The Equal-Area Criterion and Critical Clearing Time

The swing simulations of the previous lesson showed P1 surviving a fault cleared in 0.20 s0.20\ \text{s} and losing synchronism at 0.25 s0.25\ \text{s}. Where exactly is the limit? For one machine against an infinite bus there is an answer without integrating anything: an energy balance drawn as two areas on the power-angle diagram. The equal-area criterion gives the critical clearing angle in closed form, explains intuitively what helps stability (fast clearing, more lines, higher voltage, less load), and is the yardstick for checking numerical results.

Safety: generators and transmission faults are studied here by calculation and simulation only.

Energy on the power-angle diagram

Multiply the swing equation (The Swing Equation) by dδ/dtd\delta/dt and integrate:

Hωs(dδdt)2=∫δ0δ(Pm−Pe)dδ\frac{H}{\omega_s}\left(\frac{d\delta}{dt}\right)^2 = \int_{\delta_0}^{\delta}\left(P_m - P_e\right) d\delta

The left side is the rotor's extra kinetic energy (in per-unit seconds). The rotor stops advancing, dδ/dt=0d\delta/dt = 0, at the angle where the integral returns to zero. So the area where Pm>PeP_m > P_e (acceleration, A1A_1) must be matched by an equal area where Pe>PmP_e > P_m (deceleration, A2A_2) before δ\delta passes δmax⁡\delta_{\max}, the angle beyond which the post-fault curve falls below PmP_m again:

A1=∫δ0δc(Pm−Pmax⁡,2sin⁡δ)dδ ≤ A2,avail=∫δcδmax⁡(Pmax⁡,3sin⁡δ−Pm)dδ,δmax⁡=π−arcsin⁡PmPmax⁡,3A_1 = \int_{\delta_0}^{\delta_c}\left(P_m - P_{\max,2}\sin\delta\right)d\delta \ \le\ A_{2,\text{avail}} = \int_{\delta_c}^{\delta_{\max}}\left(P_{\max,3}\sin\delta - P_m\right)d\delta, \qquad \delta_{\max} = \pi - \arcsin\frac{P_m}{P_{\max,3}}

Here Pmax⁡,2P_{\max,2} is the amplitude during the fault and Pmax⁡,3P_{\max,3} after clearing. Setting the two equal gives the critical clearing angle:

cos⁡δcr=Pm(δmax⁡−δ0)+Pmax⁡,3cos⁡δmax⁡−Pmax⁡,2cos⁡δ0Pmax⁡,3−Pmax⁡,2\cos\delta_{cr} = \frac{P_m(\delta_{\max} - \delta_0) + P_{\max,3}\cos\delta_{\max} - P_{\max,2}\cos\delta_0}{P_{\max,3} - P_{\max,2}}

When Pmax⁡,2=0P_{\max,2} = 0 (a bolted fault that blocks all transfer) the rotor accelerates uniformly, δ=δ0+ωsPm4Ht2\delta = \delta_0 + \frac{\omega_s P_m}{4H}t^2, and the critical clearing time follows directly:

tcr=4H (δcr−δ0)ωsPmt_{cr} = \sqrt{\frac{4H\,(\delta_{cr} - \delta_0)}{\omega_s P_m}}

For a partial fault (Pmax⁡,2>0P_{\max,2} > 0) there is no closed form for the time: integrate the swing equation until δ=δcr\delta = \delta_{cr}.

Worked example: P1, fault on the HV bus

Given: plant P1 with Pm=0.8 puP_m = 0.8\ \text{pu}, H=5 sH = 5\ \text{s}, δ0=27.01∘\delta_0 = 27.01^\circ (0.4715 rad0.4715\ \text{rad}), Pmax⁡,1=1.761P_{\max,1} = 1.761, Pmax⁡,2=0P_{\max,2} = 0, Pmax⁡,3=1.321P_{\max,3} = 1.321 (line 2 tripped).

Find: δmax⁡\delta_{\max}, δcr\delta_{cr} and tcrt_{cr}.

Solve:

δmax⁡=180∘−arcsin⁡0.81.321=180∘−37.27∘=142.73∘ (2.4911 rad)cos⁡δcr=0.8 (2.4911−0.4715)+1.321cos⁡142.73∘1.321=1.6157−1.05111.321=0.4274δcr=64.71∘ (1.1294 rad)tcr=4⋅5⋅(1.1294−0.4715)314.16⋅0.8=0.229 s\begin{aligned} \delta_{\max} &= 180^\circ - \arcsin\frac{0.8}{1.321} = 180^\circ - 37.27^\circ = 142.73^\circ\ (2.4911\ \text{rad}) \\ \cos\delta_{cr} &= \frac{0.8\,(2.4911 - 0.4715) + 1.321\cos 142.73^\circ}{1.321} = \frac{1.6157 - 1.0511}{1.321} = 0.4274 \\ \delta_{cr} &= 64.71^\circ\ (1.1294\ \text{rad}) \\ t_{cr} &= \sqrt{\frac{4 \cdot 5 \cdot (1.1294 - 0.4715)}{314.16 \cdot 0.8}} = 0.229\ \text{s} \end{aligned}

Check: the swing simulations bracketed the limit between 0.200.20 and 0.25 s0.25\ \text{s}, and 0.229 s0.229\ \text{s} lies in between. A transmission breaker with relay and breaker times of about 8080 to 100 ms100\ \text{ms} clears well inside it; a breaker failure, backed up after another 150150 to 250 ms250\ \text{ms}, would not, which is why breaker-failure protection at power-station substations is fast.

In Python: closed form, bisection and the areas

The second fault is at the middle of line 2. During it the generator still transfers some power: a star of j0.40j0.40 (generator and transformer), j0.40j0.40 (line 1) and j0.20j0.20 (half of line 2 to the fault) converts to a transfer reactance X12=0.4⋅0.4+0.4⋅0.2+0.2⋅0.40.2=1.60 puX_{12} = \frac{0.4 \cdot 0.4 + 0.4 \cdot 0.2 + 0.2 \cdot 0.4}{0.2} = 1.60\ \text{pu}, so Pmax⁡,2=1.057/1.60=0.661P_{\max,2} = 1.057/1.60 = 0.661.

python · try it yourself
import numpy as np
from scipy.integrate import solve_ivp
import matplotlib.pyplot as plt

H, Pm, ws = 5.0, 0.8, 2 * np.pi * 50
Ep, d0 = 1.05684, np.radians(27.0125)
P1, P3 = Ep / 0.60, Ep / 0.80
dmax = np.pi - np.arcsin(Pm / P3)

def delta_cr(P2):
    c = (Pm * (dmax - d0) + P3 * np.cos(dmax) - P2 * np.cos(d0)) / (P3 - P2)
    return np.arccos(c)

def first_swing_max(tc, P2):
    f = lambda t, x, P: [x[1], ws / (2 * H) * (Pm - P * np.sin(x[0]))]
    o = dict(max_step=1e-3, rtol=1e-9, atol=1e-9)
    a = solve_ivp(f, [0, tc], [d0, 0.0], args=(P2,), **o)
    b = solve_ivp(f, [tc, 3.0], a.y[:, -1], args=(P3,), **o)
    return b.y[0].max()

def t_cr_bisect(P2):
    lo, hi = 0.01, 2.0
    for _ in range(30):
        mid = (lo + hi) / 2
        lo, hi = (mid, hi) if first_swing_max(mid, P2) < np.pi else (lo, mid)
    return lo

X12 = (0.4 * 0.4 + 0.4 * 0.2 + 0.2 * 0.4) / 0.2
for name, P2 in [("bolted at HV bus", 0.0), ("middle of line 2", Ep / X12)]:
    dc = delta_cr(P2)
    line = f"{name:17s}: Pmax2 = {P2:.3f}, delta_cr = {np.degrees(dc):6.2f} deg, t_cr (simulated) = {t_cr_bisect(P2):.3f} s"
    if P2 == 0:
        line += f", closed form {np.sqrt(4 * H * (dc - d0) / (ws * Pm)):.3f} s"
    print(line)

dc = delta_cr(0.0)
d = np.linspace(0, np.pi, 400)
fig, ax = plt.subplots(figsize=(6, 3.6))
ax.plot(np.degrees(d), P1 * np.sin(d), label="pre-fault")
ax.plot(np.degrees(d), P3 * np.sin(d), label="post-fault (line 2 out)")
ax.axhline(Pm, c="k", lw=1, label="Pm = 0.8")
m1 = (d >= d0) & (d <= dc); m2 = (d >= dc) & (d <= dmax)
ax.fill_between(np.degrees(d[m1]), 0, Pm, alpha=0.3, label="A1 (accelerating)")
ax.fill_between(np.degrees(d[m2]), Pm, P3 * np.sin(d[m2]), alpha=0.3, label="A2 (decelerating)")
ax.set_xlabel("rotor angle (deg)"); ax.set_ylabel("P (pu)"); ax.set_xlim(0, 180)
ax.legend(fontsize=7); ax.grid(alpha=0.3); fig.tight_layout()
plt.show()
bolted at HV bus : Pmax2 = 0.000, delta_cr =  64.71 deg, t_cr (simulated) = 0.229 s, closed form 0.229 s
middle of line 2 : Pmax2 = 0.661, delta_cr =  92.08 deg, t_cr (simulated) = 0.428 s

The figure draws the bolted case cleared exactly at δcr\delta_{cr}: A1A_1 (between PmP_m and zero, from 27∘27^\circ to 64.7∘64.7^\circ) equals A2A_2 (between the post-fault curve and PmP_m, from 64.7∘64.7^\circ to 142.7∘142.7^\circ). A fault in the middle of the line is much less severe: some power still flows, the rotor accelerates more slowly, and the limit almost doubles to 0.43 s0.43\ \text{s}.

What improves transient stability

Read straight off the areas:

  • Faster clearing shrinks A1A_1 (the most effective measure; also single-pole tripping and fast reclosing).
  • A stronger post-fault network (more parallel lines, series compensation, higher voltage) raises Pmax⁡,3P_{\max,3} and so A2A_2.
  • Lower pre-fault loading lowers PmP_m, which shrinks A1A_1 and enlarges A2A_2.
  • Higher inertia does not change the areas but slows the swing, so tcrt_{cr} grows as H\sqrt{H}.
  • Fast excitation raises E′E' during the swing; fast valving or braking resistors cut Pm−PeP_m - P_e.

Guided lab: the critical time on paper and in simulation

Hand calculation. Repeat the worked example with Pm=0.6 puP_m = 0.6\ \text{pu}: find δ0\delta_0 (keep E′=1.057E' = 1.057, so δ0=arcsin⁡(0.6/1.761)=19.92∘\delta_0 = \arcsin(0.6/1.761) = 19.92^\circ), δmax⁡\delta_{\max}, δcr\delta_{cr} and tcrt_{cr}.

Simulation. Change Pm (and d0) in the Python cell and confirm the closed-form and bisection times agree, then plot tcrt_{cr} against PmP_m from 0.20.2 to 1.0 pu1.0\ \text{pu}.

What an engineer would measure. Nobody tests transient stability by faulting a power station on purpose; it is checked in planning studies with full dynamic models, and against disturbance records. Phasor measurement units (PMUs, IEEE/IEC 60255-118-1) sampling at 5050 frames per second record the angle swings after real faults; a utility compares those records with its simulations, typically to within a few degrees of first-swing amplitude and 55 to 10 %10\ \% in swing frequency.

Hazards and safe setup. Desk study only.

Pitfalls

  • Using δmax⁡\delta_{\max} of the pre-fault curve. The deceleration area ends on the post-fault curve.
  • Applying the closed-form time when Pmax⁡,2>0P_{\max,2} > 0. The rotor no longer accelerates uniformly; integrate.
  • Multi-machine systems. Equal area applies to one machine against an infinite bus (or two machines); larger systems need time-domain simulation or energy-function methods.
  • Ignoring damping and controls. Equal area is a first-swing check; later swings can still grow.

Practice

  1. P1 with both lines restored after clearing (Pmax⁡,3=1.761P_{\max,3} = 1.761) and a bolted fault at the HV bus. Find δmax⁡\delta_{\max} and δcr\delta_{cr}.
  2. If P1's inertia were doubled, what would tcrt_{cr} be for the bolted HV-bus fault?
  3. Why does single-phase faulting leave more margin than a three-phase fault at the same place?
Answer
  1. δmax⁡=180∘−arcsin⁡(0.8/1.761)=152.98∘\delta_{\max} = 180^\circ - \arcsin(0.8/1.761) = 152.98^\circ (2.670 rad2.670\ \text{rad}); cos⁡δcr=(0.8(2.670−0.4715)+1.761cos⁡152.98∘)/1.761=(1.7588−1.5689)/1.761=0.1078\cos\delta_{cr} = (0.8(2.670 - 0.4715) + 1.761\cos 152.98^\circ)/1.761 = (1.7588 - 1.5689)/1.761 = 0.1078, δcr=83.8∘\delta_{cr} = 83.8^\circ.
  2. tcr∝Ht_{cr} \propto \sqrt{H}: 0.229⋅2=0.324 s0.229 \cdot \sqrt{2} = 0.324\ \text{s}.
  3. The two healthy phases keep carrying power, so Pmax⁡,2P_{\max,2} during the fault is far above zero and the accelerating area is smaller.

Test yourself

The equal-area criterion states that the first swing is stable if…

  1. PmP_m is below Pmax⁡,1P_{\max,1}
  2. the decelerating area available after clearing is at least the accelerating area
  3. the fault current is below breaker rating
  4. the angle stays below 90°

For a bolted fault with zero power transfer, tcrt_{cr} scales with the inertia constant as…

  1. HH
  2. H\sqrt{H}
  3. 1/H1/H
  4. it does not depend on HH

P1's critical clearing time for the bolted HV-bus fault is about…

  1. 0.10 s
  2. 0.23 s
  3. 0.43 s
  4. 1.1 s

Which measure improves first-swing stability by shrinking the accelerating area A1A_1, rather than by raising the post-fault power curve?

  1. keeping more parallel lines in service after the fault
  2. series capacitors on the line
  3. faster fault clearing
  4. higher post-fault voltage