Long Lines: Propagation, the Exact and Surge Impedance Loading
A line long is already one fifteenth of a wavelength at . Its voltage and current are no longer the same along it, the lumped model starts to drift, and something remarkable happens at one particular load: the line's reactive power balances itself, the voltage is flat along the whole length, and the line neither needs nor supplies vars. That load, the surge impedance loading (SIL), is the yardstick for every long line. This lesson solves the line exactly, builds the exact equivalent , and uses SIL to explain how long lines are loaded. The wave equations of a line (, , reflections) are derived in The Transmission-Line Model.
Safety: extra-high-voltage lines are studied here by calculation and simulation only.
The exact solution
With series impedance and shunt admittance per unit length, voltage and current along the line obey the telegrapher's equations. Measuring back from the receiving end:
So the ABCD parameters of a line of length are
is the phase constant (radians per km), the wavelength (close to at on overhead lines), the attenuation, and the characteristic (surge) impedance, about to for overhead lines and to for cables.
The exact equivalent
Any symmetrical two-port can be drawn as a . Matching its ABCD parameters to the exact ones gives
The nominal (, ) is the first term of these series; the correction factors tend to 1 for short lines. Load-flow programs use the exact for long lines so that a single branch is still correct.
Surge impedance loading
If a line is terminated in its own characteristic impedance, , the backward wave vanishes and, for a lossless line (, real),
At SIL the reactive power absorbed by the series inductance, per km, exactly equals that generated by the shunt capacitance, per km. Below SIL the capacitance wins: the line generates vars and the voltage rises toward the receiving end (in the limit at no load, the Ferranti effect). Above SIL the inductance wins: the line absorbs vars and the voltage sags. Typical SIL values (2020s textbook ranges): about at , to at , and more at . Bundling lowers and so raises SIL.
Worked example: a 400 km, 400 kV line
Given: a line with two-conductor bundles: , (from the bundle of Line Capacitance), .
Find: , , the wavelength, the ABCD parameters, the exact and nominal , and the SIL.
Solve:
The exact has against the nominal ( less reactance), and is larger than .
Check: , and : the real part of agrees. A lossless line with the same and has ; the losses barely change it.
import numpy as np
z, y, ell = 0.030 + 0.3383j, 3.311e-6j, 400.0
g = np.sqrt(z * y)
Zc = np.sqrt(z / y)
print(f"gamma = {g.real:.3e} + j{g.imag:.4e} 1/km, Zc = {Zc.real:.1f} {Zc.imag:+.1f}j ohm, wavelength = {2*np.pi/g.imag:.0f} km")
A = np.cosh(g * ell); B = Zc * np.sinh(g * ell); C = np.sinh(g * ell) / Zc
print(f"A = {A:.4f}, B = {B:.2f} ohm, C = {C.imag*1e3:.4f}j mS")
Zp, Yp = B, 2 * np.tanh(g * ell / 2) / Zc
print(f"exact pi: Z' = {Zp:.2f} ohm, Y'/2 = {Yp.imag/2*1e3:.4f}j mS")
print(f"nominal pi: Z = {z*ell:.2f} ohm, Y/2 = {(y*ell).imag/2*1e3:.4f}j mS")
print(f"SIL = {400e3**2 / abs(Zc) / 1e6:.1f} MW")
# Sending voltage needed to hold 400 kV at the receiving end, unity-pf load
VR = 400e3 / np.sqrt(3)
for frac in (0.0, 0.5, 1.0, 1.5):
P = frac * 400e3**2 / abs(Zc)
IR = P / (3 * VR)
Vs = A * VR + B * IR
Is = C * VR + A * IR
Qs = (3 * Vs * np.conj(Is)).imag
print(f"P = {frac:.1f} SIL ({P/1e6:5.0f} MW): Vs = {abs(Vs)*np.sqrt(3)/1e3:5.1f} kV at {np.degrees(np.angle(Vs)):5.1f} deg, Qs = {Qs/1e6:+6.0f} Mvar")
# Voltage profile at 0 and 1 SIL with the sending end held at 400 kV (receiving end floats)
x = np.linspace(0, ell, 5)
for frac in (0.0, 1.0):
ZL = np.inf if frac == 0 else 400e3**2 / (frac * 400e3**2 / abs(Zc))
# receiving voltage for Vs = 400 kV: Vs = (A + B/ZL) VR
VRr = (400e3 / np.sqrt(3)) / (A + (0 if frac == 0 else B / ZL))
IRr = 0 if frac == 0 else VRr / ZL
prof = [abs(VRr * np.cosh(g * (ell - xi)) + Zc * IRr * np.sinh(g * (ell - xi))) * np.sqrt(3) / 1e3 for xi in x]
print(f"{frac:.0f} SIL, profile from sending end (kV):", np.round(prof, 1))gamma = 4.688e-05 + j1.0594e-03 1/km, Zc = 320.0 -14.2j ohm, wavelength = 5931 km
A = 0.9117+0.0077j, B = 11.29+131.35j ohm, C = 1.2852j mS
exact pi: Z' = 11.29+131.35j ohm, Y'/2 = 0.6723j mS
nominal pi: Z = 12.00+135.32j ohm, Y/2 = 0.6622j mS
SIL = 499.6 MW
P = 0.0 SIL ( 0 MW): Vs = 364.7 kV at 0.5 deg, Qs = -187 Mvar
P = 0.5 SIL ( 250 MW): Vs = 381.4 kV at 12.9 deg, Qs = -145 Mvar
P = 1.0 SIL ( 500 MW): Vs = 414.0 kV at 23.8 deg, Qs = -8 Mvar
P = 1.5 SIL ( 749 MW): Vs = 459.3 kV at 32.9 deg, Qs = +221 Mvar
0 SIL, profile from sending end (kV): [400. 416.8 428.9 436.3 438.7]
1 SIL, profile from sending end (kV): [400. 396.9 393.6 390.1 386.5]
At no load the sending end must absorb of line charging, and with at the sending end the open end rises to , almost high. At SIL the sending end exchanges only and the profile is nearly flat (the sag comes from the resistance, which the lossless theory ignores). At SIL the line absorbs and needs at the sending end, which is beyond the equipment limit: long lines are rarely loaded much above SIL without series compensation.
Interactive: a matched line has no reflection
The transmission-line lab is a scaled, lossless line with a step source; its time axis is in units of the one-way delay (for our line , far outside the lab's nanosecond scale, so treat it as a scale model). With , and a load (the line terminated in its surge impedance), the lab shows , a launched wave of from a source, at both ends after one transit and a VSWR of 1: the wave simply runs into the load. This is SIL in the time domain. Switch the termination to "open" and the reflected wave doubles the far-end voltage to (), the transient picture behind the open-line voltage rise.
Guided lab: a cable terminated in its characteristic impedance
Hand calculation. of coaxial cable (velocity factor about ) has a one-way delay of about . Terminated in , a fast step at the input should show no reflection; open-ended, a step that doubles after at the input.
Simulation. Set the lab to , , and try , open and short.
What you would measure. With a function generator's fast square wave (or a pulse generator) and an oscilloscope at the cable input, the step staircase of Transmission-Line Transients: flat with a terminator, a double-height step after the round trip with the end open. Expect the timing within (velocity factor tolerance) and edges rounded by the generator's rise time.
Hazards and safe setup. Signal levels only.
Pitfalls
- Using the nominal on very long lines. At the series reactance is off; at much more. Use the exact .
- Hyperbolic functions of complex arguments. Use complex-capable functions (
np.coshon complex numbers), not real approximations. - Thinking SIL is a thermal limit. Short lines carry several times their SIL (thermal limit); long lines carry less than about SIL (voltage and stability limits).
- Ignoring losses at SIL. A real line still has a small voltage drop at SIL.
Practice
- A lossless line has and . Find , the wave speed and the SIL at .
- What is for a line at with a wave speed of ?
- Why does series compensation raise the power a long line can carry?
Answer
- ; ; .
- ; .
- It cancels part of the series reactance, which lowers the angle needed for a given power () and the reactive losses.
Test yourself
At surge impedance loading, a lossless line…
- has zero current
- has a flat voltage profile and no net reactive power exchange
- is at its thermal limit
- has a 90° phase shift
The ABCD parameter A of a long line is…
A 400 kV line has . Its SIL is about…
- 1.25 MW
- 125 MW
- 500 MW
- 1250 MW
Loaded below SIL, a long line…
- absorbs reactive power
- generates net reactive power and its voltage rises toward the receiving end
- has no losses
- trips