Home › Power Systems: Three-Phase, Generation, Grids & Protection › Long Lines: Propagation, the Exact π and Surge Impedance Loading

Long Lines: Propagation, the Exact π\pi and Surge Impedance Loading

A 400 kV400\ \text{kV} line 400 km400\ \text{km} long is already one fifteenth of a wavelength at 50 Hz50\ \text{Hz}. Its voltage and current are no longer the same along it, the lumped π\pi model starts to drift, and something remarkable happens at one particular load: the line's reactive power balances itself, the voltage is flat along the whole length, and the line neither needs nor supplies vars. That load, the surge impedance loading (SIL), is the yardstick for every long line. This lesson solves the line exactly, builds the exact equivalent π\pi, and uses SIL to explain how long lines are loaded. The wave equations of a line (γ\gamma, ZcZ_c, reflections) are derived in The Transmission-Line Model.

Safety: extra-high-voltage lines are studied here by calculation and simulation only.

The exact solution

With series impedance zz and shunt admittance yy per unit length, voltage and current along the line obey the telegrapher's equations. Measuring xx back from the receiving end:

V(x)=VRcosh⁡γx+ZcIRsinh⁡γx,I(x)=VRZcsinh⁡γx+IRcosh⁡γxγ=zy=α+jβ,Zc=zy\begin{aligned} \mathbf{V}(x) &= \mathbf{V}_R\cosh\gamma x + Z_c\mathbf{I}_R\sinh\gamma x, \qquad \mathbf{I}(x) = \frac{\mathbf{V}_R}{Z_c}\sinh\gamma x + \mathbf{I}_R\cosh\gamma x \\ \gamma &= \sqrt{zy} = \alpha + j\beta, \qquad Z_c = \sqrt{\frac{z}{y}} \end{aligned}

So the ABCD parameters of a line of length ℓ\ell are

A=D=cosh⁡γℓ,B=Zcsinh⁡γℓ,C=sinh⁡γℓZcA = D = \cosh\gamma\ell, \qquad B = Z_c\sinh\gamma\ell, \qquad C = \frac{\sinh\gamma\ell}{Z_c}

β\beta is the phase constant (radians per km), λ=2π/β\lambda = 2\pi/\beta the wavelength (close to 6000 km6000\ \text{km} at 50 Hz50\ \text{Hz} on overhead lines), α\alpha the attenuation, and ZcZ_c the characteristic (surge) impedance, about 250250 to 400 Ω400\ \Omega for overhead lines and 2020 to 60 Ω60\ \Omega for cables.

The exact equivalent π\pi

Any symmetrical two-port can be drawn as a π\pi. Matching its ABCD parameters to the exact ones gives

Z′=Zcsinh⁡γℓ=Z sinh⁡γℓγℓ,Y′2=tanh⁡(γℓ/2)Zc=Y2 tanh⁡(γℓ/2)γℓ/2Z' = Z_c\sinh\gamma\ell = Z\,\frac{\sinh\gamma\ell}{\gamma\ell}, \qquad \frac{Y'}{2} = \frac{\tanh(\gamma\ell/2)}{Z_c} = \frac{Y}{2}\,\frac{\tanh(\gamma\ell/2)}{\gamma\ell/2}

The nominal π\pi (ZZ, Y/2Y/2) is the first term of these series; the correction factors tend to 1 for short lines. Load-flow programs use the exact π\pi for long lines so that a single branch is still correct.

Surge impedance loading

If a line is terminated in its own characteristic impedance, VR=ZcIR\mathbf{V}_R = Z_c\mathbf{I}_R, the backward wave vanishes and, for a lossless line (Zc=L/CZ_c = \sqrt{L/C}, real),

∣V(x)∣=∣VR∣ everywhere,SIL=VL2Zc\lvert \mathbf{V}(x) \rvert = \lvert \mathbf{V}_R \rvert \ \text{everywhere}, \qquad \text{SIL} = \frac{V_L^2}{Z_c}

At SIL the reactive power absorbed by the series inductance, I2ωLI^2\omega L per km, exactly equals that generated by the shunt capacitance, V2ωCV^2\omega C per km. Below SIL the capacitance wins: the line generates vars and the voltage rises toward the receiving end (in the limit at no load, the Ferranti effect). Above SIL the inductance wins: the line absorbs vars and the voltage sags. Typical SIL values (2020s textbook ranges): about 50 MW50\ \text{MW} at 132 kV132\ \text{kV}, 500500 to 600 MW600\ \text{MW} at 400 kV400\ \text{kV}, 2000 MW2000\ \text{MW} and more at 765 kV765\ \text{kV}. Bundling lowers ZcZ_c and so raises SIL.

Worked example: a 400 km, 400 kV line

Given: a 400 kV400\ \text{kV} line with two-conductor bundles: z=0.030+j0.3383 Ω/kmz = 0.030 + j0.3383\ \Omega/\text{km}, y=j3.311 μS/kmy = j3.311\ \mu\text{S/km} (from the bundle of Line Capacitance), ℓ=400 km\ell = 400\ \text{km}.

Find: γ\gamma, ZcZ_c, the wavelength, the ABCD parameters, the exact and nominal π\pi, and the SIL.

Solve:

γ=(0.030+j0.3383)(j3.311×10−6)=(4.688×10−5+j1.0594×10−3) km−1Zc=0.030+j0.3383j3.311×10−6=320.0−j14.2 Ω,λ=2πβ=5931 kmA=cosh⁡γℓ=0.9117+j0.0077,B=11.29+j131.35 Ω,C=j1.2852×10−3 SSIL=(400 kV)2320.27 Ω=499.6 MW\begin{aligned} \gamma &= \sqrt{(0.030 + j0.3383)(j3.311 \times 10^{-6})} = (4.688 \times 10^{-5} + j1.0594 \times 10^{-3})\ \text{km}^{-1} \\ Z_c &= \sqrt{\frac{0.030 + j0.3383}{j3.311 \times 10^{-6}}} = 320.0 - j14.2\ \Omega, \qquad \lambda = \frac{2\pi}{\beta} = 5931\ \text{km} \\ A &= \cosh\gamma\ell = 0.9117 + j0.0077, \qquad B = 11.29 + j131.35\ \Omega, \qquad C = j1.2852 \times 10^{-3}\ \text{S} \\ \text{SIL} &= \frac{(400\ \text{kV})^2}{320.27\ \Omega} = 499.6\ \text{MW} \end{aligned}

The exact π\pi has Z′=11.29+j131.35 ΩZ' = 11.29 + j131.35\ \Omega against the nominal Z=12.0+j135.32 ΩZ = 12.0 + j135.32\ \Omega (3 %3\ \% less reactance), and Y′/2Y'/2 is 1.5 %1.5\ \% larger than Y/2Y/2.

Check: βℓ=0.424 rad=24.3∘\beta\ell = 0.424\ \text{rad} = 24.3^\circ, and cosh⁡γℓ≈cos⁡βℓ=0.911\cosh\gamma\ell \approx \cos\beta\ell = 0.911: the real part of AA agrees. A lossless line with the same LL and CC has Zc=L/C=319.6 ΩZ_c = \sqrt{L/C} = 319.6\ \Omega; the losses barely change it.

python · try it yourself
import numpy as np

z, y, ell = 0.030 + 0.3383j, 3.311e-6j, 400.0
g = np.sqrt(z * y)
Zc = np.sqrt(z / y)
print(f"gamma = {g.real:.3e} + j{g.imag:.4e} 1/km, Zc = {Zc.real:.1f} {Zc.imag:+.1f}j ohm, wavelength = {2*np.pi/g.imag:.0f} km")
A = np.cosh(g * ell); B = Zc * np.sinh(g * ell); C = np.sinh(g * ell) / Zc
print(f"A = {A:.4f}, B = {B:.2f} ohm, C = {C.imag*1e3:.4f}j mS")
Zp, Yp = B, 2 * np.tanh(g * ell / 2) / Zc
print(f"exact pi:   Z' = {Zp:.2f} ohm, Y'/2 = {Yp.imag/2*1e3:.4f}j mS")
print(f"nominal pi: Z  = {z*ell:.2f} ohm, Y/2  = {(y*ell).imag/2*1e3:.4f}j mS")
print(f"SIL = {400e3**2 / abs(Zc) / 1e6:.1f} MW")

# Sending voltage needed to hold 400 kV at the receiving end, unity-pf load
VR = 400e3 / np.sqrt(3)
for frac in (0.0, 0.5, 1.0, 1.5):
    P = frac * 400e3**2 / abs(Zc)
    IR = P / (3 * VR)
    Vs = A * VR + B * IR
    Is = C * VR + A * IR
    Qs = (3 * Vs * np.conj(Is)).imag
    print(f"P = {frac:.1f} SIL ({P/1e6:5.0f} MW): Vs = {abs(Vs)*np.sqrt(3)/1e3:5.1f} kV at {np.degrees(np.angle(Vs)):5.1f} deg, Qs = {Qs/1e6:+6.0f} Mvar")

# Voltage profile at 0 and 1 SIL with the sending end held at 400 kV (receiving end floats)
x = np.linspace(0, ell, 5)
for frac in (0.0, 1.0):
    ZL = np.inf if frac == 0 else 400e3**2 / (frac * 400e3**2 / abs(Zc))
    # receiving voltage for Vs = 400 kV: Vs = (A + B/ZL) VR
    VRr = (400e3 / np.sqrt(3)) / (A + (0 if frac == 0 else B / ZL))
    IRr = 0 if frac == 0 else VRr / ZL
    prof = [abs(VRr * np.cosh(g * (ell - xi)) + Zc * IRr * np.sinh(g * (ell - xi))) * np.sqrt(3) / 1e3 for xi in x]
    print(f"{frac:.0f} SIL, profile from sending end (kV):", np.round(prof, 1))
gamma = 4.688e-05 + j1.0594e-03 1/km, Zc = 320.0 -14.2j ohm, wavelength = 5931 km
A = 0.9117+0.0077j, B = 11.29+131.35j ohm, C = 1.2852j mS
exact pi:   Z' = 11.29+131.35j ohm, Y'/2 = 0.6723j mS
nominal pi: Z  = 12.00+135.32j ohm, Y/2  = 0.6622j mS
SIL = 499.6 MW
P = 0.0 SIL (    0 MW): Vs = 364.7 kV at   0.5 deg, Qs =   -187 Mvar
P = 0.5 SIL (  250 MW): Vs = 381.4 kV at  12.9 deg, Qs =   -145 Mvar
P = 1.0 SIL (  500 MW): Vs = 414.0 kV at  23.8 deg, Qs =     -8 Mvar
P = 1.5 SIL (  749 MW): Vs = 459.3 kV at  32.9 deg, Qs =   +221 Mvar
0 SIL, profile from sending end (kV): [400.  416.8 428.9 436.3 438.7]
1 SIL, profile from sending end (kV): [400.  396.9 393.6 390.1 386.5]

At no load the sending end must absorb 187 Mvar187\ \text{Mvar} of line charging, and with 400 kV400\ \text{kV} at the sending end the open end rises to 438.7 kV438.7\ \text{kV}, almost 10 %10\ \% high. At SIL the sending end exchanges only 8 Mvar8\ \text{Mvar} and the profile is nearly flat (the 3.4 %3.4\ \% sag comes from the resistance, which the lossless theory ignores). At 1.51.5 SIL the line absorbs 221 Mvar221\ \text{Mvar} and needs 459 kV459\ \text{kV} at the sending end, which is beyond the 420 kV420\ \text{kV} equipment limit: long lines are rarely loaded much above SIL without series compensation.

Interactive: a matched line has no reflection

The transmission-line lab is a scaled, lossless line with a step source; its time axis is in units of the one-way delay TdT_d (for our 400 km400\ \text{km} line Td≈1.35 msT_d \approx 1.35\ \text{ms}, far outside the lab's nanosecond scale, so treat it as a scale model). With Z0=150 ΩZ_0 = 150\ \Omega, Rs=150 ΩR_s = 150\ \Omega and a load RL=150 ΩR_L = 150\ \Omega (the line terminated in its surge impedance), the lab shows ΓL=0\Gamma_L = 0, a launched wave of 5 V5\ \text{V} from a 10 V10\ \text{V} source, 5 V5\ \text{V} at both ends after one transit and a VSWR of 1: the wave simply runs into the load. This is SIL in the time domain. Switch the termination to "open" and the reflected wave doubles the far-end voltage to 10 V10\ \text{V} (ΓL=1\Gamma_L = 1), the transient picture behind the open-line voltage rise.

024source endload endv(x) (V)t = 8.00 Td = 8.00 nsS10.0 VRs 150 OhmZ0 = 150 Ohm, one-way delay Td = 1.00 nsRL 150 Ohm0 Td2 Td4 Td6 Td8 TdGS = 0.000GL = 0.0005.00002402468t (Td)v at source endv at load end

Guided lab: a cable terminated in its characteristic impedance

Hand calculation. 10 m10\ \text{m} of 50 Ω50\ \Omega coaxial cable (velocity factor about 0.660.66) has a one-way delay of about 50 ns50\ \text{ns}. Terminated in 50 Ω50\ \Omega, a fast step at the input should show no reflection; open-ended, a step that doubles after 100 ns100\ \text{ns} at the input.

Simulation. Set the lab to Z0=50 ΩZ_0 = 50\ \Omega, Rs=50 ΩR_s = 50\ \Omega, Td=50 nsT_d = 50\ \text{ns} and try RL=50R_L = 50, open and short.

What you would measure. With a function generator's fast square wave (or a pulse generator) and an oscilloscope at the cable input, the step staircase of Transmission-Line Transients: flat with a 50 Ω50\ \Omega terminator, a double-height step after the round trip with the end open. Expect the timing within 5 %5\ \% (velocity factor tolerance) and edges rounded by the generator's rise time.

Hazards and safe setup. Signal levels only.

Pitfalls

  • Using the nominal π\pi on very long lines. At 400 km400\ \text{km} the series reactance is 3 %3\ \% off; at 800 km800\ \text{km} much more. Use the exact π\pi.
  • Hyperbolic functions of complex arguments. Use complex-capable functions (np.cosh on complex numbers), not real approximations.
  • Thinking SIL is a thermal limit. Short lines carry several times their SIL (thermal limit); long lines carry less than about SIL (voltage and stability limits).
  • Ignoring losses at SIL. A real line still has a small voltage drop at SIL.

Practice

  1. A lossless line has L=1.0 mH/kmL = 1.0\ \text{mH/km} and C=11.5 nF/kmC = 11.5\ \text{nF/km}. Find ZcZ_c, the wave speed and the SIL at 220 kV220\ \text{kV}.
  2. What is βℓ\beta\ell for a 300 km300\ \text{km} line at 50 Hz50\ \text{Hz} with a wave speed of 2.95×105 km/s2.95 \times 10^5\ \text{km/s}?
  3. Why does series compensation raise the power a long line can carry?
Answer
  1. Zc=10−3/1.15×10−8=294.9 ΩZ_c = \sqrt{10^{-3}/1.15 \times 10^{-8}} = 294.9\ \Omega; v=1/LC=2.95×105 km/sv = 1/\sqrt{LC} = 2.95 \times 10^5\ \text{km/s}; SIL=2202/294.9=164 MW\text{SIL} = 220^2/294.9 = 164\ \text{MW}.
  2. λ=v/f=5900 km\lambda = v/f = 5900\ \text{km}; βℓ=2π⋅300/5900=0.319 rad=18.3∘\beta\ell = 2\pi \cdot 300/5900 = 0.319\ \text{rad} = 18.3^\circ.
  3. It cancels part of the series reactance, which lowers the angle needed for a given power (P≈VsVRsin⁡δ/XP \approx V_sV_R\sin\delta/X) and the reactive losses.

Test yourself

At surge impedance loading, a lossless line…

  1. has zero current
  2. has a flat voltage profile and no net reactive power exchange
  3. is at its thermal limit
  4. has a 90° phase shift

The ABCD parameter A of a long line is…

  1. 11
  2. cosh⁡γℓ\cosh\gamma\ell
  3. Zcsinh⁡γℓZ_c\sinh\gamma\ell
  4. γℓ\gamma\ell

A 400 kV line has Zc=320 ΩZ_c = 320\ \Omega. Its SIL is about…

  1. 1.25 MW
  2. 125 MW
  3. 500 MW
  4. 1250 MW

Loaded below SIL, a long line…

  1. absorbs reactive power
  2. generates net reactive power and its voltage rises toward the receiving end
  3. has no losses
  4. trips