Short and Medium Lines: the Nominal π\pi and ABCD Parameters

The previous two lessons gave the 132 kV132\ \text{kV} line its per-kilometre parameters: z=0.0882+j0.390 Ω/kmz = 0.0882 + j0.390\ \Omega/\text{km} in series and y=j2.913 μS/kmy = j2.913\ \mu\text{S/km} in shunt. Now a utility wants to deliver 50 MW50\ \text{MW} at power factor 0.90.9 over 120 km120\ \text{km} of it. What voltage must the sending end hold, how much current does it supply, what is the regulation and how much is lost? For lines up to a few hundred kilometres, lumping the distributed parameters into a few elements is accurate enough, and the result fits a four-number description, the ABCD (transmission) parameters, that chains neatly with transformers and other lines. Two-port parameters in general are in Two-Port Networks: h and ABCD.

Safety: transmission lines are studied here by calculation and simulation only.

Models by length

Model Length (50 Hz, rule of thumb) Circuit
short line below about 80 km80\ \text{km} series Z=zℓZ = z\ell only; shunt capacitance neglected
medium line, nominal π\pi about 8080 to 250 km250\ \text{km} ZZ in series, Y/2Y/2 at each end, Y=yℓY = y\ell
long line above about 250 km250\ \text{km} exact distributed solution or the equivalent π\pi (Long Lines)

The boundaries are conventions, not physics: they come from the error of lumping compared with the exact solution, which grows roughly with (ℓ/λ)2(\ell/\lambda)^2, where the wavelength at 50 Hz50\ \text{Hz} is about 6000 km6000\ \text{km}. Cables, with their large capacitance, need the π\pi model at much shorter lengths.

Z = R + jX = 10.58 + j46.8 Ohm Y/2Y/2 0.557 uF0.557 uF VsVR Is IR 120 km of the 132 kV line, per phase to neutral

ABCD parameters

Any two-port between a sending end (s) and a receiving end (R) can be written as

[VsIs]=[ABCD][VRIR],AD−BC=1 (reciprocal),A=D (symmetrical)\begin{bmatrix} \mathbf{V}_s \\ \mathbf{I}_s \end{bmatrix} = \begin{bmatrix} A & B \\ C & D \end{bmatrix} \begin{bmatrix} \mathbf{V}_R \\ \mathbf{I}_R \end{bmatrix}, \qquad AD - BC = 1 \ \text{(reciprocal)}, \qquad A = D \ \text{(symmetrical)}

For the models above:

short: A=D=1, B=Z, C=0;nominal π: A=D=1+YZ2, B=Z, C=Y(1+YZ4)\text{short: } A = D = 1,\ B = Z,\ C = 0; \qquad \text{nominal } \pi\text{: } A = D = 1 + \frac{YZ}{2},\ B = Z,\ C = Y\left(1 + \frac{YZ}{4}\right)

Two lines or a transformer and a line in cascade multiply their matrices. AA also gives the open-circuit receiving voltage: with IR=0\mathbf{I}_R = 0, VR=Vs/A\mathbf{V}_R = \mathbf{V}_s/A. The voltage regulation compares that no-load voltage with the full-load one:

VR=∣Vs∣/∣A∣−∣VR,FL∣∣VR,FL∣⋅100 %\text{VR} = \frac{\lvert \mathbf{V}_s \rvert/\lvert A \rvert - \lvert \mathbf{V}_{R,\text{FL}} \rvert}{\lvert \mathbf{V}_{R,\text{FL}} \rvert} \cdot 100\ \%

Worked example: 50 MW over 120 km

Given: the 132 kV132\ \text{kV} line, ℓ=120 km\ell = 120\ \text{km}: Z=10.58+j46.80 ΩZ = 10.58 + j46.80\ \Omega, Y=j349.6 μSY = j349.6\ \mu\text{S}; receiving end 132 kV132\ \text{kV} (line), 50 MW50\ \text{MW} at pf 0.90.9 lagging.

Find: the sending-end voltage and current, the regulation and the efficiency, with the short and the nominal-π\pi models.

Solve: per phase, VR=76.21 kV∠0∘\mathbf{V}_R = 76.21\ \text{kV}\angle 0^\circ and IR=50×106/(3⋅132 000⋅0.9)=243.0 A∠−25.84∘\mathbf{I}_R = 50 \times 10^6/(\sqrt{3} \cdot 132\,000 \cdot 0.9) = 243.0\ \text{A}\angle -25.84^\circ.

A=1+YZ2=0.99182+j0.00185Vs=AVR+BIR=83.37 kV∠6.37∘(144.41 kV line)Is=CVR+DIR=230.7 A∠−19.79∘VR=144.41/0.99182−132132=10.3 %,η=50 MW51.79 MW=96.5 %\begin{aligned} A &= 1 + \frac{YZ}{2} = 0.99182 + j0.00185 \\ \mathbf{V}_s &= A\mathbf{V}_R + B\mathbf{I}_R = 83.37\ \text{kV}\angle 6.37^\circ \quad (144.41\ \text{kV line}) \\ \mathbf{I}_s &= C\mathbf{V}_R + D\mathbf{I}_R = 230.7\ \text{A}\angle -19.79^\circ \\ \text{VR} &= \frac{144.41/0.99182 - 132}{132} = 10.3\ \%, \qquad \eta = \frac{50\ \text{MW}}{51.79\ \text{MW}} = 96.5\ \% \end{aligned}

The short-line model gives 145.45 kV145.45\ \text{kV}, 243.0 A243.0\ \text{A}, VR=10.2 %\text{VR} = 10.2\ \% and η=96.4 %\eta = 96.4\ \%.

Check: the line's charging current partly cancels the load's lagging current, so the π\pi model's sending current (230.7 A230.7\ \text{A}) is lower than the receiving current, and the sending end supplies 25.425.4 instead of 32.5 Mvar32.5\ \text{Mvar}. The π\pi model's AD−BCAD - BC equals 11 (the program checks it). A regulation of 10 %10\ \% is large: in practice a tap changer or compensation would hold the receiving voltage (Voltage Control).

python · try it yourself
import numpy as np

z, y, ell = 0.0882 + 0.390j, 2.913e-6j, 120.0
Z, Y = z * ell, y * ell
VR = 132e3 / np.sqrt(3)
P, pf = 50e6, 0.9
IR = P / (np.sqrt(3) * 132e3 * pf) * np.exp(-1j * np.arccos(pf))
print(f"Z = {Z.real:.2f} + j{Z.imag:.2f} ohm, Y = j{Y.imag*1e6:.1f} uS, IR = {abs(IR):.1f} A at {np.degrees(np.angle(IR)):.2f} deg")

def abcd(model):
    if model == "short":
        return np.array([[1, Z], [0, 1]], complex)
    A = 1 + Y * Z / 2
    return np.array([[A, Z], [Y * (1 + Y * Z / 4), A]])

for model in ("short", "nominal pi"):
    M = abcd(model)
    Vs, Is = M @ np.array([VR, IR])
    Ss, Sr = 3 * Vs * np.conj(Is), 3 * VR * np.conj(IR)
    reg = (abs(Vs) / abs(M[0, 0]) - VR) / VR
    print(f"{model:10s}: Vs = {abs(Vs)*np.sqrt(3)/1e3:7.2f} kV at {np.degrees(np.angle(Vs)):5.2f} deg,"
          f" Is = {abs(Is):6.1f} A at {np.degrees(np.angle(Is)):6.2f} deg,"
          f" Ss = {Ss.real/1e6:5.2f} + j{Ss.imag/1e6:5.2f} MVA, VR = {100*reg:5.2f} %, eff = {100*Sr.real/Ss.real:5.2f} %")
    print(f"            AD - BC = {abs(np.linalg.det(M)):.6f}")

# Two 60 km halves in cascade equal one 120 km nominal pi? (no: lumping error)
Z2, Y2 = Z / 2, Y / 2
half = np.array([[1 + Y2*Z2/2, Z2], [Y2*(1 + Y2*Z2/4), 1 + Y2*Z2/2]])
M2 = half @ half
print(f"A of one 120 km pi: {abcd('nominal pi')[0,0]:.6f}, of two 60 km pis: {M2[0,0]:.6f}")
Z = 10.58 + j46.80 ohm, Y = j349.6 uS, IR = 243.0 A at -25.84 deg
short     : Vs =  145.45 kV at  6.23 deg, Is =  243.0 A at -25.84 deg, Ss = 51.87 + j32.51 MVA, VR = 10.19 %, eff = 96.39 %
            AD - BC = 1.000000
nominal pi: Vs =  144.41 kV at  6.37 deg, Is =  230.7 A at -19.79 deg, Ss = 51.79 + j25.44 MVA, VR = 10.30 %, eff = 96.54 %
            AD - BC = 1.000000
A of one 120 km pi: 0.991820+0.001850j, of two 60 km pis: 0.991828+0.001846j

Splitting the line into two π\pi sections hardly changes AA: at 120 km120\ \text{km} the nominal π\pi is already accurate to about 10−510^{-5}.

Interactive: the nominal π\pi under load

The netlist lab holds the π\pi circuit with the sending end at the 83.37 kV83.37\ \text{kV} phase voltage found above and the load as a constant impedance (348.5 Ω348.5\ \Omega in parallel with 2.290 H2.290\ \text{H}, which draws 50 MW50\ \text{MW} at pf 0.90.9 at 132 kV132\ \text{kV}). The capacitors are 0.5563 μF0.5563\ \mu\text{F} each. Read the values at the 50 Hz50\ \text{Hz} cursor: the receiving end r shows 76.21 kV∠−6.4∘76.21\ \text{kV}\angle -6.4^\circ and the series current 237.5 A237.5\ \text{A}, between the sending current (230.7 A230.7\ \text{A}) and the receiving current (243 A243\ \text{A}) because each end's capacitor takes about 1313 to 15 A15\ \text{A}. Slide RR up to remove the active load and watch the receiving voltage rise.

050000100m1101001k10kf (Hz)|V| (V)|V(r)||V(s)|phasors at f = 50.00 Hz (magnitude @ phase)V(s)83.4 kV @ 0.0 degV(m)81.2 kV @ 0.9 degV(r)76.2 kV @ -6.4 degI(V1)231 A @ 153.8 degI(C1)14.6 A @ 90.0 degI(R1)237 A @ -29.3 degI(L1)237 A @ -29.3 degI(C2)13.3 A @ 83.6 degI(RR)219 A @ -6.4 degI(LR)106 A @ -96.4 deg

Guided lab: a scaled line on the bench

Hand calculation. Scale the line down: 1 V1\ \text{V} at the bench is 10 kV10\ \text{kV}, and use a 1 kHz1\ \text{kHz} source so that small components work. A series 10 Ω10\ \Omega resistor plus 10 mH10\ \text{mH} inductor (62.8 Ω62.8\ \Omega) with 0.1 μF0.1\ \mu\text{F} (1.59 kΩ1.59\ \text{k}\Omega) at each end feeding a 220 Ω220\ \Omega load. Compute AA and VR/Vs\mathbf{V}_R/\mathbf{V}_s with the program (change Z, Y).

Simulation. Enter the same values in the netlist lab with f = 1000.

What you would measure. From a function generator at 5 V5\ \text{V} rms: the receiving voltage with a DMM, and the phase shift with a two-channel oscilloscope. Expect agreement within the components' tolerances (±5\pm 5 to 10 %10\ \%) and an extra loss from the inductor's own resistance (measure it with the DMM and add it to RR).

Hazards and safe setup. Signal levels only.

Pitfalls

  • Line voltage into the per-phase ABCD equations. Use phase voltages; convert back at the end.
  • Neglecting capacitance on a cable "because it is short". A 20 km20\ \text{km} cable has as much capacitance as 400 km400\ \text{km} of overhead line.
  • Regulation from the full-load sending voltage without dividing by ∣A∣\lvert A \rvert. The no-load receiving voltage is ∣Vs∣/∣A∣\lvert \mathbf{V}_s \rvert/\lvert A \rvert, which is above ∣Vs∣\lvert \mathbf{V}_s \rvert on long lines.
  • Assuming Is=IR\mathbf{I}_s = \mathbf{I}_R on a medium line.

Practice

  1. A 40 km40\ \text{km}, 33 kV33\ \text{kV} line has z=0.2+j0.35 Ω/kmz = 0.2 + j0.35\ \Omega/\text{km} and supplies 8 MW8\ \text{MW} at pf 0.850.85 lagging at 33 kV33\ \text{kV}. Find the sending-end line voltage (short-line model).
  2. Show that AD−BC=1AD - BC = 1 for the nominal π\pi.
  3. Two identical lines in parallel: what are the ABCD parameters of the pair?
Answer
  1. Z=8+j14 ΩZ = 8 + j14\ \Omega, I=8×106/(3⋅33 000⋅0.85)=164.7 A∠−31.79∘I = 8 \times 10^6/(\sqrt{3} \cdot 33\,000 \cdot 0.85) = 164.7\ \text{A}\angle -31.79^\circ; Vs=19 053+(8+j14)⋅164.7∠−31.79∘=21 424 V∠3.39∘\mathbf{V}_s = 19\,053 + (8 + j14) \cdot 164.7\angle -31.79^\circ = 21\,424\ \text{V}\angle 3.39^\circ (phase), 37.11 kV37.11\ \text{kV} line.
  2. AD−BC=(1+YZ/2)2−ZY(1+YZ/4)=1+YZ+Y2Z2/4−YZ−Y2Z2/4=1AD - BC = (1 + YZ/2)^2 - ZY(1 + YZ/4) = 1 + YZ + Y^2Z^2/4 - YZ - Y^2Z^2/4 = 1.
  3. AA and DD stay the same, BB halves (Z/2Z/2), CC doubles.

Test yourself

For a short line model, the ABCD parameters are…

  1. A = D = 1, B = Z, C = 0
  2. A = D = 1 + YZ/2, B = Z, C = Y
  3. A = 0, B = Z, C = Y, D = 1
  4. A = D = Z, B = C = 1

For a reciprocal two-port, AD - BC equals…

  1. 0
  2. 1
  3. -1
  4. Z

On an open-circuited medium line, the receiving voltage is…

  1. VsV_s
  2. Vs/∣A∣V_s/\lvert A \rvert, slightly above VsV_s
  3. VsAV_s A
  4. zero

Why does the nominal-pi sending current come out lower than the receiving current for a lagging load?

  1. losses
  2. the line's charging current partly cancels the lagging load current
  3. the transformer
  4. skin effect