporary overvoltage
- arc-flash test
Moving a surge arrester further from the transformer it protects…
- improves protection
- raises the voltage at the transformer by about
- has no effect
- lowers the arrester's residual voltage
Which change reduces arc-flash incident energy most directly?
- a larger CT
- faster fault clearing
- a higher LIWL
- a longer cable