Short and Medium Lines: the Nominal and ABCD Parameters
The previous two lessons gave the line its per-kilometre parameters: in series and in shunt. Now a utility wants to deliver at power factor over of it. What voltage must the sending end hold, how much current does it supply, what is the regulation and how much is lost? For lines up to a few hundred kilometres, lumping the distributed parameters into a few elements is accurate enough, and the result fits a four-number description, the ABCD (transmission) parameters, that chains neatly with transformers and other lines. Two-port parameters in general are in Two-Port Networks: h and ABCD.
Safety: transmission lines are studied here by calculation and simulation only.
Models by length
| Model | Length (50 Hz, rule of thumb) | Circuit |
|---|---|---|
| short line | below about | series only; shunt capacitance neglected |
| medium line, nominal | about to | in series, at each end, |
| long line | above about | exact distributed solution or the equivalent (Long Lines) |
The boundaries are conventions, not physics: they come from the error of lumping compared with the exact solution, which grows roughly with , where the wavelength at is about . Cables, with their large capacitance, need the model at much shorter lengths.
ABCD parameters
Any two-port between a sending end (s) and a receiving end (R) can be written as
For the models above:
Two lines or a transformer and a line in cascade multiply their matrices. also gives the open-circuit receiving voltage: with , . The voltage regulation compares that no-load voltage with the full-load one:
Worked example: 50 MW over 120 km
Given: the line, : , ; receiving end (line), at pf lagging.
Find: the sending-end voltage and current, the regulation and the efficiency, with the short and the nominal- models.
Solve: per phase, and .
The short-line model gives , , and .
Check: the line's charging current partly cancels the load's lagging current, so the model's sending current () is lower than the receiving current, and the sending end supplies instead of . The model's equals (the program checks it). A regulation of is large: in practice a tap changer or compensation would hold the receiving voltage (Voltage Control).
import numpy as np
z, y, ell = 0.0882 + 0.390j, 2.913e-6j, 120.0
Z, Y = z * ell, y * ell
VR = 132e3 / np.sqrt(3)
P, pf = 50e6, 0.9
IR = P / (np.sqrt(3) * 132e3 * pf) * np.exp(-1j * np.arccos(pf))
print(f"Z = {Z.real:.2f} + j{Z.imag:.2f} ohm, Y = j{Y.imag*1e6:.1f} uS, IR = {abs(IR):.1f} A at {np.degrees(np.angle(IR)):.2f} deg")
def abcd(model):
if model == "short":
return np.array([[1, Z], [0, 1]], complex)
A = 1 + Y * Z / 2
return np.array([[A, Z], [Y * (1 + Y * Z / 4), A]])
for model in ("short", "nominal pi"):
M = abcd(model)
Vs, Is = M @ np.array([VR, IR])
Ss, Sr = 3 * Vs * np.conj(Is), 3 * VR * np.conj(IR)
reg = (abs(Vs) / abs(M[0, 0]) - VR) / VR
print(f"{model:10s}: Vs = {abs(Vs)*np.sqrt(3)/1e3:7.2f} kV at {np.degrees(np.angle(Vs)):5.2f} deg,"
f" Is = {abs(Is):6.1f} A at {np.degrees(np.angle(Is)):6.2f} deg,"
f" Ss = {Ss.real/1e6:5.2f} + j{Ss.imag/1e6:5.2f} MVA, VR = {100*reg:5.2f} %, eff = {100*Sr.real/Ss.real:5.2f} %")
print(f" AD - BC = {abs(np.linalg.det(M)):.6f}")
# Two 60 km halves in cascade equal one 120 km nominal pi? (no: lumping error)
Z2, Y2 = Z / 2, Y / 2
half = np.array([[1 + Y2*Z2/2, Z2], [Y2*(1 + Y2*Z2/4), 1 + Y2*Z2/2]])
M2 = half @ half
print(f"A of one 120 km pi: {abcd('nominal pi')[0,0]:.6f}, of two 60 km pis: {M2[0,0]:.6f}")Z = 10.58 + j46.80 ohm, Y = j349.6 uS, IR = 243.0 A at -25.84 deg
short : Vs = 145.45 kV at 6.23 deg, Is = 243.0 A at -25.84 deg, Ss = 51.87 + j32.51 MVA, VR = 10.19 %, eff = 96.39 %
AD - BC = 1.000000
nominal pi: Vs = 144.41 kV at 6.37 deg, Is = 230.7 A at -19.79 deg, Ss = 51.79 + j25.44 MVA, VR = 10.30 %, eff = 96.54 %
AD - BC = 1.000000
A of one 120 km pi: 0.991820+0.001850j, of two 60 km pis: 0.991828+0.001846j
Splitting the line into two sections hardly changes : at the nominal is already accurate to about .
Interactive: the nominal under load
The netlist lab holds the circuit with the sending end at the phase voltage found above and the load as a constant impedance ( in parallel with , which draws at pf at ). The capacitors are each. Read the values at the cursor: the receiving end r shows and the series current , between the sending current () and the receiving current () because each end's capacitor takes about to . Slide RR up to remove the active load and watch the receiving voltage rise.
Guided lab: a scaled line on the bench
Hand calculation. Scale the line down: at the bench is , and use a source so that small components work. A series resistor plus inductor () with () at each end feeding a load. Compute and with the program (change Z, Y).
Simulation. Enter the same values in the netlist lab with f = 1000.
What you would measure. From a function generator at rms: the receiving voltage with a DMM, and the phase shift with a two-channel oscilloscope. Expect agreement within the components' tolerances ( to ) and an extra loss from the inductor's own resistance (measure it with the DMM and add it to ).
Hazards and safe setup. Signal levels only.
Pitfalls
- Line voltage into the per-phase ABCD equations. Use phase voltages; convert back at the end.
- Neglecting capacitance on a cable "because it is short". A cable has as much capacitance as of overhead line.
- Regulation from the full-load sending voltage without dividing by . The no-load receiving voltage is , which is above on long lines.
- Assuming on a medium line.
Practice
- A , line has and supplies at pf lagging at . Find the sending-end line voltage (short-line model).
- Show that for the nominal .
- Two identical lines in parallel: what are the ABCD parameters of the pair?
Answer
- , ; (phase), line.
- .
- and stay the same, halves (), doubles.
Test yourself
For a short line model, the ABCD parameters are…
- A = D = 1, B = Z, C = 0
- A = D = 1 + YZ/2, B = Z, C = Y
- A = 0, B = Z, C = Y, D = 1
- A = D = Z, B = C = 1
For a reciprocal two-port, AD - BC equals…
- 0
- 1
- -1
- Z
On an open-circuited medium line, the receiving voltage is…
- , slightly above
- zero
Why does the nominal-pi sending current come out lower than the receiving current for a lagging load?
- losses
- the line's charging current partly cancels the lagging load current
- the transformer
- skin effect